2012 International Mechanical Code 7th Printing February 2019
N INTERNATIONAL CODE COUNCIL° INTERNATIONAL MECHANICAL CODE A Member of the International Code Family® INTERNATIONAL MECHANICAL CODE A Member of the International Code Family° I 1AC 0 Become a Building Safety Professional Member and Learn More about the Code Council GO TO W W W.ICCSAFE.ORG for All You r Technical and Professional Needs Including: > Codes, Standards and Guidelines > Membership Benefits ation >Comm Communications onIndust > Communications on Industry News Cop 1@m11 Asp by aoO—w—1��M.=1 o..,eM aw p.��m�sAM.�,..w��« arero ee.�omnm Aa, m��mma .re�M oa��na000moNosou-re�eunoNMAV�o—OEnff MnmA,.we�.re�O�rrAOrwO—C— C— 2012 International Mechanical Code® First Printing April 2011 Second Printing June 2011 Third Printing September 2013 Fourth Pnnnng December 2013 Fifth Printing November 2014 Sixth Printing April 2018 Seventh Pnnhng February2019 ISBN: 978-1-60983-051-9 (soft-cover edition) ISBN: 978-1-60983-050-2 (loose-leaf edition) COPYRIGHT © 2011 by INTERNATIONAL CODE COUNCIL, INC ALL RIGHTS RESERVED This 2012International Mechanical Code® is a copyrighted work owned by the International Code Council, Inc (ICC) Without advance written permission from the ICC, no part of this book maybe reproduced, distributed or transmitted many form or by any means, including, without limitation, electromc, optical or mechanical means (byway of exam- ple, and not limitation, photocopying, or recording by or man information storage retrieval system) For information on use rights and permissions, please contact ICC Publications, 4051 Flossmoor Road, Country Club Hills, IL 60478 Phone 1-888-ICC-SAFE (422-7233) Trademarks "International Code Council," the "International Code Council' logo, "ICC," the "ICC' logo, "International Mechanical Code," " IMC and other names and trademarks appearing in this book are registered trademarks of the International Code Council, Inc , and/or its licensors (as applicable), and may not be used without permission T023540 PRINTED IN THE USA CopyngbtOO ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 201901 av PM(PDT) p—Potto I»eAge mt,oUICC No FYUP ep,od Utoa oAYUP, "eFod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single.--1, mpymg Pod.Nyodmg F oARbtAd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Introduction Development Adoption PREFACE Internationally, code officials recognize the need for a modern, up-to-date mechanical code addressing the design and installation of mechanical systems through requirements emphasizing performance. The International Mechanical Code', in this 2012 edition, is designed to meet these needs through model code regulations that safeguard the public health and safety in all communi- ties, large and small. This comprehensive mechanical code establishes minimum regulations for mechanical systems using prescriptive and performance -related provisions. It is founded on broad -based principles that make possible the use of new materials and new mechanical designs. This 2012 edition is fully com- patible with all of the International Codes (I -Codes°) published by the International Code Council (ICC), including the International Building Code', International Energy Conservation Code', Interna- tional Existing Building Code" International Fire Code" International Fuel Gas Code" International Green Construction Code TM (to be available March 2012), International Plumbing Code°, ICC Perfor- mance Code°, International Private Sewage Disposal Code" International Property Maintenance Code`, International Residential Code°, International Swimming Pool and Spa Code TM (to be avail- able March 2012), International Urban-Wildland Interface Code and International Zoning Code". The International Mechanical Code provisions provide many benefits, among which is the model code development process that offers an international forum for mechanical professionals to dis- cuss performance and prescriptive code requirements. This forum provides an excellent arena to debate proposed revisions. This model code also encourages international consistency in the appli- cation of provisions. The first edition of the International Mechanical Code (1996) was the culmination of an effort initi- ated in 1994 by a development committee appointed by the ICC and consisting of representatives of the three statutory members of the International Code Council at that time, including: Building Offi- cials and Code Administrators International, Inc. (BOCA), International Conference of Building Offi- cials (ICBO) and Southern Building Code Congress International (SBCCI). The intent was to draft a comprehensive set of regulations for mechanical systems consistent with and inclusive of the scope of the existing model codes. Technical content of the latest model codes promulgated by BOCA, ICBO and SBCCI was utilized as the basis for the development. This 2012 edition presents the code as originally issued, with changes approved through the ICC Code Development Process through 2010. A new edition such as this is promulgated every 3 years. This code is founded on principles intended to establish provisions consistent with the scope of a mechanical code that adequately protects public health, safety and welfare; provisions that do not unnecessarily increase construction costs; provisions that do not restrict the use of new materials, products or methods of construction; and provisions that do not give preferential treatment to par- ticular types or classes of materials, products or methods of construction. The International Mechanical Code is available for adoption and use byjurisdictions internationally. Its use within a governmental jurisdiction is intended to be accomplished through adoption by ref- erence in accordance with proceedings establishing the jurisdiction's laws. At the time of adoption, jurisdictions should insert the appropriate information in provisions requiring specific local informa- tion, such as the name of the adopting jurisdiction. These locations are shown in bracketed words in small capital letters in the code and in the sample ordinance. The sample adoption ordinance on page xi addresses several key elements of a code adoption ordinance, including the information required for insertion into the code text. 2012 INTERNATIONAL MECHANICAL CODE® III I " ' Copy,ght @ zoI I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep so.2.o190147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,oddtoa oAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Maintenance The International Mechanical Code is kept up to date through the review of proposed changes sub- mitted by code enforcing officials, industry representatives, design professionals and other inter- ested parties. Proposed changes are carefully considered through an open code development process in which all interested and affected parties may participate. The contents of this work are subject to change both through the Code Development Cycles and the governmental body that enacts the code into law. For more information regarding the code development process, contact the Codes and Standards Development Department of the Interna- tional Code Council. While the development procedure of the International Mechanical Code assures the highest degree of care, ICC and ICC's members and those participating in the development of this code do not accept any liability resulting from compliance or noncompliance with the provisions because ICC and its members do not have the power or authority to police or enforce compliance with the con- tents of this code. Only the governmental body that enacts the code into law has such authority. Code Development Committee Responsibilities (Letter Designations in Front of Section Numbers) In each code development cycle, proposed changes to this code are considered at the Code Devel- opment Hearing by the International Mechanical Code Development Committee. Proposed changes to a code section whose number begins with a letter in brackets are considered by a different code development committee. For instance, proposed changes to code sections which have the letter [B] in front (for example, [B] 309.1), are considered by one of the International Building Code develop- ment committees (IBC -General) at the Code Development Hearing. The content of sections in this code which begin with a letter designation is maintained by another code development committee in accordance with the following: [A] = Administrative Code Development Committee; [B] = International Building Code Development Committee (IBC —Fire Safety, General, Means of Egress or Structural); [EC] = International Energy Conservation Code Development Committee; [F] = International Fire Code Development Committee; and [FG] = International Fuel Gas Code Development Committee. iv 2012 INTERNATIONAL MECHANICAL CODE® "TITP-1CoTy,ght @ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx 100760189 oc Sep SO,2019 o 1 av PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( ,Fod,Yo,,bymytl,dputy,o,ANb�to,au o,sd Single —oPIA PTymg anodmgp� dortuokbad ANY UNAUTHORIZED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,EDERAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Note that, for the development of the 2015 edition of the I -Codes, there will be two groups of code development committees and they will meet in separate years. The groupings are as follows: Group A Codes (Heard in 2012, Code Change Proposals Deadline: January 3, 2012) Group B Codes (Heard in 2013, Code Change Proposals Deadline: January 3, 2013) International Building Code Administrative Provisions (Chapter 1 all codes except IRC and ICC PC, administrative updates to currently ref- erenced standards, and designated definitions) International Fuel Gas Code International Energy Conservation Code International Mechanical Code International Existing Building Code International Plumbing Code International Fire Code International Private Sewage Disposal Code International Green Construction Code ICC Performance Code International Property Maintenance Code International Residential Code International Swimming Pool and Spa Code International Wildland-Urban Interface Code International Zoning Code Code change proposals submitted for code sections that have a letter designation in front of them will be heard by the respective committee responsible for such code sections. Because differ- ent committees will meet in different years, it is possible that some proposals for this code will be heard by a committee in a differentyear than the year in which the primary committee for this code meets. For example, every section of Chapter 1 of this code is designated as the responsibility of the Administrative Code Development Committee, and that committee is part of the Group B code hearings. This committee will conduct its code development hearings in 2013 to consider all code change proposals for Chapter 1 of this code and proposals for Chapter 1 of all I -Codes. Therefore, any proposals received for Chapter 1 of this code will be deferred for consideration in 2013 by the Administrative Code Development Committee. Another example is Section 606.4 of this code which is designated as the responsibility of the International Fire Code Development Committee. This committee will conduct its code develop- ment hearings in 2013 to consider code change proposals in its purview, which includes any propos- als to Section 606.4. In some cases, another committee in Group A will be responsible for a section of this code. For example, Section 607.3 has a [B] in front of the numbered section, indicating that this section of the code is the responsibility of one of the International Building Code Development Committees. The International Building Code is in Group A; therefore, any code change proposals to this section will be due before the Group A deadline of January 3, 2012, and these code change proposals will be assigned to the appropriate International Building Code Development Committee for consideration. It is very important that anyone submitting code change proposals understand which code devel- opment committee is responsible for the section of the code that is the subject of the code change proposal. For further information on the code development committee responsibilities, please visit the ICC web site at www.iccsafe.org/scoping. 2012 INTERNATIONAL MECHANICAL CODE® v I " ' CoTy,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nomb,x1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo,,bymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Marginal Markings Italicized Terms Solid vertical lines in the margins within the body of the code indicate a technical change from the requirements of the 2009 edition. Deletion indicators (m*) are provided in the margin where an entire section, paragraph, exception or table has been deleted or an item in a list of items or in a table has been deleted. Selected terms set forth in Chapter 2, Definitions, are italicized where they appear in code text. Such terms are not italicized where the definition set forth in Chapter 2 does not impart the intended meaning in the use of the term. The terms selected have definitions which the user should read carefully to facilitate better understanding of the code. vi 2012 INTERNATIONAL MECHANICAL CODE® '' ' Copy,ghtOoON I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.no—oAYUP, iff S I ( N ,FodmYo,,bymytl,dputy,o,Abau�to,o,sd Smglo oPIA PTymg and-Pyodmg Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Effective Use of the International Mechanical Code The International Mechanical Code' (IMC°) is a model code that regulates the design and installa- tion of mechanical systems, appliances, appliance venting, duct and ventilation systems, combus- tion air provisions, hydronic systems and solar systems. The purpose of the code is to establish the minimum acceptable level of safety and to protect life and property from the potential dangers associated with the installation and operation of mechanical systems. The code also protects the personnel that install, maintain, service and replace the systems and appliances addressed by this code. The IMC is primarily a prescriptive code with some performance text. The code relies heavily on product specifications and listings to provide much of the appliance and equipment installation requirements. The general Section 105.2 and the exception to Section 403.2 allow designs and installations to be performed by approved engineering methods as alternatives to the prescriptive methods in the code. The format of the IMC allows each chapter to be devoted to a particular subject with the excep- tion of Chapter 3, which contains general subject matters that are not extensive enough to warrant their own independent chapter. Chapter 1 Scope and Administration. Chapter 1 establishes the limits of applicability of the code and describes how the code is to be applied and enforced. A mechanical code, like any other code, is intended to be adopted as a legally enforceable document and it cannot be effective without ade- quate provisions for its administration and enforcement. The provisions of Chapter 1 establish the authority and duties of the code official appointed by the jurisdiction having authority and also establish the rights and privileges of the design professional, contractor and property owner. Chapter 2 Definitions. Chapter 2 is the repository of the definitions of terms used in the body of the code. Codes are technical documents and every word and term can impact the meaning of the code text and the intended results. The code often uses terms that have a unique meaning in the code and the code meaning can differ substantially from the ordinarily understood meaning of the term as used outside of the code. The terms defined in Chapter 2 are deemed to be of prime importance in establishing the mean- ing and intent of the code text that uses the terms. The user of the code should be familiar with and consult this chapter because the definitions are essential to the correct interpretation of the code and because the user may not be aware that a term is defined. Chapter 3 General Regulations. Chapter 3 contains broadly applicable requirements related to appliance location and installation, appliance and systems access, protection of structural elements, condensate disposal and clearances to combustibles, among others. Chapter 4 Ventilation. Chapter 4 includes means for protecting building occupant health by control- ling the quality of indoor air and protecting property from the effects of inadequate ventilation. In some cases, ventilation is required to prevent or reduce a health hazard by removing contaminants at their source. Ventilation is both necessary and desirable for the control of air contaminants, moisture and temperature. Habitable and occupiable spaces are ventilated to promote a healthy and comfortable environment for the occupants. Uninhabited and unoccupied spaces are ventilated to protect the building structure from the harmful effects of excessive humidity and heat. Ventilation of specific occupancies is necessary to minimize the potential for toxic or otherwise harmful substances to reach dangerously high concentrations in air. 2012 INTERNATIONAL MECHANICAL CODE® vii I II I CoTy,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Chapter 5 Exhaust Systems. Chapter 5 provides guidelines for reasonable protection of life, prop- erty and health from the hazards associated with exhaust systems, air contaminants and smoke development in the event of a fire. In most cases, these hazards involve materials and gases that are flammable, explosive, toxic or otherwise hazardous. Where contaminants are known to be present in quantities that are irritating or harmful to the occupants' health or are hazardous in a fire, both naturally and mechanically ventilated spaces must be equipped with mechanical exhaust systems capable of collecting and removing the contaminants. This chapter contains requirements for the installation of exhaust systems, with an emphasis on the structural integrity of the systems and equipment involved and the overall impact of the sys- tems on the fire safety performance of the building. It includes requirements for the exhaust of commercial kitchen grease- and smoke -laden air, hazardous fumes and toxic gases, clothes dryer moisture and heat and dust, stock and refuse materials. Chapter 6 Duct Systems. Chapter 6 of the code regulates the materials and methods used for con- structing and installing ducts, plenums, system controls, exhaust systems, fire protection systems and related components that affect the overall performance of a building's air distribution system and the reasonable protection of life and property from the hazards associated with air -moving equipment and systems. This chapter contains requirements for the installation of supply, return and exhaust air systems. Specific exhaust systems are also addressed in Chapter 5. Information on the design of duct systems is limited to that in Section 603.2. The code is very much concerned with the structural integrity of the systems and the overall impact of the systems on the fire safety and life safety performance of the building. Design considerations such as duct sizing, maximum effi- ciency, cost effectiveness, occupant comfort and convenience are the responsibility of the design professional. The provisions for the protection of duct penetrations of wall, floor, ceiling and roof assemblies are extracted from the International Building Code. Chapter 7 Combustion Air. Complete combustion of solid and liquid fuel is essential for the proper operation of appliances, for control of harmful emissions and for achieving maximum fuel effi- ciency. The specific combustion air requirements provided in previous editions of the code have been deleted in favor of a single section that directs the user to NFPA 31 for oil -fired appliance combus- tion air requirements and the manufacturer's installation instructions for solid -fuel burning appli- ances. For gas -fired appliances, the provisions of the International Fuel Gas Code are applicable. Chapter 8 Chimneys and Vents. Chapter 8 is intended to regulate the design, construction, installa- tion, maintenance, repair and approval of chimneys, vents and their connections to solid and liquid fuel -burning appliances. The requirements of this chapter are intended to achieve the complete removal of the products of combustion from fuel -burning appliances and equipment. This chapter includes regulations for the proper selection, design, construction and installation of a chimney or vent, along with appropriate measures to minimize the related potential fire hazards. A chimney or vent must be designed for the type of appliance or equipment it serves. Chimneys and vents are designed for specific applications depending on the flue gas temperatures and the type of fuel being burned in the appliance. Chimneys and vents for gas -fired appliances are covered in the Interna- tional Fuel Gas Code. Chapter 9 Specific Appliances, Fireplaces and Solid Fuel -burning Equipment. Chapter 9 sets mini- mum construction and performance criteria for fireplaces, appliances and equipment and provides for the safe installation of these items. It reflects the code's intent to specifically address all of the types of appliances that the code intends to regulate. Other regulations affecting the installation of solid fuel -burning fireplaces, appliances and accessory appliances are found in Chapters 3, 6, 7, 8, 10, 11, 12, 13 and 14. viii 2012 INTERNATIONAL MECHANICAL CODE® I I Copy,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO,2019 o 1 av PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,od U:oa oAYUP, S I ( ,Fod,Y,,bymytl,dputy,o,ANb�to,au o,sd Single—mlympymg andortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDERAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Chapter 10 Boilers, Water Heaters and Pressure Vessels. Chapter 10 presents regulations for the proper installation of boilers, water heaters and pressure vessels to protect life and property from the hazards associated with those appliances and vessels. It applies to all types of boilers and pres- sure vessels, regardless of size, heat input, operating pressure or operating temperature. Because pressure vessels are closed containers designed to contain liquids, gases or both under pressure, they must be designed and installed to prevent structural failures that can result in extremely hazardous situations. Certain safety features are therefore provided in Chapter 10 to reduce the potential for explosion hazards. Chapter 11 Refrigeration. Chapter 11 contains regulations pertaining to the life safety of building occupants. These regulations establish minimum requirements to achieve the proper design, con- struction, installation and operation of refrigeration systems. Refrigeration systems are a combina- tion of interconnected components and piping assembled to form a closed circuit in which a refrigerant is circulated. The system's function is to extract heat from a location or medium, and to reject that heat to a different location or medium. This chapter establishes reasonable safeguards for the occupants by defining and mandating practices that are consistent with the practices and experience of the industry. Chapter 12 Hydronic Piping. Hydronic piping includes piping, fittings and valves used in building space conditioning systems. Applications include hot water, chilled water, steam, steam conden- sate, brines and water/antifreeze mixtures. Chapter 12 contains the provisions that govern the con- struction, installation, alteration and repair of all hydronic piping systems that affect reliability, serviceability, energy efficiency and safety. Chapter 13 Fuel Oil Piping and Storage. Chapter 13 regulates the design and installation of fuel oil storage and piping systems. The regulations include reference to construction standards for above- ground and underground storage tanks, material standards for piping systems (both above -ground and underground) and extensive requirements for the proper assembly of system piping and com- ponents. The International Fire Code (IFC) covers subjects not addressed in detail here. The provi- sions in this chapter are intended to prevent fires, leaks and spills involving fuel oil storage and piping systems. Chapter 14 Solar Systems. Chapter 14 establishes provisions for the safe installation, operation and repair of solar energy systems used for space heating or cooling, domestic hot water heating or pro- cessing. Although such systems use components similar to those of conventional mechanical equip- ment, many of these provisions are unique to solar energy systems. Chapter 15 Referenced Standards. Chapter 15 lists all of the product and installation standards and codes that are referenced throughout Chapters 1 through 14. As stated in Section 102.8, these stan- dards and codes become an enforceable part of the code (to the prescribed extent of the reference) as if printed in the body of the code. Chapter 15 provides the full title and edition year of the stan- dards and codes in addition to the address of the promulgators and the section numbers in which the standards and codes are referenced. Appendix A Chimney Connector Pass-throughs. Appendix A provides figures that illustrate various requirements in the body of the code. Figure A-1 illustrates the chimney connector clearance requirements of Table 803.10.4. Appendix B Recommended Permit Fee Schedule. Appendix B provides a sample permit fee sched- ule for mechanical permits. The local jurisdiction can adopt this appendix and fill in the dollar amounts in the blank spaces to establish their official permit fee schedule. The ICC does not estab- lish permit fees because the code is adopted throughout the country and there are vast differences in operating budgets between different parts of the country, as well as between large and small municipalities within the same region. 2012 INTERNATIONAL MECHANICAL CODE® ix I II I Copy,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo,,bymytl,dputy,o,ANb,to,au o,sd Single —ooly mpymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by (). (-) O,d¢ Nombs x 100760189 oc Sep V,2o1901 av PM (PDT)pwmmtto I»eAg—mt,oU ICC No FYUP,,eplod dtoo.00 AYUP, eFod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single—mlympymg mdortuodmg F oARItAd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER LEGISLATION The International Codes are designed and promulgated to be adopted by reference by legislative action. Jurisdictions wishing to adopt the 2012 International Mechanical Code as an enforceable regulation governing plumbing systems should ensure that cer- tain factual information is included in the adopting legislation at the time adoption is being considered by the appropriate gov- ernmental body. The following sample adoption legislation addresses several key elements, including the information required for insertion into the code text. SAMPLE LEGISLATION FOR ADOPTION OF THE INTERNATIONAL MECHANICAL CODE ORDINANCE NO. A[N] [ORDINANCE/STATUTE/REGULATION] of the [JURISDICTION] adopting the 2012 edition of the International Mechanical Code, regulating and governing the design, construction, quality of materials, erection, installation, alteration, repair, location, relocation, replacement, addition to, use or maintenance of mechanical systems in the [JURISDICTION]; providing for the issuance of permits and collection of fees therefor; repealing [ORDINANCE/STATUTE/REGULATION] No. of the [JURISDICTION] and all other ordinances or parts of laws in conflict therewith. The [GOVERNING BODY] of the [JURISDICTION] does ordain as follows: Section 1. That a certain document, three (3) copies of which are on file in the office of the [TITLE OF JURISDICTION'S KEEPER OF RECORDS] of [NAME OF JURISDICTION], being marked and designated as the International Mechanical Code, 2012 edition, including Appendix Chapters [FILL IN THE APPENDIX CHAPTERS BEING ADOPTED], as published by the International Code Coun- cil, be and is hereby adopted as the Mechanical Code of the [JURISDICTION], in the State of [STATE NAME] regulating and govern- ing the design, construction, quality of materials, erection, installation, alteration, repair, location, relocation, replacement, addition to, use or maintenance of mechanical systems as herein provided; providing for the issuance of permits and collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions and terms of said Mechanical Code on file in the office of the [JURISDICTION] are hereby referred to, adopted, and made a part hereof, as if fully set out in this legislation, with the additions, insertions, deletions and changes, if any, prescribed in Section 2 of this ordinance. Section 2. The following sections are hereby revised: Section 101.1. Insert: [NAME OF JURISDICTION] Section 106.5.2. Insert: [APPROPRIATE SCHEDULE] Section 106.5.3. Insert: [PERCENTAGES IN TWO LOCATIONS] Section 108.4. Insert: [OFFENSE, DOLLAR AMOUNT, NUMBER OF DAYS] Section 108.5. Insert: [DOLLAR AMOUNT IN TWO LOCATIONS] Section 3. That [ORDINANCE/STATUTE/REGULATION] No. of [JURISDICTION] entitled [FILL IN HERE THE COMPLETE TITLE OF THE LEGISLATION OR LAWS IN EFFECT AT THE PRESENT TIME SO THAT THEY WILL BE REPEALED BY DEFINITE MEN- TION] and all other ordinances or parts of laws in conflict herewith are hereby repealed. Section 4. That if any section, subsection, sentence, clause or phrase of this legislation is, for any reason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this ordinance. The [GOVERNING BODY] hereby declares that it would have passed this law, and each section, subsection, clause or phrase thereof, irrespective of the fact that any one or more sections, subsections, sentences, clauses and phrases be declared unconstitutional. Section 5. That nothing in this legislation or in the Mechanical Code hereby adopted shall be construed to affect any suit or pro- ceeding impending in any court, or any rights acquired, or liability incurred, or any cause or causes of action acquired or exist- ing, under any act or ordinance hereby repealed as cited in Section 2 of this law; nor shall any just or legal right or remedy of any character be lost, impaired or affected by this legislation. Section 6. That the [JURISDICTION'S KEEPER OF RECORDS] is hereby ordered and directed to cause this legislation to be pub- lished. (An additional provision may be required to direct the number of times the legislation is to be published and to specify that it is to be in a newspaper in general circulation. Posting may also be required.) Section 7. That this law and the rules, regulations, provisions, requirements, orders and matters established and adopted hereby shall take effect and be in full force and effect [TIME PERIOD] from and after the date of its final passage and adoption. 2012 INTERNATIONAL MECHANICAL CODE® xi I [ [ [ C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1 av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyodmg FoIRbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER xii 2012 INTERNATIONAL MECHANICAL CODE® 17i''' Co,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I (eFodmYo,,bymytl,dputy,o,ANb�to,au o,sd Smglo mlymp,YE mdoehuodmg Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER TABLE OF CONTENTS CHAPTER 1 SCOPE AND ADMINISTRATION .... 1 PART 1—SCOPE AND APPLICATION ............. 1 Section 101 General..................................1 102 Applicability ..............................I PART 2ADMINISTRATION AND ENFORCEMENT ................................ 2 103 Department of Mechanical Inspection .......... 2 104 Duties and Powers of the Code Official......... 2 105 Approval.................................3 106 Permits..................................3 107 Inspections and Testing ..................... 5 108 Violations................................6 109 Means of Appeal ...........................7 110 Temporary Equipment, Systems and Uses....... 8 CHAPTER 2 DEFINITIONS ..................... 9 Section 201 General..................................9 202 General Definitions ........................ 9 CHAPTER 3 GENERAL REGULATIONS ........ 21 Section 301 General.................................21 302 Protection of Structure ..................... 22 303 Equipment and Appliance Location........... 23 304 Installation .............................. 23 305 Piping Support ...........................25 306 Access and Service Space .................. 25 307 Condensate Disposal ......................27 308 Clearance Reduction .......................28 309 Temperature Control ...................... 28 310 Explosion Control .........................28 311 Smoke and Heat Vents ..................... 29 312 Heating and Cooling Load Calculations ........................... 29 CHAPTER 4 VENTILATION ................... 31 Section 401 General.................................31 402 Natural Ventilation ........................ 31 403 Mechanical Ventilation .................... 32 404 Enclosed Parking Garages .................. 37 405 Systems Control .......................... 37 406 Ventilation of Uninhabited Spaces ........... 38 CHAPTER 5 EXHAUST SYSTEMS .............. 39 Section 501 General ................................. 39 502 Required Systems ......................... 40 503 Motors and Fans .......................... 46 504 Clothes Dryer Exhaust.....................46 505 Domestic Kitchen Exhaust Equipment ........ 48 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment ...... 48 507 Commercial Kitchen Hoods ................. 53 508 Commercial Kitchen Makeup Air ............ 55 509 Fire Suppression Systems .................. 56 510 Hazardous Exhaust Systems ................ 56 511 Dust, Stock and Refuse Conveying Systems.... 58 512 Subslab Soil Exhaust Systems ............... 59 513 Smoke Control Systems .................... 59 514 Energy Recovery Ventilation Systems ........ 63 CHAPTER 6 DUCT SYSTEMS .................. 65 Section 601 General ................................. 65 602 Plenums ................................ 66 603 Duct Construction and Installation ........... 67 604 Insulation ............................... 69 605 Air Filters...............................70 606 Smoke Detection Systems Control ........... 70 607 Duct and Transfer Openings ................ 71 CHAPTER 7 COMBUSTION AIR ............... 77 Section 701 General ................................. 77 CHAPTER 8 CHIMNEYS AND VENTS .......... 79 Section 801 General ................................. 79 802 Vents..................................80 803 Connectors..............................81 2012 INTERNATIONAL MECHANICAL CODE® xiii I " ' Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,FodmYo¢ebymytl,dputy,o,ANb,to,au o,sd SmgIP ooIympymg Pod.Nyodmg F oARbtAd ANY VNAVTHORIVED REPRODUCTION ORDISIRIBVTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER TABLE OF CONTENTS 804 Direct -vent, Integral Vent and Mechanical Draft Systems ..........................82 805 Factory -built Chimneys .................... 83 806 Metal Chimneys ..........................84 CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL - BURNING EQUIPMENT ........... 85 Section 901 General.................................85 902 Masonry Fireplaces ....................... 85 903 Factory -built Fireplaces .................... 85 904 Pellet Fuel -burning Appliances .............. 85 905 Fireplace Stoves and Room Heaters........... 85 906 Factory -built Barbecue Appliances ........... 85 907 Incinerators and Crematories ................ 85 908 Cooling Towers, Evaporative Condensers and Fluid Coolers ............. 85 909 Vented Wall Furnaces ..................... 86 910 Floor Furnaces ...........................86 911 Duct Furnaces ............................86 912 Infrared Radiant Heaters .................... 86 913 Clothes Dryers ...........................86 914 Sauna Heaters ............................87 915 Engine and Gas Turbine -powered Equipment and Appliances................87 916 Pool and Spa Heaters......................87 917 Cooking Appliances .......................87 918 Forced -air Warm -air Furnaces...............88 919 Conversion Burners .......................89 920 Unit Heaters .............................89 921 Vented Room Heaters ...................... 89 922 Kerosene and Oil -fired Stoves ............... 89 923 Small Ceramic Kilns ....................... 89 924 Stationary Fuel Cell Power Systems .......... 89 925 Masonry Heaters ..........................89 926 Gaseous Hydrogen Systems.................89 927 Radiant Heating Systems ................... 89 928 Evaporative Cooling Equipment ............. 90 CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS ......... 91 Section 1001 General.................................91 1002 Water Heaters ............................91 1003 Pressure Vessels ..........................91 1004 Boilers ................................. 91 1005 Boiler Connections ........................ 92 1006 Safety and Pressure Relief Valves and Controls ........................... 92 1007 Boiler Low-water Cutoff ................... 93 1008 Steam Blowoff Valve ...................... 93 1009 Hot Water Boiler Expansion Tank............ 93 1010 Gauges ................................. 93 1011 Tests ................................... 93 CHAPTER 11 REFRIGERATION ................ 95 Section 1101 General ................................. 95 1102 System Requirements ...................... 95 1103 Refrigeration System Classification........... 96 1104 System Application Requirements........... 101 1105 Machinery Room, General Requirements ..... 102 1106 Machinery Room, Special Requirements...... 103 1107 Refrigerant Piping .......................103 1108 Field Test..............................105 1109 Periodic Testing .........................105 CHAPTER 12 HYDRONIC PIPING .............. 107 Section 1201 General................................107 1202 Material ............................... 107 1203 Joints and Connections ................... 108 1204 Pipe Insulation ..........................110 1205 Valves.................................110 1206 Piping Installation ....................... 110 1207 Transfer Fluid ...........................III 1208 Tests..................................III 1209 Embedded Piping ........................III CHAPTER 13 FUEL OIL PIPING AND STORAGE .................. 113 Section 1301 General................................113 1302 Material ............................... 113 1303 Joints and Connections ................... 113 1304 Piping Support ..........................114 1305 Fuel Oil System Installation ................ 114 1306 Oil Gauging ............................115 1307 Fuel Oil Valves ......................... 115 1308 Testing................................115 xiv 2012 INTERNATIONAL MECHANICAL CODE® ''TT ' ' Copy,ghtOo O N I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO,2019 o 1 av PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( [,Fod Uto,,by POVO d party. o,±RYb�toc P,,Uoosd SmgIP oPIA Tymg Pod o NyodmgFoARbtAd ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPER REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER TABLE OF CONTENTS CHAPTER 14 SOLAR SYSTEMS ................ 117 Section 1401 General................................117 1402 Installation ............................. 117 1403 Heat Transfer Fluids......................118 1404 Materials...............................118 CHAPTER 15 REFERENCED STANDARDS ...... 119 APPENDIX A CHIMNEY CONNECTOR PASS-THROUGHS ............... 127 APPENDIX B RECOMMENDED PERMIT FEE SCHEDULE ................. 129 INDEX.......................................131 2012 INTERNATIONAL MECHANICAL CODE® xv I " ' Co,gbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 100760189 oc Sep so.2.o190147 PM(PDT) pwmmtto IL eAg—mt,oUICC No FYUP,,eplodmeoo.00 AYUP, (,eFodmYo¢ebymytl,dputy,o,ANb,to,au o,sd Emgle®lympymg Podortuodmg F oARItAd ANY VNAVTHORIVED REPRODUCTION ORDISIRIBVTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER xvi 2012 INTERNATIONAL MECHANICAL CODE® Co,gbtOO ON I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT) pwmmtto IL eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I (eFodmYo,,bymytl,dputy,o,ANb�to,au o,sd Smglo mlympymg and-PyodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDRRAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER1 SCOPE AND ADMINISTRATION PART 1—SCOPE AND APPLICATION SECTION 101 GENERAL [A] 101.1 Title. These regulations shall be known as the Mechanical Code of [NAME OF JURISDICTION], hereinafter referred to as "this code." [A] 101.2 Scope. This code shall regulate the design, installa- tion, maintenance, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechani- cal systems, system components, equipment and appliances specifically addressed herein. The installation of fuel gas dis- tribution piping and equipment, fuel gas -fired appliances and fuel gas -fired appliance venting systems shall be regulated by the International Fuel Gas Code. Exception: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the Interna- tional Residential Code. [A] 101.2.1 Appendices. Provisions in the appendices shall not apply unless specifically adopted. [A] 101.3 Intent. The purpose of this code is to provide min- imum standards to safeguard life or limb, health, property and public welfare by regulating and controlling the design, con- struction, installation, quality of materials, location, operation and maintenance or use of mechanical systems. [A] 101.4 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any reason, held to be unconstitutional, such decision shall not affect the validity of the remaining portions of this code. SECTION 102 APPLICABILITY [A] 102.1 General. Where there is a conflict between a gen- eral requirement and a specific requirement, the specific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. [A] 102.2 Existing installations. Except as otherwise pro- vided for in this chapter, a provision in this code shall not require the removal, alteration or abandonment of, nor pre- vent the continued utilization and maintenance of, a mechani- cal system lawfully in existence at the time of the adoption of this code. [A] 102.3 Maintenance. Mechanical systems, both existing and new, and parts thereof shall be maintained in proper oper- ating condition in accordance with the original design and in a safe and sanitary condition. Devices or safeguards which are required by this code shall be maintained in compliance with the code edition under which they were installed. The owner or the owner's designated agent shall be responsible for maintenance of mechanical systems. To determine com- pliance with this provision, the code official shall have the authority to require a mechanical system to be reinspected. The inspection for maintenance of HVAC systems shall be done in accordance with ASHRAE/ACCA/ANSI Standard 180. [A] 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to a mechanical system shall conform to that required for a new mechanical system without requiring the existing mechanical system to comply with all of the requirements of this code. Additions, altera- tions or repairs shall not cause an existing mechanical system to become unsafe, hazardous or overloaded. Minor additions, alterations, renovations and repairs to existing mechanical systems shall meet the provisions for new construction, unless such work is done in the same man- ner and arrangement as was in the existing system, is not haz- ardous and is approved. [A] 102.5 Change in occupancy. It shall be unlawful to make a change in the occupancy of any structure which will subject the structure to any special provision of this code applicable to the new occupancy without approval. The code official shall certify that such structure meets the intent of the provisions of law governing building construction for the proposed new occupancyand that such change of occupancy does not result in any hazard to the public health, safety or welfare. [A] 102.6 Historic buildings. The provisions of this code relating to the construction, alteration, repair, enlargement, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local jurisdiction as historic buildings when such buildings or structures are judged by the code official to be safe and in the public inter- est of health, safety and welfare regarding any proposed con- struction, alteration, repair, enlargement, restoration, relocation or moving of buildings. [A] 102.7 Moved buildings. Except as determined by Sec- tion 102.2, mechanical systems that are a part of buildings or structures moved into or within the jurisdiction shall comply with the provisions of this code for new installations. [A] 102.8 Referenced codes and standards. The codes and standards referenced herein shall be those that are listed in Chapter 15 and such codes and standards shall be considered 2012 INTERNATIONAL MECHANICAL CODE® 1 I II I C,Ty,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx100760189 oc Sep V,2019o1av PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg andortuodmg FoIRbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION as part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sec- tions 102.8.1 and 102.8.2. Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing and the manufac- turer's installation instructions shall apply. [A] 102.8.1 Conflicts. Where conflicts occur between pro- visions of this code and the referenced standards, the pro- visions of this code shall apply. [A] 102.8.2 Provisions in referenced codes and stan- dards. Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code, as applica- ble, shall take precedence over the provisions in the refer- enced code or standard. [A] 102.9 Requirements not covered by this code. Require- ments necessary for the strength, stability or proper operation of an existing or proposed mechanical system, or for the pub- lic safety, health and general welfare, not specifically covered by this code, shall be determined by the code official. [A] 102.10 Other laws. The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law. [A] 102.11 Application of references. Reference to chapter or section numbers, or to provisions not specifically identi- fied by number, shall be construed to refer to such chapter, section or provision of this code. PART 2—ADMINISTRATION AND ENFORCEMENT SECTION 103 DEPARTMENT OF MECHANICAL INSPECTION [A] 103.1 General. The department of mechanical inspection is hereby created and the executive official in charge thereof shall be known as the code official. [A] 103.2 Appointment The code official shall be appointed by the chief appointing authority of the jurisdiction. [A] 103.3 Deputies. In accordance with the prescribed proce- dures of this jurisdiction and with the concurrence of the appointing authority, the code official shall have the authority to appoint a deputy code official, other related technical offi- cers, inspectors and other employees. Such employees shall have powers as delegated by the code official. [A] 103.4 Liability. The code official, member of the board of appeals or employee charged with the enforcement of this code, while acting for the jurisdiction in good faith and with- out malice in the discharge of the duties required by this code or other pertinent law or ordinance, shall not thereby be ren- dered liable personally, and is hereby relieved from personal liability for any damage accruing to persons or property as a result of an act or by reason of an act or omission in the dis- charge of official duties. Any suit instituted against any officer or employee because of an act performed by that officer or employee in the lawful discharge of duties and under the provisions of this code shall be defended by the legal representative of the juris- diction until the final termination of the proceedings. The code official or any subordinate shall not be liable for costs in an action, suit or proceeding that is instituted in pursuance of the provisions of this code. SECTION 104 DUTIES AND POWERS OF THE CODE OFFICIAL [A] 104.1 General. The code official is hereby authorized and directed to enforce the provisions of this code. The code official shall have the authority to render interpretations of this code and to adopt policies and procedures in order to clarify the application of its provisions. Such interpretations, policies and procedures shall be in compliance with the intent and purpose of this code. Such policies and procedures shall not have the effect of waiving requirements specifically pro- vided for in this code. [A] 104.2 Applications and permits. The code official shall receive applications, review construction documents and issue permits for the installation and alteration of mechanical systems, inspect the premises for which such permits have been issued and enforce compliance with the provisions of this code. [A] 104.3 Inspections. The code official shall make all of the required inspections, or shall accept reports of inspection by approved agencies or individuals. All reports of such inspec- tions shall be in writing and be certified by a responsible offi- cer of such approved agency or by the responsible individual. The code official is authorized to engage such expert opinion as deemed necessary to report upon unusual technical issues that arise, subject to the approval of the appointing authority. [A] 104.4 Right of entry. Whenever it is necessary to make an inspection to enforce the provisions of this code, or when- ever the code official has reasonable cause to believe that there exists in a building or upon any premises any conditions or violations of this code which make the building or prem- ises unsafe, insanitary, dangerous or hazardous, the code offi- cial shall have the authority to enter the building or premises at all reasonable times to inspect or to perform the duties imposed upon the code official by this code. If such building or premises is occupied, the code official shall present cre- dentials to the occupant and request entry. If such building or premises is unoccupied, the code official shall first make a reasonable effort to locate the owner or other person having charge or control of the building or premises and request entry. If entry is refused, the code official has recourse to every remedy provided by law to secure entry. When the code official has first obtained a proper inspec- tion warrant or other remedy provided by law to secure entry, an owner or occupant or person having charge, care or control of the building or premises shall not fail or neglect, after proper request is made as herein provided, to promptly permit entry therein by the code official for the purpose of inspection and examination pursuant to this code. 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by (). (-) O,d,, Nmmbs x 100760189 oc Sep s o.2o1901 av PM (PDT)p—Potto I»eAg—mt,oU ICC No FYUP ep,od dtoa o AYUP, ,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION [A] 104.5 Identification. The code official shall carry proper identification when inspecting structures or premises in the performance of duties under this code. [A] 104.6 Notices and orders. The code official shall issue all necessary notices or orders to ensure compliance with this code. [A] 104.7 Department records. The code official shall keep official records of applications received, permits and certifi- cates issued, fees collected, reports of inspections, and notices and orders issued. Such records shall be retained in the official records for the period required for retention of public records. SECTION 105 APPROVAL [A] 105.1 Modifications. Whenever there are practical diffi- culties involved in carrying out the provisions of this code, the code official shall have the authority to grant modifica- tions for individual cases upon application of the owner or owner's representative, provided that the code official shall first find that special individual reason makes the strict letter of this code impractical and the modification is in compliance with the intent and purpose of this code and does not lessen health, life and fire safety requirements. The details of action granting modifications shall be recorded and entered in the files of the mechanical inspection department. [A] 105.2 Alternative materials, methods, equipment and appliances. The provisions of this code are not intended to prevent the installation of any material or to prohibit any method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material or method of construction shall be approved where the code official finds that the proposed design is satisfactory and complies with the intent of the pro- visions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. [A] 105.2.1 Research reports. Supporting data, where necessary to assist in the approval of materials or assem- blies not specifically provided for in this code, shall con- sist of valid research reports from approved sources. [A] 105.3 Required testing. Whenever there is insufficient evidence of compliance with the provisions of this code, or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the code official shall have the authority to require tests as evidence of compliance to be made at no expense to the jurisdiction. [A] 105.3.1 Test methods. Test methods shall be as speci- fied in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the code official shall approve the testing procedures. [A] 105.3.2 Testing agency. All tests shall be performed by an approved agency. [A] 105.3.3 Test reports. Reports of tests shall be retained by the code official for the period required for retention of public records. [A] 105.4 Approved materials and equipment. Materials, equipment and devices approved by the code official shall be constructed and installed in accordance with such approval. [A] 105.5 Material, equipment and appliance reuse. Mate- rials, equipment, appliances and devices shall not be reused unless such elements have been reconditioned, tested and placed in good and proper working condition and approved. SECTION 106 PERMITS [A] 106.1 When required. An owner, authorized agent or contractor who desires to erect, install, enlarge, alter, repair, remove, convert or replace a mechanical system, the installa- tion of which is regulated by this code, or to cause such work to be done, shall first make application to the code official and obtain the required permit for the work. Exception: Where equipment and appliance replacements or repairs must be performed in an emergency situation, the permit application shall be submitted within the next working business day of the department of mechanical inspection. [A] 106.2 Permits not required. Permits shall not be required for the following: 1. Portable heating appliances; 2. Portable ventilation appliances and equipment, 3. Portable cooling units; 4. Steam, hot water or chilled water piping within any heating or cooling equipment or appliances regulated by this code; 5. The replacement of any minor part that does not alter the approval of equipment or an appliance or make such equipment or appliance unsafe; 6. Portable evaporative coolers; 7. Self-contained refrigeration systems that contain 10 pounds (4.5 kg) or less of refrigerant, or that are actu- ated by motors of 1 horsepower (0.75 kW) or less; and 8. Portable fuel cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid. Exemption from the permit requirements of this code shall not be deemed to grant authorization for work to be done in violation of the provisions of this code or other laws or ordi- nances of this jurisdiction. [A] 106.3 Application for permit. Each application for a permit, with the required fee, shall be filed with the code offi- cial on a form furnished for that purpose and shall contain a general description of the proposed work and its location. The application shall be signed by the owner or an authorized agent. The permit application shall indicate the proposed occupancy of all parts of the building and of that portion of the site or lot, if any, not covered by the building or structure 2012 INTERNATIONAL MECHANICAL CODE® 3 I II I C,Ty,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION and shall contain such other information required by the code official. [A] 106.3.1 Construction documents. Construction doc- uments, engineering calculations, diagrams and other data shall be submitted in two or more sets with each applica- tion for a permit. The code official shall require construc- tion documents, computations and specifications to be prepared and designed by a registered design professional when required by state law. Where special conditions exist, the code official is authorized to require additional construction documents to be prepared by a registered design professional Construction documents shall be drawn to scale and shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that the work conforms to the provisions of this code. Construction documents for buildings more than two stories in height shall indicate where penetrations will be made for mechanical systems, and the materials and methods for maintaining required structural safety, fire - resistance rating and fireblocking. Exception: The code official shall have the authority to waive the submission of construction documents, cal- culations or other data if the nature of the work applied for is such that reviewing of construction documents is not necessary to determine compliance with this code. [A] 106.3.2 Preliminary inspection. Before a permit is issued, the code official is authorized to inspect and evalu- ate the systems, equipment, buildings, devices, premises and spaces or areas to be used. [A] 106.3.3 Time limitation of application. An applica- tion for a permit for any proposed work shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the code official shall have the authority to grant one or more extensions of time for additional periods not exceeding 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. [A] 106.4 Permit issuance. The application, construction documents and other data filed by an applicant for a permit shall be reviewed by the code official. If the code official finds that the proposed work conforms to the requirements of this code and all laws and ordinances applicable thereto, and that the fees specified in Section 106.5 have been paid, a per- mit shall be issued to the applicant. [A] 106.4.1 Approved construction documents. When the code official issues the permit where construction doc- uments are required, the construction documents shall be endorsed in writing and stamped "APPROVED." Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents. The code official shall have the authority to issue a per- mit for the construction of part of a mechanical system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed com- plying with all pertinent requirements of this code. The holder of such permit shall proceed at his or her own risk without assurance that the permit for the entire mechanical system will be granted. [A] 106.4.2 Validity. The issuance of a permit or approval of construction documents shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of other ordinances of the juris- diction. A permit presuming to give authority to violate or cancel the provisions of this code shall be invalid. The issuance of a permit based upon construction docu- ments and other data shall not prevent the code official from thereafter requiring the correction of errors in said construction documents and other data or from preventing building operations from being carried on thereunder when in violation of this code or of other ordinances of this jurisdiction. [A] 106.4.3 Expiration. Every permit issued by the code official under the provisions of this code shall expire by limitation and become null and void if the work authorized by such permit is not commenced within 180 days from the date of such permit, or if the work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days. Before such work recommences, a new permit shall be first obtained and the fee, therefore, shall be one-half the amount required for a new permit for such work, provided no changes have been made or will be made in the original construction documents for such work, and provided fur- ther that such suspension or abandonment has not exceeded one year. [A] 106.4.4 Extensions. A permittee holding an unexpired permit shall have the right to apply for an extension of the time within which the permittee will commence work under that permit when work is unable to be commenced within the time required by this section for good and satis- factory reasons. The code official shall extend the time for action by the permittee for a period not exceeding 180 days if there is reasonable cause. A permit shall not be extended more than once. The fee for an extension shall be one-half the amount required for a new permit for such work. [A] 106.4.5 Suspension or revocation of permit The code official shall have the authority to suspend or revoke a permit issued under the provisions of this code wherever the permit is issued in error or on the basis of incorrect, inaccurate or incomplete information, or in violation of any ordinance or regulation or any of the provisions of this code. [A] 106.4.6 Retention of construction documents. One set of approved construction documents shall be retained by the code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws. One set of approved con- struction documents shall be returned to the applicant, and said set shall be kept on the site of the building or job at all times during which the work authorized thereby is in prog- ress. 2012 INTERNATIONAL MECHANICAL CODE® C,gbt OO?.o„ ICC ALL RIGHTS RESERVED Awsed by (). (-) O,d,, Nombs x,00vco,es oc Sep V,2o19 o, av PM (PDT)p—Potto l»eAg—mt,oU ICC No FYUP ep,od dtoa o AYUP, ,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION [A] 106.4.7 Previous approvals. This code shall not require changes in the construction documents, construc- tion or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise law- fully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned. [A] 106.4.8 Posting of permit The permit or a copy shall be kept on the site of the work until the completion of the project. [A] 106.5 Fees. A permit shall not be issued until the fees prescribed in Section 106.5.2 have been paid, nor shall an amendment to a permit be released until the additional fee, if any, due to an increase of the mechanical system, has been paid. [A] 106.5.1 Work commencing before permit issuance. Any person who commences work on a mechanical sys- tem before obtaining the necessary permits shall be subject to 100 percent of the usual permit fee in addition to the required permit fees. [A] 106.5.2 Fee schedule. The fees for mechanical work shall be as indicated in the following schedule. [JURISDICTION TO INSERT APPROPRIATE SCHEDULE] [A] 106.5.3 Fee refunds. The code official shall authorize the refunding of fees as follows. 1. The full amount of any fee paid hereunder which was erroneously paid or collected. 2. Not more than [SPECIFY PERCENTAGE] percent of the permit fee paid when no work has been done under a permit issued in accordance with this code. 3. Not more than [SPECIFY PERCENTAGE] percent of the plan review fee paid when an application for a per- mit for which a plan review fee has been paid is withdrawn or canceled before any plan review effort has been expended. The code official shall not authorize the refunding of any fee paid, except upon written application filed by the original permittee not later than 180 days after the date of fee pay- ment. SECTION 107 INSPECTIONS AND TESTING [A] 107.1 General. The code official is authorized to conduct such inspections as are deemed necessary to determine com- pliance with the provisions of this code. Construction or work for which a permit is required shall be subject to inspection by the code official, and such construction or work shall remain accessible and exposed for inspection purposes until approved Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. Inspec- tions presuming to give authority to violate or cancel the pro- visions of this code or of other ordinances of the jurisdiction shall not be valid. [A] 107.2 Required inspections and testing. The code offi- cial, upon notification from the permit holder or the permit holder's agent, shall make the following inspections and other such inspections as necessary, and shall either release that portion of the construction or shall notify the permit holder or the permit holder's agent of violations that must be corrected. The holder of the permit shall be responsible for the scheduling of such inspections. 1. Underground inspection shall be made after trenches or ditches are excavated and bedded, piping installed, and before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site. 2. Rough -in inspection shall be made after the roof, fram- ing, fireblocking and bracing are in place and all duct- ing and other components to be concealed are complete, and prior to the installation of wall or ceiling membranes. 3. Final inspection shall be made upon completion of the mechanical system. Exception: Ground -source heat pump loop systems tested in accordance with Section 1208.1.1 shall be permitted to be backfilled prior to inspection. The requirements of this section shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appli- ances has been filed with the department not more than 48 hours after such replacement work is completed, and before any portion of such equipment or appliances is concealed by any permanent portion of the structure. [A] 107.2.1 Other inspections. In addition to the inspec- tions specified above, the code official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced. [A] 107.2.2 Inspection requests. It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code. [A] 107.2.3 Approval required. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the code official. The code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the code official. [A] 107.2.4 Approved inspection agencies. The code official is authorized to accept reports of approved agen- 2012 INTERNATIONAL MECHANICAL CODE® 5 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyodmg FoIRbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION cies, provided that such agencies satisfy the requirements as to qualifications and reliability. [A] 107.2.5 Evaluation and follow-up inspection ser- vices. Prior to the approval of a prefabricated construction assembly having concealed mechanical work and the issu- ance of a mechanical permit, the code official shall require the submittal of an evaluation report on each prefabricated construction assembly, indicating the complete details of the mechanical system, including a description of the sys- tem and its components, the basis upon which the system is being evaluated, test results and similar information, and other data as necessary for the code official to determine conformance to this code. [A] 107.2.5.1 Evaluation service. The code official shall designate the evaluation service of an approved agency as the evaluation agency, and review such agency's evaluation report for adequacy and confor- mance to this code. [A] 107.2.5.2 Follow-up inspection. Except where ready access is provided to mechanical systems, service equipment and accessories for complete inspection at the site without disassembly or dismantling, the code official shall conduct the in -plant inspections as fre- quently as necessary to ensure conformance to the approved evaluation report or shall designate an inde- pendent, approved inspection agency to conduct such inspections. The inspection agency shall furnish the code official with the follow-up inspection manual and a report of inspections upon request, and the mechani- cal system shall have an identifying label permanently affixed to the system indicating that factory inspections have been performed. [A] 107.2.5.3 Test and inspection records. Required test and inspection records shall be available to the code official at all times during the fabrication of the mechanical system and the erection of the building; or such records as the code official designates shall be filed. [A] 107.3 Testing. Mechanical systems shall be tested as required in this code and in accordance with Sections 107.3.1 through 107.3.3. Tests shall be made by the permit holder and observed by the code official. [A] 107.3.1 New, altered, extended or repaired systems. New mechanical systems and parts of existing systems, which have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. [A] 107.3.2 Apparatus, material and labor for tests. Apparatus, material and labor required for testing a mechanical system or part thereof shall be furnished by the permit holder. [A] 107.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve com- pliance with this code. The work or installation shall then be resubmitted to the code official for inspection and test- ing. [A] 107.4 Approval. After the prescribed tests and inspec- tions indicate that the work complies in all respects with this code, a notice of approval shall be issued by the code official. [A] 107.4.1 Revocation. The code official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the notice is issued in error, on the basis of incorrect informa- tion supplied, or where it is determined that the building or structure, premise or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code. [A] 107.5 Temporary connection. The code official shall have the authority to authorize the temporary connection of a mechanical system to the sources of energy for the purpose of testing mechanical systems or for use under a temporary cer- tificate of occupancy. [A] 107.6 Connection of service utilities. No person shall make connections from a utility, source of energy, fuel or power to any building or system that is regulated by this code for which a permit is required, until authorized by the code official. SECTION 108 VIOLATIONS [A] 108.1 Unlawful acts. It shall be unlawful for a person, firm or corporation to erect, construct, alter, repair, remove, demolish or utilize a mechanical system, or cause same to be done, in conflict with or in violation of any of the provisions of this code. [A] 108.2 Notice of violation. The code official shall serve a notice of violation or order to the person responsible for the erection, installation, alteration, extension, repair, removal or demolition of mechanical work in violation of the provisions of this code, or in violation of a detail statement or the approved construction documents thereunder, or in violation of a permit or certificate issued under the provisions of this code. Such order shall direct the discontinuance of the illegal action or condition and the abatement of the violation. [A] 108.3 Prosecution of violation. If the notice of violation is not complied with promptly, the code official shall request the legal counsel of the jurisdiction to institute the appropri- ate proceeding at law or in equity to restrain, correct or abate such violation, or to require the removal or termination of the unlawful occupancyof the structure in violation of the provi- sions of this code or of the order or direction made pursuant thereto. [A] 108.4 Violation penalties. Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter or repair mechanical work in violation of the approved construction documents or directive of the code official, or of a permit or certificate issued under the provisions of this code, shall be guilty of a [SPECIFY OFFENSE], punishable by a fine of not more than [AMOUNT] dollars or by imprisonment not exceed- ing [NUMBER OF DAYS], or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense. 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbt OO?.o„ ICC ALL RIGHTS RESERVED Awsed by (). (-) O,d,, Nombs x,00vco,es oc Sep V,2o19 o, av PM (PDT)p—Potto l»eAge mt,oU ICC No FYUP ep,od dtoa o AYUP, ,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg Podortuodmg FoIRbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION [A] 108.5 Stop work orders. Upon notice from the code offi- cial that mechanical work is being done contrary to the provi- sions of this code or in a dangerous or unsafe manner, such work shall immediately cease. Such notice shall be in writing and shall be given to the owner of the property, or to the owner's agent, or to the person doing the work. The notice shall state the conditions under which work is authorized to resume. Where an emergency exists, the code official shall not be required to give a written notice prior to stopping the work. Any person who shall continue any work on the system after having been served with a stop work order, except such work as that person is directed to perform to remove a viola- tion or unsafe condition, shall be liable for a fine of not less than [AMOUNT] dollars or more than [AMOUNT] dollars. [A] 108.6 Abatement of violation. The imposition of the penalties herein prescribed shall not preclude the legal officer of the jurisdiction from instituting appropriate action to pre- vent unlawful construction or to restrain, correct or abate a violation, or to prevent illegal occupancyof a building, struc- ture or premises, or to stop an illegal act, conduct, business or utilization of the mechanical system on or about any prem- ises. [A] 108.7 Unsafe mechanical systems. A mechanical system that is unsafe, constitutes a fire or health hazard, or is other- wise dangerous to human life, as regulated by this code, is hereby declared as an unsafe mechanical system. Use of a mechanical system regulated by this code constituting a haz- ard to health, safety or welfare by reason of inadequate main- tenance, dilapidation, fire hazard, disaster, damage or abandonment is hereby declared an unsafe use. Such unsafe equipment and appliances are hereby declared to be a public nuisance and shall be abated by repair, rehabilitation, demoli- tion or removal. [A] 108.7.1 Authority to condemn mechanical systems. Whenever the code official determines that any mechani- cal system, or portion thereof, regulated by this code has become hazardous to life, health, property, or has become insanitary, the code official shall order in writing that such system either be removed or restored to a safe condition. A time limit for compliance with such order shall be speci- fied in the written notice. A person shall not use or main- tain a defective mechanical system after receiving such notice. When such mechanical system is to be disconnected, written notice as prescribed in Section 108.2 shall be given. In cases of immediate danger to life or property, such disconnection shall be made immediately without such notice. [A] 108.7.2 Authority to order disconnection of energy sources. The code official shall have the authority to order disconnection of energy sources supplied to a building, structure or mechanical system regulated by this code, when it is determined that the mechanical system or any portion thereof has become hazardous or unsafe. Written notice of such order to disconnect service and the causes therefor shall be given within 24 hours to the owner and occupant of such building, structure or premises, provided, however, that in cases of immediate danger to life or prop - erty, such disconnection shall be made immediately with- out such notice. Where energy sources are provided by a public utility, the code official shall immediately notify the serving utility in writing of the issuance of such order to disconnect. [A] 108.7.3 Connection after order to disconnect. A person shall not make energy source connections to mechanical systems regulated by this code which have been disconnected or ordered to be disconnected by the code official, or the use of which has been ordered to be discontinued by the code official until the code official authorizes the reconnection and use of such mechanical systems. When a mechanical system is maintained in violation of this code, and in violation of a notice issued pursuant to the provisions of this section, the code official shall insti- tute appropriate action to prevent, restrain, correct or abate the violation. SECTION 109 MEANS OF APPEAL [A] 109.1 Application for appeal. A person shall have the right to appeal a decision of the code official to the board of appeals. An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equally good or better form of construction is proposed. The application shall be filed on a form obtained from the code official within 20 days after the notice was served. [A] 109.1.1 Limitation of authority. The board of appeals shall have no authority relative to interpretation of the administration of this code nor shall such board be empowered to waive requirements of this code. [A] 109.2 Membership of board. The board of appeals shall consist of five members appointed by the chief appointing authority as follows: one for five years; one for four years; one for three years; one for two years; and one for one year. Thereafter, each new member shall serve for five years or until a successor has been appointed. [A] 109.2.1 Qualifications. The board of appeals shall consist of five individuals, one from each of the following professions or disciplines. 1. Registered design professional who is a registered architect; or a builder or superintendent of building construction with at least 10 years' experience, five of which shall have been in responsible charge of work. 2. Registered design professional with structural engi- neering or architectural experience. 3. Registered design professional with mechanical and plumbing engineering experience; or a mechanical contractor with at least 10 years' experience, five of which shall have been in responsible charge of work. 2012 INTERNATIONAL MECHANICAL CODE® 7 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyodmg FoIRbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SCOPE AND ADMINISTRATION 4. Registered design professional with electrical engi- neering experience; or an electrical contractor with at least 10 years' experience, five of which shall have been in responsible charge of work. 5. Registered design professional with fire protection engineering experience; or a fire protection contrac- tor with at least 10 years' experience, five of which shall have been in responsible charge of work. [A] 109.2.2 Alternate members. The chief appointing authority shall appoint two alternate members who shall be called by the board chairman to hear appeals during the absence or disqualification of a member. Alternate mem- bers shall possess the qualifications required for board membership and shall be appointed for five years, or until a successor has been appointed. [A] 109.2.3 Chairman. The board shall annually select one of its members to serve as chairman. [A] 109.2.4 Disqualification of member. A member shall not hear an appeal in which that member has a personal, professional or financial interest. [A] 109.2.5 Secretary. The chief administrative officer shall designate a qualified clerk to serve as secretary to the board. The secretary shall file a detailed record of all pro- ceedings in the office of the chief administrative officer. [A] 109.2.6 Compensation of members. Compensation of members shall be determined by law. [A] 109.3 Notice of meeting. The board shall meet upon notice from the chairman, within ten days of the filing of an appeal, or at stated periodic meetings. [A] 109.4 Open hearing. All hearings before the board shall be open to the public. The appellant, the appellant's represen- tative, the code official and any person whose interests are affected shall be given an opportunity to be heard. [A] 109.4.1 Procedure. The board shall adopt and make available to the public through the secretary procedures under which a hearing will be conducted. The procedures shall not require compliance with strict rules of evidence, but shall mandate that only relevant information be received. [A] 109.5 Postponed hearing. When five members are not present to hear an appeal, either the appellant or the appel- lant's representative shall have the right to request a post- ponement of the hearing. [A] 109.6 Board decision. The board shall modify or reverse the decision of the code official by a concurring vote of three members. [A] 109.6.1 Resolution. The decision of the board shall be by resolution. Certified copies shall be furnished to the appellant and to the code official. [A] 109.6.2 Administration. The code official shall take immediate action in accordance with the decision of the board. [A] 109.7 Court review. Any person, whether or not a previ- ous party of the appeal, shall have the right to apply to the appropriate court for a writ of certiorari to correct errors of law. Application for review shall be made in the manner and time required by law following the filing of the decision in the office of the chief administrative officer. SECTION 110 TEMPORARY EQUIPMENT, SYSTEMS AND USES [A] 110.1 General. The code official is authorized to issue a permit for temporary equipment, systems and uses. Such per- mits shall be limited as to time of service, but shall not be permitted for more than 180 days. The code official is autho- rized to grant extensions for demonstrated cause. [A] 110.2 Conformance. Temporary equipment, systems and uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation and sanitary requirements of this code as necessary to ensure the public health, safety and general welfare. [A] 110.3 Temporary utilities. The code official is autho- rized to give permission to temporarily supply utilities before an installation has been fully completed and the final certifi- cate of completion has been issued. The part covered by the temporary certificate shall comply with the requirements specified for temporary lighting, heat or power in the code. [A] 110.4 Termination of approval. The code official is authorized to terminate such permit for temporary equipment, systems or uses and to order the temporary equipment, sys- tems or uses to be discontinued. 2012 INTERNATIONAL MECHANICAL CODE® Copyngbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by (). (-) O,d,, Nombs x 100760189 oc Sep so.2o19 0147 PM (PDT)p—Potto l»eAge mt,oU ICC No FYUP ep,od dtoa o AYUP, ,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER DEFINITIONS SECTION 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the follow- ing words and terms shall, for the purposes of this code, have the meanings indicated in this chapter. 201.2 Interchangeability. Words used in the present tense include the future; words in the masculine gender include the feminine and neuter; the singular number includes the plural and the plural, the singular. 201.3 Terms defined in other codes. Where terms are not defined in this code and are defined in the International Building Code, International Fire Code, International Fuel Gas Code or the International Plumbing Code, such terms shall have meanings ascribed to them as in those codes. 201.4 Terms not defined. Where terms are not defined through the methods authorized by this section, such terms shall have ordinarily accepted meanings such as the context implies. SECTION 202 GENERAL DEFINITIONS ABRASIVE MATERIALS. Moderately abrasive particulate in high concentrations, and highly abrasive particulate in moderate and high concentrations, such as alumina, bauxite, iron silicate, sand and slag. ABSORPTION SYSTEM. A refrigerating system in which refrigerant is pressurized by pumping a chemical solution of refrigerant in absorbent, and then separated by the addition of heat in a generator, condensed (to reject heat), expanded, evaporated (to provide refrigeration), and reabsorbed in an absorber to repeat the cycle; the system may be single or mul- tiple effect, the latter using multiple stages or internally cas- caded use of heat to improve efficiency. ACCESS (TO). That which enables a device, appliance or equipment to be reached by ready access or by a means that first requires the removal or movement of a panel, door or similar obstruction [see also "Ready access (to)"]. AIR. All air supplied to mechanical equipment and appli- ances for combustion, ventilation, cooling, etc. Standard air is air at standard temperature and pressure, namely, 70°F (21°C) and 29.92 inches of mercury (101.3 kPa). AIR CONDITIONING. The treatment of air so as to control simultaneously the temperature, humidity, cleanness and dis- tribution of the air to meet the requirements of a conditioned space. AIR-CONDITIONING SYSTEM. A system that consists of heat exchangers, blowers, filters, supply, exhaust and return ducts, and shall include any apparatus installed in con- nection therewith. AIR DISPERSION SYSTEM. Any diffuser system designed to both convey air within a room, space or area and diffuse air into that space while operating under positive pres- sure. Systems are commonly constructed of, but not limited to, fabric or plastic film. AIR DISTRIBUTION SYSTEM. Any system of ducts, ple- nums and air -handling equipment that circulates air within a space or spaces and includes systems made up of one or more air -handling units. AIR, EXHAUST. Air being removed from any space, appli- ance or piece of equipment and conveyed directly to the atmosphere by means of openings or ducts. AIR -HANDLING UNIT. A blower or fan used for the pur- pose of distributing supply air to a room, space or area. AIR, MAKEUP. Air that is provided to replace air being exhausted. [A] ALTERATION. A change in a mechanical system that involves an extension, addition or change to the arrangement, type or purpose of the original installation. APPLIANCE. A device or apparatus that is manufactured and designed to utilize energy and for which this code pro- vides specific requirements. APPLIANCE, EXISTING. Any appliance regulated by this code which was legally installed prior to the effective date of this code, or for which a permit to install has been issued. APPLIANCE TYPE. High -heat appliance. Any appliance in which the prod- ucts of combustion at the point of entrance to the flue under normal operating conditions have a temperature greater than 2,000°F (1093°C). Low -heat appliance (residential appliance). Any appli- ance in which the products of combustion at the point of entrance to the flue under normal operating conditions have a temperature of 1,000°F (538°C) or less. Medium -heat appliance. Any appliance in which the products of combustion at the point of entrance to the flue under normal operating conditions have a temperature of more than 1,000°F (538°C), but not greater than 2,000°F (1093°C). APPLIANCE, VENTED. An appliance designed and installed in such a manner that all of the products of combus- tion are conveyed directly from the appliance to the outdoor atmosphere through an approved chimneyor vent system. [A] APPROVED. Acceptable to the code official or other authority having jurisdiction. [A] APPROVED AGENCY. An established and recognized agency that is approved by the code official and regularly engaged in conducting tests or furnishing inspection services. 2012 INTERNATIONAL MECHANICAL CODE® 9 I II I Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow60189 oc SIP V,2019o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,FodmYo¢tbymytl,dputy,o,iNb,to,au o,sd SmgIP—oPIA mpymg Pod.Nyodmg FoIRbthd ANY VNAVTHORIVED REPRODUCTION ORDISIRIBVTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS AUTOMATIC BOILER. Any class of boiler that is equipped with the controls and limit devices specified in Chapter 10. BATHROOM. A room containing a bathtub, shower, spa or similar bathing fixture. BOILER. A closed heating appliance intended to supply hot water or steam for space heating, processing or power pur- poses. Low-pressure boilers operate at pressures less than or equal to 15 pounds per square inch (psi) (103 kPa) for steam and 160 psi (1103 kPa) for water. High-pressure boilers oper- ate at pressures exceeding those pressures. BOILER ROOM. A room primarily utilized for the installa- tion of a boiler. BRAZED JOINT. A gas -tight joint obtained by the joining of metal parts with metallic mixtures or alloys which melt at a temperature above 1,000°F (538°C), but lower than the melt- ing temperature of the parts to be joined. BRAZING. A metal joining process wherein coalescence is produced by the use of a nonferrous filler metal having a melting point above 1,000°F (538°C), but lower than that of the base metal being joined. The filler material is distributed between the closely fitted surfaces of the joint by capillary attraction. BREATHING ZONE. The region within an occupied space between planes 3 and 72 inches (76 and 1829 mm) above the floor and more than 2 feet (610 mm) from the walls of the space or from fixed air-conditioning equipment. BTU. Abbreviation for British thermal unit, which is the quantity of heat required to raise the temperature of 1 pound (454 g) of water 1°F (0.56°C) (1 Btu = 1055 j. [A] BUILDING. Any structure occupied or intended for sup- porting or sheltering any occupancy. [B] CEILING RADIATION DAMPER. A listed device installed in a ceiling membrane of a fire -resistance -rated floor/ceiling or roof/ceiling assembly to limit automatically the radiative heat transfer through an air inlet/outlet opening. CHIMNEY. A primarily vertical structure containing one or more flues, for the purpose of carrying gaseous products of combustion and air from a fuel -burning appliance to the out- door atmosphere. Factory -built chimney. A listed and labeled chimney composed of factory -made components, assembled in the field in accordance with manufacturer's instructions and the conditions of the listing. Masonry chimney. A field -constructed chimney com- posed of solid masonry units, bricks, stones or concrete. Metal chimney. A field -constructed chimney of metal. CHIMNEY CONNECTOR. A pipe that connects a fuel - burning appliance to a chimney. CLEARANCE. The minimum distance through air mea- sured between the heat -producing surface of the mechanical appliance, device or equipment and the surface of the com- bustible material or assembly. CLOSED COMBUSTION SOLID -FUEL -BURNING APPLIANCE. A heat -producing appliance that employs a combustion chamber that has no openings other than the flue collar, fuel charging door and adjustable openings provided to control the amount of combustion air that enters the com- bustion chamber. CLOTHES DRYER. An appliance used to dry wet laundry I by means of heat. [A] CODE. These regulations, subsequent amendments 4m thereto, or any emergency rule or regulation that the adminis- trative authority having jurisdiction has lawfully adopted. [A] CODE OFFICIAL. The officer or other designated authority charged with the administration and enforcement of this code, or a duly authorized representative. [B] COMBINATION FIRE/SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed to close automatically upon the detection of heat and resist the passage of flame and smoke. The device is installed to oper- ate automatically, be controlled by a smoke detection system, and where required, is capable of being positioned from a fire command center. COMBUSTIBLE ASSEMBLY. Wall, floor, ceiling or other assembly constructed of one or more component materials that are not defined as noncombustible. [F] COMBUSTIBLE LIQUID. A liquid having a closed I cup flash point at or above 100°F (380C). Combustible liquids shall be subdivided as follows: Class II. Liquids having a closed cup flash point at or ' above 100°F (38°C) and below 140OF (600C). Class IIIA. Liquids having a closed cup flash point at or above 140OF (60°C) and below 200OF (930C). Class IIIB. Liquids having a closed cup flash point at or ' above 200OF (930C). The category of combustible liquids does not include com- pressed gases or cryogenic fluids. COMBUSTIBLE MATERIAL. Any material not defined as noncombustible. COMBUSTION. In the context of this code, refers to the rapid oxidation of fuel accompanied by the production of heat or heat and light. COMBUSTION AIR. Air necessary for complete combus- tion of a fuel, including theoretical air and excess air. COMBUSTION CHAMBER. The portion of an appliance within which combustion occurs. COMBUSTION PRODUCTS. Constituents resulting from the combustion of a fuel with the oxygen of the air, including the inert gases, but excluding excess air. COMMERCIAL COOKING APPLIANCES. Appliances used in a commercial food service establishment for heating or cooking food and which produce grease vapors, steam, fumes, smoke or odors that are required to be removed through a local exhaust ventilation system. Such appliances include deep fat fryers; upright broilers; griddles; broilers; steam jacketed kettles; hot -top ranges; under -fired broilers 10 2012 INTERNATIONAL MECHANICAL CODE® C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I kliF ( od Uto.. by POVO d party. o,±RYb�toc P,,Uoosd SmgIP--1,mpymg Pod o Nyo,k,FoARbtAd ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS (charbroilers); ovens; barbecues; rotisseries; and similar appliances. For the purpose of this definition, a food service establishment shall include any building or a portion thereof used for the preparation and serving of food. COMMERCIAL COOKING RECIRCULATING SYS- TEM. Self-contained system consisting of the exhaust hood, the cooking equipment, the filters and the fire suppression system. The system is designed to capture cooking vapors and residues generated from commercial cooking equipment. The system removes contaminants from the exhaust air and recirculates the air to the space from which it was withdrawn. KI1�A15IIIKN/\I 240CNIIIILIam101011b.1 Backshelf hood. A backshelf hood is also referred to as a low -proximity hood, or as a sidewall hood where wall mounted. Its front lower lip is low over the appliance(s) and is "set back" from the front of the appliance(s). It is always closed to the rear of the appliances by a panel where free-standing, or by a panel or wall where wall mounted, and its height above the cooking surface varies. (This style of hood can be constructed with partial end panels to increase its effectiveness in capturing the efflu- ent generated by the cooking operation). Double island canopy hood. A double island canopy hood is placed over back-to-back appliances or appliance lines. It is open on all sides and overhangs both fronts and the sides of the appliance(s). It could have a wall panel between the backs of the appliances. (The fact that exhaust air is drawn from both sides of the double canopy to meet in the center causes each side of this hood to emulate a wall canopy hood, and thus it functions much the same with or without an actual wall panel between the backs of the appliances). Eyebrow hood. An eyebrow hood is mounted directly to the face of an appliance, such as an oven and dishwasher, above the opening(s) or door(s) from which effluent is emitted, extending past the sides and overhanging the front of the opening to capture the effluent. Pass -over hood. A pass -over hood is a free-standing form of a backshelf hood constructed low enough to pass food over the top. Single island canopy hood. A single island canopy hood is placed over a single appliance or appliance line. It is open on all sides and overhangs the front, rear and sides of the appliance(s). A single island canopy is more suscepti- ble to cross drafts and requires a greater exhaust air flow than an equivalent sized wall -mounted canopy to capture and contain effluent generated by the cooking opera- tion(s). Wall canopy hood. A wall canopy exhaust hood is mounted against a wall above a single appliance or line of appliance(s), or it could be free-standing with a back panel from the rear of the appliances to the hood. It overhangs the front and sides of the appliance(s) on all open sides. The wall acts as a back panel, forcing the makeup air to be drawn across the front of the cooking equipment, thus increasing the effectiveness of the hood to capture and contain effluent generated by the cooking operation(s). COMPENSATING HOODS. Compensating hoods are those having integral (built-in) makeup air supply. The makeup airsupply for such hoods is generally supplied from: short-circuit flow from inside the hood, air curtain flow from the bottom of the front face, and front face discharge from the outside front wall of the hood. The compensating makeup air- flow can also be supplied from the rear or side of the hood, or the rear, front or sides of the cooking equipment. The makeup airflow can be one or a combination of methods. COMPRESSOR. A specific machine, with or without acces- sories, for compressing a gas. COMPRESSOR, POSITIVE DISPLACEMENT. A com- pressor in which increase in pressure is attained by changing the internal volume of the compression chamber. COMPRESSOR UNIT. A compressor with its prime mover and accessories. CONCEALED LOCATION. A location that cannot be accessed without damaging permanent parts of the building structure or finish surface. Spaces above, below or behind readily removable panels or doors shall not be considered as concealed. CONDENSATE. The liquid that condenses from a gas (including flue gas) caused by a reduction in temperature. CONDENSER. A heat exchanger designed to liquefy refrig- erant vapor by removal of heat. CONDENSING UNIT. A specific refrigerating machine combination for a given refrigerant, consisting of one or more power -driven compressors, condensers, liquid receivers (when required) and the regularly furnished accessories. CONDITIONED SPACE. An area, room or space being heated or cooled by any equipmentor appliance. [A] CONSTRUCTION DOCUMENTS. All of the written, graphic and pictorial documents prepared or assembled for describing the design, location and physical characteristics of the elements of the project necessary for obtaining a building permit. The construction drawings shall be drawn to an appropriate scale. CONTROL. A manual or automatic device designed to regu- late the gas, air, water or electrical supply to, or operation of, a mechanical system. CONVERSION BURNER. A burner designed to supply gaseous fuel to an appliance originally designed to utilize another fuel. COOKING APPLIANCE. See "Commercial cookingappli- ances." DAMPER. A manually or automatically controlled device to regulate draft or the rate of flow of air or combustion gases. Volume damper. A device that, when installed, will restrict, retard or direct the flow of air in a duct, or the products of combustion in a heat -producing appliance, its vent connector, vent or chimney therefrom. [B] DESIGN FLOOD ELEVATION. The elevation of the "design flood," including wave height, relative to the datum specified on the community's legally designated flood hazard area map. 2012 INTERNATIONAL MECHANICAL CODE® 11 I II I Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS DESIGN WORKING PRESSURE. The maximum allow- able working pressure for which a specific part of a system is designed. DIRECT REFRIGERATION SYSTEM. A system in which the evaporator or condenser of the refrigerating system is in direct contact with the air or other substances to be cooled or heated. DIRECT -VENT APPLIANCES. Appliances that are con- structed and installed so that all air for combustion is derived from the outdoor atmosphere and all flue gases are dis- charged to the outdoor atmosphere. DRAFT. The pressure difference existing between the appli- ance or any component part and the atmosphere, that causes a continuous flow of air and products of combustion through the gas passages of the appliance to the atmosphere. Induced draft The pressure difference created by the action of a fan, blower or ejector, that is located between the appliance and the chimney or vent termination. Natural draft. The pressure difference created by a vent or chimney because of its height, and the temperature dif- ference between the flue gases and the atmosphere. DRIP. The container placed at a low point in a system of pip- ing to collect condensate and from which the condensate is removable. DRY CLEANING SYSTEMS. Dry cleaning plants or sys- tems are classified as follows: Type I. Those systems using Class I flammable liquid sol- vents having a flash point below 100°F (38°C). Type II. Those systems using Class II combustible liquid solvents having a flash point at or above 100°F (38°C) and below 140°F (60°C). Type III. Those systems using Class III combustible liq- uid solvents having a flash point at or above 140°F (60°C). Types IV and V. Those systems using Class IV nonflam- mable liquid solvents. DUCT. A tube or conduit utilized for conveying air. The air passages of self-contained systems are not to be construed as air ducts. DUCT FURNACE. A warm -air furnace normally installed in an air distribution duct to supply warm air for heating. This definition shall apply only to a warm -air heating appliance that, for air circulation, depends on a blower not furnished as part of the furnace. DUCT SYSTEM. A continuous passageway for the trans- mission of air that, in addition to ducts, includes duct fittings, dampers, plenums, fans and accessory air -handling equip- ment and appliances. [B] DWELLING. A building or portion thereof that contains not more than two dwellingunits. [B] DWELLING UNIT. A single unit providing complete, independent living facilities for one or more persons, includ- ing permanent provisions for living, sleeping, eating, cooking and sanitation. ELECTRIC HEATING APPLIANCE. An appliance that produces heat energy to create a warm environment by the application of electric power to resistance elements, refriger- ant compressors or dissimilar material junctions. ENERGY RECOVERY VENTILATION SYSTEM. Sys- tems that employ air-to-air heat exchangers to recover energy from or reject energy to exhaust air for the purpose of pre- heating, pre -cooling, humidifying or dehumidifying outdoor ventilation air prior to supplying such air to a space, either directly or as part of an HVAC system. ENVIRONMENTAL AIR. Air that is conveyed to or from occupied areas through ducts which are not part of the heat- ing or air-conditioning system, such as ventilation for human usage, domestic kitchen range exhaust, bathroom exhaust, domestic clothes dryer exhaust and parking garage exhaust. EQUIPMENT. All piping, ducts, vents, control devices and other components of systems other than appliances which are permanently installed and integrated to provide control of environmental conditions for buildings. This definition shall also include other systems specifically regulated in this code. EQUIPMENT, EXISTING. Any equipment regulated by this code which was legally installed prior to the effective date of this code, or for which a permit to install has been issued. EVAPORATIVE COOLER. A device used for reducing the sensible heat of air for cooling by the process of evaporation of water into an airstream. EVAPORATIVE COOLING SYSTEM. The equipment and appliances intended or installed for the purpose of envi- ronmental cooling by an evaporative cooler from which the conditioned air is distributed through ducts or plenums to the conditioned area. EVAPORATOR. That part of the system in which liquid refrigerant is vaporized to produce refrigeration. EXCESS AIR. The amount of air provided in addition to the- oretical airto achieve complete combustion of a fuel, thereby preventing the formation of dangerous products of combus- tion. EXHAUST SYSTEM. An assembly of connected ducts, ple- nums, fittings, registers, grilles and hoods through which air is conducted from the space or spaces and exhausted to the outdoor atmosphere. EXTRA -HEAVY-DUTY COOKING APPLIANCE. Extra -heavy-duty cooking appliances include appliances uti- lizing solid fuel such as wood, charcoal, briquettes, and mes- quite to provide all or part of the heat source for cooking. [B] FIRE DAMPER. A listed device installed in ducts and air transfer openings designed to close automatically upon detection of heat and to restrict the passage of flame. Fire dampers are classified for use in either static systems that will automatically shut down in the event of a fire, or in dynamic systems that continue to operate during a fire. A dynamic fire damper is tested and rated for closure under elevated temper- ature airflow. 12 2012 INTERNATIONAL MECHANICAL CODE® C,Ty,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I kliF ( [IFod Ut.. by POVOt pPLO I,±Nb�to, P,,UoFsd SmgIP—oPIA Tymg Pod o NyodmgFoARbtAd ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS FIREPLACE. An assembly consisting of a hearth and fire chamber of noncombustible material and provided with a chimney, for use with solid fuels. Factory -built fireplace. A listed and labeled fireplace and chimney system composed of factory -made compo- nents, and assembled in the field in accordance with man- ufacturer's instructions and the conditions of the listing. Masonry fireplace. A field -constructed fireplace com- posed of solid masonry units, bricks, stones or concrete. FIREPLACE STOVE. A free-standing chimney -connected solid -fuel -burning heater, designed to be operated with the fire chamber doors in either the open or closed position. FLAME SAFEGUARD. A device that will automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inopera- tive, and when flame failure occurs on the burner or group of burners. [B] FLAME SPREAD INDEX. The numerical value assigned to a material tested in accordance with ASTM E 84 or UL 723. FLAMMABILITY CLASSIFICATION. Refrigerants shall be assigned to one of the three classes1, 2 or 3—in accor- dance with ASHRAE 34. For Classes 2 and 3, the heat of combustion shall be calculated assuming that combustion products are in the gas phase and in their most stable state. Class 1. Refrigerants that do not show flame propagation when tested in air at 14.7 psia (101 kPa) and 70°F (21°C). Class 2. Refrigerants having a lower flammability limit (LFL) of more than 0.00625 pound per cubic foot (0.10 kg/m') at 70°F (21°C) and 14.7 psia (101 kPa) and a heat of combustion of less than 8,174 Btu/lb (19 000 kj/kg). Class 3. Refrigerants that are highly flammable, having a LFL of less than or equal to 0.00625 pound per cubic foot (0.10 kg/m') at 70°F (21°C) and 14.7 psia (101 kPa) or a heat of combustion greater than or equal to 8,174 Btu/lb (19 000 kJ/kg). [F] FLAMMABLE LIQUIDS. Any liquid that has a flash point below 100°F (38°C), and has a vapor pressure not exceeding 40 psia (276 kPa) at 100°F (380C). Flammable liq- uids shall be known as Class I liquids and shall be divided into the following classifications: Class IA. Liquids having a flash point below 730F (23°C) and a boiling point below 100°F (380C). Class IB. Liquids having a flash point below 730F (23°C) and a boiling point at or above 100°F (380C). Class IC. Liquids having a flash point at or above 730F (23°C) and below 100°F (380C). [F] FLAMMABLE VAPOR OR FUMES. Mixtures of gases in air at concentrations equal to or greater than the LFL and less than or equal to the upper flammability limit (UFL). [F] FLASH POINT. The minimum temperature corrected to a pressure of 14.7 psia (101 kPa) at which the application of a test flame causes the vapors of a portion of the sample to ignite under the conditions specified by the test procedures and apparatus. The flash point of a liquid shall be determined in accordance with ASTM D 56, ASTM D 93 or ASTM D 3278. FLOOR AREA, NET. The actual occupied area, not includ- ing unoccupied accessory areas or thicknesses of walls. FLOOR FURNACE. A completely self-contained furnace suspended from the floor of the space being heated, taking air for combustion from outside such space and with means for observing flames and lighting the appliance from such space. FLUE. A passageway within a chimney or vent through which gaseous combustion products pass. FLUE CONNECTION (BREECHING). A passage for conducting the products of combustion from a fuel -fired appliance to the vent or chimney (see also "Chimneyconnec- tor" and "Vent connector"). FLUE GASES. Products of combustion and excess air. FLUE LINER (LINING). A system or material used to form the inside surface of a flue in a chimney or vent, for the pur- pose of protecting the surrounding structure from the effects of combustion products and conveying combustion products without leakage to the atmosphere. FUEL GAS. A natural gas, manufactured gas, liquefied petroleum gas or a mixture of these. FUEL OIL. Kerosene or any hydrocarbon oil having a flash point not less than 100°F (380C). FUEL -OIL PIPING SYSTEM. A closed piping system that connects a combustible liquid from a source of supply to a fuel -oil -burning appliance. FURNACE. A completely self-contained heating unit that is designed to supply heated air to spaces remote from or adja- cent to the appliance location. FURNACE ROOM. A room primarily utilized for the instal- lation of fuel -burning, space -heating and water -heating appli- ances other than boilers (see also "Boiler room"). FUSIBLE PLUG. A device arranged to relieve pressure by operation of a fusible member at a predetermined tempera- ture. GROUND SOURCE HEAT PUMP LOOP SYSTEM. Pip- ing buried in horizontal or vertical excavations or placed in a body of water for the purpose of transporting heat transfer liquid to and from a heat pump. Included in this definition are closed loop systems in which the liquid is recirculated and open loop systems in which the liquid is drawn from a well or other source. HAZARDOUS LOCATION. Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances. The location is not necessarily categorized in the International Building Code as a high -hazard use group classification. HEAT EXCHANGER. A device that transfers heat from one medium to another. HEAT PUMP. A refrigeration system that extracts heat from one substance and transfers it to another portion of the same substance or to a second substance at a higher temperature for a beneficial purpose. 2012 INTERNATIONAL MECHANICAL CODE® 13 I II I C,Ty,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS HEAT TRANSFER LIQUID. The operating or thermal storage liquid in a mechanical system, including water or other liquid base, and additives at the concentration present under operating conditions used to move heat from one loca- tion to another. Refrigerants are not included as heat transfer liquids. HEAVY-DUTY COOKING APPLIANCE. Heavy-duty cooking appliances include electric under -fired broilers, elec- tric chain (conveyor) broilers, gas under -fired broilers, gas chain (conveyor) broilers, gas open -burner ranges (with or without oven), electric and gas wok ranges, and electric and gas over -fired (upright) broilers and salamanders. HIGH -PROBABILITY SYSTEMS. A refrigeration system in which the basic design or the location of components is such that a leakage of refrigerant from a failed connection, seal or component will enter an occupancy classified area, other than the machineryroom. HIGH -SIDE PRESSURE. The parts of a refrigerating sys- tem subject to condenser pressure. HOOD. An air intake device used to capture by entrapment, impingement, adhesion or similar means, grease, moisture, heat and similar contaminants before they enter a duct sys- tem. Type I. A kitchen hood for collecting and removing grease vapors and smoke. Such hoods are equipped with a fire suppression system. Type II. A general kitchen hood for collecting and remov- ing steam, vapor, heat, odors and products of combustion. [FG] HYDROGEN GENERATING APPLIANCE. A self- contained package or factory -matched packages of integrated systems for generating gaseous hydrogen. Hydrogen generat- ing appliances utilize electrolysis, reformation, chemical, or other processes to generate hydrogen. IGNITION SOURCE. A flame, spark or hot surface capable of igniting flammable vapors or fumes. Such sources include appliance burners, burner ignitors and electrical switching devices. [F] IMMEDIATELY DANGEROUS TO LIFE OR HEALTH ODLH). The concentration of airborne contami- nants that poses a threat of death, immediate or delayed per- manent adverse health effects, or effects that could prevent escape from such an environment. This contaminant concen- tration level is established by the National Institute of Occu- pational Safety and Health (NIOSH) based on both toxicity and flammability. It is generally expressed in parts per mil- lion by volume (ppm v/v) or milligrams per cubic meter (mg/ m3) INDIRECT REFRIGERATION SYSTEM. A system in which a secondary coolant cooled or heated by the refrigerat- ing system is circulated to the air or other substance to be cooled or heated. Indirect systems are distinguished by the method of application shown below: Closed system. A system in which a secondary fluid is either cooled or heated by the refrigerating system and then circulated within a closed circuit in indirect contact with the air or other substance to be cooled or heated. Double -indirect open -spray system. A system in which the secondary substance for an indirect open -spray system is heated or cooled by an intermediate coolant circulated from a second enclosure. Open -spray system. A system in which a secondary cool- ant is cooled or heated by the refrigerating system and then circulated in direct contact with the air or other sub- stance to be cooled or heated. Vented closed system. A system in which a secondary coolant is cooled or heated by the refrigerating system and then passed through a closed circuit in the air or other sub- stance to be cooled or heated, except that the evaporator or condenser is placed in an open or appropriately vented tank. INTERLOCK. A device actuated by another device with which it is directly associated, to govern succeeding opera- tions of the same or allied devices. A circuit in which a given action cannot occur until after one or more other actions have taken place. JOINT, FLANGED. A joint made by bolting together a pair of flanged ends. JOINT, FLARED. A metal -to -metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare. JOINT, PLASTIC ADHESIVE. Ajoint made in thermoset plastic piping by the use of an adhesive substance which forms a continuous bond between the mating surfaces with- out dissolving either one of them. JOINT, PLASTIC HEAT FUSION. A joint made in ther- moplastic piping by heating the parts sufficiently to permit fusion of the materials when the parts are pressed together. JOINT, PLASTIC SOLVENT CEMENT. Ajoint made in thermoplastic piping by the use of a solvent or solvent cement which forms a continuous bond between the mating surfaces. JOINT, SOLDERED. A gas-tightjoint obtained by thejoin- ing of metal parts with metallic mixtures of alloys which melt at temperatures between 400°F (204°C) and 1,000°F (538°C). JOINT, WELDED. A gas-tightjoint obtained by thejoining of metal parts in molten state. [A] LABELED. Equipment, materials or products to which have been affixed a label, seal, symbol or other identifying mark of a nationally recognized testing laboratory, inspection agency or other organization concerned with product evalua- tion that maintains periodic inspection of the production of the above -labeled items and whose labeling indicates either that the equipment, material or product meets identified stan- dards or has been tested and found suitable for a specified purpose. LIGHT -DUTY COOKING APPLIANCE. Light -duty cooking appliances include gas and electric ovens (including standard, bake, roasting, revolving, retherm, convection, combination convection/steamer, countertop conveyorized baking/finishing, deck and pastry), electric and gas steam - jacketed kettles, electric and gas pasta cookers, electric and gas compartment steamers (both pressure and atmospheric) and electric and gas cheesemelters. 4m 14 2012 INTERNATIONAL MECHANICAL CODE® C,Ty,ght @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I kliF ( [IFod Ut.. by POVO d party. o,±RYb�toc P,,Uoosd Smgle—oPIA Tymg Pod o Nyodmg F oARbtAd ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS [FG] LIMIT CONTROL. A device responsive to changes in pressure, temperature or level for turning on, shutting off or throttling the gas supply to an appliance. LIMITED CHARGE SYSTEM. A system in which, with the compressor idle, the design pressure will not be exceeded when the refrigerant charge has completely evaporated. [A] LISTED. Equipment, materials, products or services included in a list published by an organization acceptable to the code official and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipmentor materials or periodic evaluation of ser- vices and whose listing states either that the equipment, mate- rial, product or service meets identified standards or has been tested and found suitable for a specified purpose. LIVING SPACE. Space within a dwelling unit utilized for living, sleeping, eating, cooking, bathing, washing and sanita- tion purposes. LOWER EXPLOSIVE LIMIT (LEL). See "LFL." LOWER FLAMMABLE LIMIT (REFRIGERANT) (LFL). The minimum concentration of refrigerant that is capable of propagating a flame through a homogeneous mix- ture of refrigerant and air. I[F] LOWER FLAMMABLE LIMIT (LFL). The minimum concentration of vapor in air at which propagation of flame will occur in the presence of an ignition source. The LFL is sometimes referred to as LEL or lower explosive limit. LOW-PRESSURE HOT WATER -HEATING BOILER. A boiler furnishing hot water at pressures not exceeding 160 psi (1103 kPa) and at temperatures not exceeding 250°F (121°C). LOW-PRESSURE STEAM -HEATING BOILER. A boiler furnishing steam at pressures not exceeding 15 psi (103 kPa). LOW -PROBABILITY SYSTEMS. A refrigeration system in which the basic design or the location of components is such that a leakage of refrigerant from a failed connection, seal or component will not enter an occupancy -classified area, other than the machineryroom. LOW -SIDE PRESSURE. The parts of a refrigerating sys- tem subject to evaporator pressure. MACHINERY ROOM. A room meeting prescribed safety requirements and in which refrigeration systems or compo- nents thereof are located (see Sections 1105 and 1106). MECHANICAL DRAFT SYSTEM. A venting system designed to remove flue or vent gases by mechanical means, that consists of an induced -draft portion under nonpositive static pressure or a forced -draft portion under positive static pressure. Forced -draft venting system. A portion of a venting sys- tem using a fan or other mechanical means to cause the removal of flue or vent gases under positive static pres- sure. Induced -draft venting system. A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under nonpositive static vent pressure. Power venting system. A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under positive static vent pressure. MECHANICAL EQUIPMENT/APPLIANCE ROOM. A room or space in which nonfuel-fired mechanical equipment and appliances are located. MECHANICAL EXHAUST SYSTEM. A system for removing air from a room or space by mechanical means. MECHANICAL JOINT. 1. A connection between pipes, fittings, or pipes and fit- tings that is not welded, brazed, caulked, soldered or solvent cemented. 2. A general form of gas or liquid -tight connections obtained by the joining of parts through a positive hold- ing mechanical construction such as, but not limited to, flanged, screwed, clamped or flared connections. MECHANICAL SYSTEM. A system specifically addressed and regulated in this code and composed of components, devices, appliances and equipment. MEDIUM -DUTY COOKING APPLIANCE. Medium - duty cooking appliances include electric discrete element ranges (with or without oven), electric and gas hot -top ranges, electric and gas griddles, electric and gas double - sided griddles, electric and gas fryers (including open deep fat fryers, donut fryers, kettle fryers and pressure fryers), electric and gas conveyor pizza ovens, electric and gas tilting skillets (braising pans) and electric and gas rotisseries. MODULAR BOILER. A steam or hot -water -heating assem- bly consisting of a group of individual boilers called modules intended to be installed as a unit with no intervening stop valves. Modules are under one jacket or are individually jack- eted. The individual modules shall be limited to a maximum input rating of 400,000 Btu/h (117 228 W) gas, 3 gallons per hour (gph) (11.4 L/h) oil, or 115 kW (electric). NATURAL DRAFT SYSTEM. A venting system designed to remove flue or vent gases under nonpositive static vent pressure entirely by natural draft. NATURAL VENTILATION. The movement of air into and out of a space through intentionally provided openings, such as windows and doors, or through nonpowered ventilators. NET OCCUPIABLE FLOOR AREA. The floor area of an occupiable space defined by the inside surfaces of its walls but excluding shafts, column enclosures and other perma- nently enclosed, inaccessible and unoccupiable areas. Obstructions in the space such as furnishings, display or stor- age racks and other obstructions, whether temporary or per- manent, shall not be deducted from the space area. NONABRASIVE/ABRASIVE MATERIALS. Nonabra- sive particulate in high concentrations, moderately abrasive particulate in low and moderate concentrations, and highly abrasive particulate in low concentrations, such as alfalfa, asphalt, plaster, gypsum and salt. 2012 INTERNATIONAL MECHANICAL CODE® 15 I " ' Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS NONCOMBUSTIBLE MATERIALS. Materials that, when tested in accordance with ASTM E 136, have at least three of four specimens tested meeting all of the following criteria: 1. The recorded temperature of the surface and interior thermocouples shall not at any time during the test rise more than 54°F (30°C) above the furnace temperature at the beginning of the test. 2. There shall not be flaming from the specimen after the first 30 seconds. 3. If the weight loss of the specimen during testing exceeds 50 percent, the recorded temperature of the surface and interior thermocouples shall not at any time during the test rise above the furnace air temperature at the beginning of the test, and there shall not be flaming of the specimen. [A] OCCUPANCY. The purpose for which a building, or portion thereof, is utilized or occupied. OCCUPIABLE SPACE. An enclosed space intended for human activities, excluding those spaces intended primarily for other purposes, such as storage rooms and equipment rooms, that are only intended to be occupied occasionally and for short periods of time. OFFSET (VENT). A combination of approved bends that make two changes in direction bringing one section of the vent out of line but into a line parallel with the other section. OUTDOOR AIR. Air taken from the outdoors, and therefore not previously circulated through the system. OUTDOOR OPENING. A door, window, louver or skylight openable to the outdoor atmosphere. OUTLET. A threaded connection or bolted flange in a piping system to which a gas -burning appliance is attached. PANEL HEATING. A method of radiant space heating in which heat is supplied by large heated areas of room surfaces. The heating element usually consists of warm water piping, warm air ducts, or electrical resistance elements embedded in or located behind ceiling, wall or floor surfaces. PELLET FUEL -BURNING APPLIANCE. A closed -com- bustion, vented appliance equipped with a fuel -feed mecha- nism for burning processed pellets of solid fuel of a specified size and composition. PIPING. Where used in this code, "piping" refers to either pipe or tubing, or both. Pipe. A rigid conduit of iron, steel, copper, brass or plas- tic. Tubing. Semirigid conduit of copper, aluminum, plastic or steel. PLASTIC, THERMOPLASTIC. A plastic that is capable of being repeatedly softened by increase of temperature and hardened by decrease of temperature. PLASTIC, THERMOSETTING. A plastic that is capable of being changed into a substantially infusible or insoluble product when cured under application of heat or chemical means. PLENUM. An enclosed portion of the building structure, other than an occupiable space being conditioned, that is designed to allow air movement, and thereby serve as part of an air distribution system. PORTABLE FUEL CELL APPLIANCE. A fuel cell gen- erator of electricity, which is not fixed in place. A portable fuel cell appliance utilizes a cord and plug connection to a grid -isolated load and has an integral fuel supply. POWER BOILER. See "Boiler." [A] PREMISES. A lot, plot or parcel of land, including any structure thereon. PRESS JOINT. A permanent mechanical joint incorporating an elastomeric seal or an elastomeric seal and corrosion -resis- tant grip ring. The joint is made with a pressing tool and jaw or ring approved by the fitting manufacturer. PRESSURE, FIELD TEST. A test performed in the field to prove system tightness. PRESSURE -LIMITING DEVICE. A pressure -responsive mechanism designed to stop automatically the operation of the pressure -imposing element at a predetermined pressure. PRESSURE RELIEF DEVICE. A pressure -actuated valve or rupture member designed to relieve excessive pressure automatically. PRESSURE RELIEF VALVE. A pressure -actuated valve held closed by a spring or other means and designed to relieve pressure automatically in excess of the device's set- ting. PRESSURE VESSELS. Closed containers, tanks or vessels that are designed to contain liquids or gases, or both, under pressure. PRESSURE VESSELS -REFRIGERANT. Any refrigerant - containing receptacle in a refrigerating system. This does not include evaporators where each separate section does not exceed 0.5 cubic foot (0.014 m') of refrigerant -containing volume, regardless of the maximum inside dimensions, evap- orator coils, controls, headers, pumps and piping. PROTECTIVE ASSEMBLY (REDUCED CLEAR- ANCE). Any noncombustible assembly that is labeled or constructed in accordance with Table 308.6 and is placed between combustible materials or assemblies and mechanical appliances, devices or equipment, for the purpose of reducing required airspace clearances. Protective assemblies attached directly to a combustible assembly shall not be considered as part of that combustible assembly. PURGE. To clear of air, water or other foreign substances. PUSH -FIT JOINTS. A type of mechanical joint consisting of elastomeric seals and corrosion -resistant tube grippers. Such joints are permanent or removable depending on the design. QUICK -OPENING VALVE. A valve that opens com- pletely by fast action, either manually or automatically con- trolled. A valve requiring one -quarter round turn or less is considered to be quick opening. RADIANT HEATER. A heater designed to transfer heat pri- marily by direct radiation. 16 2012 INTERNATIONAL MECHANICAL CODE® ''TT ' ' Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20190147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( [,Fod Uto,,by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRTRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS READY ACCESS (TO). That which enables a device, appliance or equipment to be directly reached, without requiring the removal or movement of any panel, door or sim- ilar obstruction [see "Access (to)"]. RECEIVER, LIQUID. A vessel permanently connected to a refrigeration system by inlet and outlet pipes for storage of liquid refrigerant. RECIRCULATED AIR. Air removed from a conditioned space and intended for reuse as supply air. RECLAIMED REFRIGERANTS. Refrigerants repro- cessed to the same specifications as for new refrigerants by means including distillation. Such refrigerants have been chemically analyzed to verify that the specifications have been met. Reclaiming usually implies the use of processes or procedures that are available only at a reprocessing or manu- facturing facility. RECOVERED REFRIGERANTS. Refrigerants removed from a system in any condition without necessarily testing or processing them. RECYCLED REFRIGERANTS. Refrigerants from which contaminants have been reduced by oil separation, removal of noncondensable gases, and single or multiple passes through devices that reduce moisture, acidity and particulate matter, such as replaceable core filter driers. These procedures usu- ally are performed at the field job site or in a local service shop. REFRIGERANT. A substance utilized to produce refrigera- tion by its expansion or vaporization. REFRIGERANT SAFETY CLASSIFICATIONS. Group- ings that indicate the toxicity and flammability classes in accordance with Section 1103.1. The classification group is made up of a letter (A or B) that indicates the toxicity class, followed by a number (1, 2 or 3) that indicates the flammabil- ity class. Refrigerant blends are similarly classified, based on the compositions at their worst cases of fractionation, as sepa- rately determined for toxicity and flammability. In some cases, the worst case of fractionation is the original formula- tion. Flammability. Class 1 indicates refrigerants that do not show flame propagation in air when tested by prescribed methods at specified conditions. Classes 2 and 3 signify refrigerants with "lower flammability" and "higher flam- mability," respectively; the distinction depends on both the LFL and heat of combustion. Toxicity. Classes A and B signify refrigerants with "lower toxicity" and "higher toxicity," respectively, based on pre- scribed measures of chronic (long-term, repeated expo- sures) toxicity. REFRIGERATED ROOM OR SPACE. A room or space in which an evaporator or brine coil is located for the purpose of reducing or controlling the temperature within the room or space to below 68°F (20°C). REFRIGERATING SYSTEM. A combination of intercon- nected refrigerant -containing parts constituting one closed refrigerant circuit in which a refrigerant is circulated for the purpose of extracting heat. REFRIGERATION CAPACITY RATING. Expressed as 1 horsepower (0.75 kW), 1 ton or 12,000 Btu/h (3.5 kW), shall all mean the same quantity. REFRIGERATION MACHINERY ROOM. See "Machin- eryroom." REFRIGERATION SYSTEM, ABSORPTION. A heat - operated, closed -refrigeration cycle in which a secondary fluid (the absorbent) absorbs a primary fluid (the refrigerant) that has been vaporized in the evaporator. Direct system. A system in which the evaporator is in direct contact with the material or space refrigerated, or is located in air -circulating passages communicating with such spaces. Indirect system. A system in which a brine coil cooled by the refrigerant is circulated to the material or space refrig- erated, or is utilized to cool the air so circulated. Indirect systems are distinguished by the type or method of appli- cation. REFRIGERATION SYSTEM CLASSIFICATION. Refrigeration systems are classified according to the degree of probability that leaked refrigerant from a failed connec- tion, seal or component will enter an occupied area. The dis- tinction is based on the basic design or location of the components. REFRIGERATION SYSTEM, MECHANICAL. A com- bination of interconnected refrigeration -containing parts con- stituting one closed refrigerant circuit in which a refrigerant is circulated for the purpose of extracting heat and in which a compressor is used for compressing the refrigerant vapor. REFRIGERATION SYSTEM, SELF-CONTAINED. A complete factory -assembled and tested system that is shipped in one or more sections and has no refrigerant -containing parts that are joined in the field by other than companion or block valves. [A] REGISTERED DESIGN PROFESSIONAL. An indi- vidual who is registered or licensed to practice their respec- tive design profession as defined by the statutory requirements of the professional registration laws of the state or jurisdiction in which the project is to be constructed. RETURN AIR. Air removed from an approved conditioned space or location and recirculated or exhausted. RETURN AIR SYSTEM. An assembly of connected ducts, plenums, fittings, registers and grilles through which air from the space or spaces to be heated or cooled is conducted back to the supply unit (see also "Supply air system") ROOM HEATER VENTED. A free-standing heating unit burning solid or liquid fuel for direct heating of the space in and adjacent to that in which the unit is located. SAFETY VALVE. A valve that relieves pressure in a steam boiler by opening fully at the rated discharge pressure. The valve is of the spring -pop type. SELF-CONTAINED EQUIPMENT. Complete, factory - assembled and tested, heating, air-conditioning or refrigera- tion equipment installed as a single unit, and having all work- ing parts, complete with motive power, in an enclosed unit of said machinery. 2012 INTERNATIONAL MECHANICAL CODE® 17 I II I CoTy,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg Podortuodmg FoIRbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS [B] SHAFT. An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and the roof. [B] SHAFT ENCLOSURE. The walls or construction form- ing the boundaries of a shaft. [B] SLEEPING UNIT. A room or space in which people sleep, which can also include permanent provisions for liv- ing, eating, and either sanitation or kitchen facilities but not both. Such rooms and spaces that are also part of a dwelling unitare not sleeping units. [B] SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed to resist the passage of smoke. The device is installed to operate automatically, con- trolled by a smoke detection system, and where required, is capable of being positioned from a fire command center. [B] SMOKE -DEVELOPED INDEX. A numerical value assigned to a material tested in accordance with ASTM E 84. SOLID FUEL (COOKING APPLICATIONS). Applicable to commercial food service operations only, solid fuel is any bulk material such as hardwood, mesquite, charcoal or bri- quettes that is combusted to produce heat for cooking opera- tions. SOURCE CAPTURE SYSTEM. A mechanical exhaust system designed and constructed to capture air contaminants at their source and to exhaust such contaminants to the out- door atmosphere. [FG] STATIONARY FUEL CELL POWER PLANT. A self-contained package or factory -matched packages which constitute an automatically operated assembly of integrated systems for generating useful electrical energy and recover- able thermal energy that is permanently connected and fixed in place. STEAM -HEATING BOILER. A boiler operated at pres- sures not exceeding 15 psi (103 kPa) for steam. STOP VALVE. A shutoff valve for controlling the flow of liquid or gases. [B] STORY. That portion of a building included between the upper surface of a floor and the upper surface of the floor next above, except that the topmost story shall be that portion of a building included between the upper surface of the top- most floor and the ceiling or roof above. STRENGTH, ULTIMATE. The highest stress level that the component will tolerate without rupture. SUPPLY AIR. That air delivered to each or any space sup- plied by the air distribution system or the total air delivered to all spaces supplied by the air distribution system, which is provided for ventilating, heating, cooling, humidification, dehumidification and other similar purposes. SUPPLY AIR SYSTEM. An assembly of connected ducts, plenums, fittings, registers and grilles through which air, heated or cooled, is conducted from the supply unit to the space or spaces to be heated or cooled (see also "Return air system"). THEORETICAL AIR. The exact amount of air required to supply oxygen for complete combustion of a given quantity of a specific fuel. THERMAL RESISTANCE (R). A measure of the ability to retard the flow of heat. The R-value is the reciprocal of ther- mal conductance. [P] THIRD -PARTY CERTIFICATION AGENCY. An approved agency operating a product or material certification system that incorporates initial product testing, assessment and surveillance of a manufacturer's quality control system. [P] THIRD -PARTY CERTIFIED. Certification obtained by the manufacturer indicating that the function and perfor- mance characteristics of a product or material have been determined by testing and ongoing surveillance by an approved third -party certification agency. Assertion of certi- fication is in the form of identification in accordance with the requirements of the third -party certification agency. [P] THIRD -PARTY TESTED. Procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified require- ments. TLV-TWA (THRESHOLD LIMIT VALUE -TIME - WEIGHTED AVERAGE). The time -weighted average con- centration of a refrigerant or other chemical in air for a nor- mal 8-hour workday and a 40-hour workweek, to which nearly all workers are repeatedly exposed, day after day, without adverse effects, as adopted by the American Confer- ence of Government Industrial Hygienists (ACGIH). TOILET ROOM. A room containing a water closet and, fre- quently, a lavatory, but not a bathtub, shower, spa or similar bathing fixture. TOXICITY CLASSIFICATION. Refrigerants shall be classified for toxicity to one of two classes in accordance with ASHRAE 34: Class A. Refrigerants for which toxicity has not been identified at concentrations less than or equal to 400 parts per million (ppm), based on data used to determine Threshold Limit Value -Time -Weighted Average (TLV- TWA) or consistent indices. Class B. Refrigerants for which there is evidence of toxic- ity at concentrations below 400 ppm, based on data used to determine TLV-TWA or consistent indices. TRANSITION FITTINGS, PLASTIC TO STEEL. An adapter for joining plastic pipe to steel pipe. The purpose of this fitting is to provide a permanent, pressure -tight connec- tion between two materials which cannot be joined directly one to another. UNIT HEATER. A self-contained appliance of the fan type, designed for the delivery of warm air directly into the space in which the appliance is located. VENT. A pipe or other conduit composed of factory -made components, containing a passageway for conveying combus- tion products and air to the atmosphere, listed and labeled for use with a specific type or class of appliance. Pellet vent A vent listed and labeled for use with listed pellet -fuel -burning appliances. 18 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,od U:oa oAYUP, S I kliF ( [,Fod Uto,,by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRTRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DEFINITIONS Type L vent. A vent listed and labeled for use with the following: 1. Oil -burning appliances that are listed for use with Type L vents. 2. Gas -fired appliances that are listed for use with Type B vents. VENT CONNECTOR. The pipe that connects an approved fuel -fired appliance to a vent. VENT DAMPER DEVICE, AUTOMATIC. A device intended for installation in the venting system, in the outlet of an individual automatically operated fuel -burning appliance that is designed to open the venting system automatically when the appliance is in operation and to close off the vent- ing system automatically when the appliance is in a standby or shutdown condition. VENTILATION. The natural or mechanical process of sup- plying conditioned or unconditioned air to, or removing such air from, any space. VENTILATION AIR. That portion of supply air that comes from the outside (outdoors), plus any recirculated air that has been treated to maintain the desired quality of air within a designated space. VENTING SYSTEM. A continuous open passageway from the flue collar of an appliance to the outside atmosphere for the purpose of removing flue or vent gases. A venting system is usually composed of a vent or a chimney and vent connec- tor, if used, assembled to form the open passageway. WATER HEATER. Any heating appliance or equipment that heats potable water and supplies such water to the pota- ble hot water distribution system. ZONE. One occupiable space or several occupiable spaces with similar occupancy classification (see Table 403.3), occupant density, zone air distribution effectiveness and zone primary airflow rate per unit area. 2012 INTERNATIONAL MECHANICAL CODE® 19 I " ' Copy,ght @ zoI I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep so.2.o190147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,oddtoa oAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 20 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( rig odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED.. COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER GENERAL REGULATIONS SECTION 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating and air-condi- tioning systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the International Energy Conservation Code. 301.3 Identification. Each length of pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identification of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings and components shall be third party certified as con- forming to NSF 14. 301.5 Third -party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced stan- dards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Pip- ing, tubing and fittings shall either be tested by an approved third -party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equipment, fuel gas -fired appliances and fuel gas -fired appliance venting systems shall be in accordance with the International Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed and labeled for the application in which they are installed and used, unless otherwise approved in accor- dance with Section 105. Exception: Listing and labeling of equipment and appli- ances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Labeling. Labeling shall be in accordance with the procedures set forth in Sections 301.8.1 through 301.8.2.3. 301.8.1 Testing. An approved agency shall test a repre- sentative sample of the mechanical equipment and appli- ances being labeled to the relevant standard or standards. The approved agency shall maintain a record of all of the tests performed. The record shall provide sufficient detail to verify compliance with the test standard. 301.8.2 Inspection and identification. The approved agency shall periodically perform an inspection, which shall be in -plant if necessary, of the mechanical equipment and appliances to be labeled. The inspection shall verify that the labeled mechanical equipment and appliances are representative of the mechanical equipmentand appliances tested. 301.8.2.1 Independent. The agency to be approved shall be objective and competent. To confirm its objec- tivity, the agency shall disclose all possible conflicts of interest. 301.8.2.2 Equipment. An approved agency shall have adequate equipment to perform all required tests. The equipment shall be periodically calibrated. 301.8.2.3 Personnel. An approved agency shall employ experienced personnel educated in conducting, supervising and evaluating tests. 301.9 Label information. A permanent factory -applied nameplate(s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer's name or trade- mark, the model number, serial number and the seal or mark of the approved agency. A label shall also include the follow- ing: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of individual electrical components in volts, amperes or watts, motor phase; Btu/h (W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); mini- mum hourly rating for units having step or automatic modulating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel -burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: electric rating in volts, amperes and phase; Btu/h (W) output rating; individual marking for each electrical component in amperes or watts, volts and phase; and required clear- ances from combustibles. 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with NFPA 70. 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the International Plumbing Code. 301.12 Fuel types. Fuel -fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a different fuel, except where approved and converted in accordance with the manufac- turer's instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Vibration isolation. Where vibration isolation of equipmentand appliances is employed, an approved means of 2012 INTERNATIONAL MECHANICAL CODE® 21 I II I Copy,EIL@?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS supplemental restraint shall be used to accomplish the sup- port and restraint. 301.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accor- dance with the International Building Code. [B] 301.16 Flood hazard. For structures located in flood haz- ard areas, mechanical systems, equipment and appliances shall be located at or above the elevation required by Section 1612 of the International Building Code for utilities and attendant equipment. Exception: Mechanical systems, equipment and appli- ances are permitted to be located below the elevation required by Section 1612 of the of the International Build- ing Code for utilities and attendant equipment provided that they are designed and installed to prevent water from entering or accumulating within the components and to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to such elevation. [B] 301.16.1 High -velocity wave action. In flood hazard areas subject to high -velocity wave action, mechanical systems and equipment shall not be mounted on or pene- trate walls intended to break away under flood loads. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to protect against the entrance of rodents in accordance with the International Building Code. 301.18 Seismic resistance. When earthquake loads are appli- cable in accordance with the International Building Code, mechanical system supports shall be designed and installed for the seismic forces in accordance with the International Building Code. SECTION 302 PROTECTION OF STRUCTURE 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the International Building Code. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance -rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire -resistance rating shall be protected in accordance with Chapter 7 of the International Building Code. [B] 302.3 Cutting, notching and boring in wood framing. The cutting, notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.4. [B] 302.3.1 Joist notching. Notches on the ends of joists shall not exceed one-fourth the joist depth. Holes bored in joists shall not be within 2 inches (51 mm) of the top or bottom of the joist, and the diameter of any such hole shall not exceed one-third the depth of the joist. Notches in the top or bottom of joists shall not exceed one -sixth the depth and shall not be located in the middle third of the span. [B] 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, any wood stud is permitted to be cut or notched not to exceed 25 percent of its depth. Cut- ting or notching of studs not greater than 40 percent of their depth is permitted in nonbearing partitions support- ing no loads other than the weight of the partition. [B] 302.3.3 Bored holes. A hole not greater in diameter than 40 percent of the stud depth is permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the depth of the stud are permitted in nonbearing parti- tions or in any wall where each bored stud is doubled, pro- vided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 0.625 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. [B] 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite veneer lumber, structural glue -laminated members and I joists are prohibited except where permitted by the manufacturer's recommendations or where the effects of such alterations are specifically considered in the design of the member. [B] 302.4 Alterations to trusses. Truss members and compo- nents shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design professional. Alterations resulting in the addition of loads to any member, such as HVAC equip- ment and water heaters, shall not be permitted without verifi- cation that the truss is capable of supporting such additional loading. [B] 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.3. [B] 302.5.1 Cutting, notching and boring holes in struc- tural steel framing. The cutting, notching and boring of holes in structural steel framing members shall be as pre- scribed by the registered design professional. [B] 302.5.2 Cutting, notching and boring holes in cold - formed steel framing. Flanges and lips of load -bearing cold -formed steel framing members shall not be cut or notched. Holes in webs of load -bearing cold -formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, penetration spacing or minimum hole edge distance as prescribed by the registered design professional. Cutting, notching and boring holes of steel floor/roof decking shall be as prescribed by the registered design professional. [B] 302.5.3 Cutting, notching and boring holes in non- structural cold -formed steel wall framing. Flanges and 22 2012 INTERNATIONAL MECHANICAL CODE® C,Ty,ght @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 1 av PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( [IFod Ut.. by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS lips of nonstructural cold -formed steel wall studs shall not be cut or notched. Holes in webs of nonstructural cold - formed steel wall studs shall be permitted along the center- line of the web of the framing member, shall not exceed P/z inches (38 mm) in width or 4 inches (102 mm) in length, and shall not be spaced less than 24 inches (610 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. SECTION 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requirements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Fuel -fired appliances shall not be located in, or obtain combustion air from, any of the fol- lowing rooms or spaces: 1. Sleeping rooms. 2. Bathrooms. 3. Toilet rooms. 4. Storage closets. 5. Surgical rooms. Exception: This section shall not apply to the following appliances: 1. Directventappliances that obtain all combustion airdirectly from the outdoors. 2. Solid fuel -fired appliances, provided that the room is not a confined space and the building is not of unusually tight construction. 3. Appliances installed in a dedicated enclosure in which all combustion air is taken directly from the outdoors, in accordance with Chapter 7. Access to such enclosure shall be through a solid door, weather-stripped in accordance with the exterior door air leakage requirements of the International Energy Conservation Code and equipped with an approved self -closing device. 303.4 Protection from damage. Appliances shall not be installed in a location where subject to mechanical damage unless protected by approved barriers. 303.5 Indoor locations. Fuel -fired furnaces, water heaters and boilers installed in closets and alcoves shall be listed for such installation. For purposes of this section, a closet or alcove shall be defined as a room or space having a volume less than 12 times the total volume of fuel -fired appliances other than boilers and less than 16 times the total volume of boilers. Room volume shall be computed using the gross floor area and the actual ceiling height up to a maximum computation height of 8 feet (2438 mm). 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor instal- lation. 303.7 Pit locations. Appliances installed in pits or excava- tions shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back a minimum of 12 inches (305 mm) from the appliance. Where the depth exceeds 12 inches (305 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend a mini- mum of 4 inches (102 mm) above adjoining grade and shall have sufficient lateral load -bearing capacity to resist collapse. The appliance shall be protected from flooding in an approved manner. [B] 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION 304 INSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer's installation instructions and this code. Manufacturer's installation instructions shall be available on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer's installation instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less restrictive than the conditions of the listing of the equipment or appliance or the manufacturer's installation instructions, the condi- tions of the listing and the manufacturer's installation instructions shall apply. 304.3 Elevation of ignition source. Equipment and appli- ances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel -dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unitand that communicate directly with a private garage through openings shall be considered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which there is a fuel -fired appliance shall be by means of a vestibule providing a two -doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accor- dance with Section 304.3. Exception: This section shall not apply to appliance installations complying with Section 304.6. 2012 INTERNATIONAL MECHANICAL CODE® 23 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, handling or dispensing of combustible, flammable or explosive materials occurs. [FG] 304.5 Hydrogen -generating and refueling opera- tions. Hydrogen -generating and refueling appliances shall be installed and located in accordance with their listing and the manufacturer's instructions. Ventilation shall be required in accordance with Section 304.5.1, 304.5.2 or 304.5.3 in public garages, private garages, repair garages, automotive motor fuel -dispensing facilities and parking garages that contain hydrogen -generating appliances or refueling systems. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be con- sidered to be part of the private garage. [FG] 304.5.1 Natural ventilation. Indoor locations intended for hydrogen -generating or refueling operations shall be limited to a maximum floor area of 850 square feet (79 m') and shall communicate with the outdoors in accordance with Sections 304.5.1.1 and 304.5.1.2. The maximum rated output capacity of hydrogen generating appliances shall not exceed 4 standard cubic feet per min- ute (0.00189 m3/s) of hydrogen for each 250 square feet (23.2 m') of floor area in such spaces. The minimum cross -sectional dimension of air openings shall be 3 inches (76 mm). Where ducts are used, they shall be of the same cross -sectional area as the free area of the openings to which they connect. In such locations, equipment and appliances having an ignition source shall be located such that the source of ignition is not within 12 inches (305 mm) of the ceiling. [FG] 304.5.1.1 Two openings. Two permanent open- ings shall be provided within the garage. The upper opening shall be located entirely within 12 inches (305 mm) of the ceiling of the garage. The lower opening shall be located entirely within 12 inches (305 mm) of the floor of the garage. Both openings shall be provided in the same exterior wall. The openings shall communi- cate directly with the outdoors and shall have a mini- mum free area of V, square foot per 1,000 cubic feet (1 m'/610 m') of garage volume. [FG] 304.5.1.2 Louvers and grilles. In calculating free area required by Section 304.5.1, the required size of openings shall be based on the net free area of each opening. If the free area through a design of louver or grille is known, it shall be used in calculating the size opening required to provide the free area specified. If the design and free area are not known, it shall be assumed that wood louvers will have 25 percent free area and metal louvers and grilles will have 75 percent free area. Louvers and grilles shall be fixed in the open position. [FG] 304.5.2 Mechanical ventilation. Indoor locations intended for hydrogen -generating or refueling operations shall be ventilated in accordance with Section 502.16. In such locations, equipmentand appliances having an igni- tion source shall be located such that the source of ignition is below the mechanical ventilation outlet(s). [FG] 304.5.3 Specially engineered installations. As an alternative to the provisions of Sections 304.5.1 and 304.5.2 the necessary supply of air for ventilation and dilution of flammable gases shall be provided by an approved engineered system. 304.6 Public garages. Appliances located in public garages, motor fueling -dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed a mini- mum of 8 feet (2438 mm) above the floor. Where motor vehi- cles are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (305 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehi- cle impact and installed in accordance with Section 304.3 and NFPA 30A. 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1829 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehi- cle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and fur- nace rooms shall be protected as required by the International Building Code. 304.9 Clearances to combustible construction. Heat -pro- ducing equipment and appliances shall be installed to main- tain the required clearances to combustible construction as specified in the listing and manufacturer's instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such consider- ations as door swing, drawer pull, overhead projections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending not less than 3 inches (76 mm) above adjoining grade or shall be suspended not less than 6 inches (152 mm) above adjoining grade. Such support shall be in accordance with the manufacturer's instal- lation instructions. [B] 304.11 Guards. Guards shall be provided where appli- ances, equipment, fans or other components that require ser- vice and roof hatch openings are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, components and roof hatch openings and the top of the guard shall be located not less than 42 inches (1067 mm) above the elevated surface adja- cent to the guard. The guard shall be constructed so as to pre- vent the passage of a 21-inch-diameter (533 mm) sphere and 24 2012 INTERNATIONAL MECHANICAL CODE® 17 Co,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nmmbsx 100760189 oc Sep SO, 2019 o 147 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( N ,Fod,Yo,,bymytl,dputy,o,Abau�to,o,sd Single—mly mpymg andmg d-PyoFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS shall comply with the loading requirements for guards speci- fied in the International Building Code. 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be perma- nently marked in an approved manner that uniquely identifies the appliance and the area it serves. SECTION 305 PIPING SUPPORT 305.1 General. All mechanical system piping shall be sup- ported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have suffi- cient strength to withstand all anticipated static and specified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with pip- ing shall be of approved materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment Hangers and anchors shall be attached to the building construction in an approved manner. 305.4 Interval of support Piping shall be supported at dis- tances not exceeding the spacing specified in Table 305.4, or in accordance with MSS SP-69. 305.5 Protection against physical damage. In concealed locations where piping, other than cast-iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than I'/, inches (38 mm) from the near- est edge of the member, the pipe shall be protected by shield plates. Protective steel shield plates having a minimum thick- ness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend a minimum of 2 inches (51 mm) above sole plates and below top plates. SECTION 306 ACCESS AND SERVICE SPACE 306.1 Access for maintenance and replacement. Appli- ances shall be accessible for inspection, service, repair and replacement without disabling the function of a fire -resis- tance -rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space at least 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be pro- vided in front of the control side to service an appliance. 306.1.1 Central furnaces. Central furnaces within com- partments or alcoves shall have a minimum working space clearance of 3 inches (76 mm) along the sides, back and top with a total width of the enclosing space being at least 12 inches (305 mm) wider than the furnace. Furnaces hav- ing a firebox open to the atmosphere shall have at least 6 inches (152 mm) working space along the front combus- tion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the require- ments of Chapter 7. Exception: This section shall not apply to replacement appliances installed in existing compartments and TABLE 305.4 PIPING SUPPORT SPACING PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feeU MAXIMUM VERTICAL SPACING (feeU ABS pipe 4 10, Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, P/g inch diameter and smaller 6 10 Brass tubing, P/i inch diameter and larger 10 10 Cast-iron pipe' 5 15 Copper or copper -alloy pipe 12 10 Copper or copper -alloy tubing, 1 11,-inch diameter and smaller 6 10 Copper or copper -alloy tubing, 1'/y--inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10` CPVC pipe or tubing, 111, inch and larger 4 10` Lead pipe Continuous 4 PB pipe or tubing 2E/g (32 inches) 4 PEX tubing 2E/g (32 inches) 10` Polypropylene (PP) pipe or tubing, 1 inch or smaller 2E/g (32 inches) 10` Polypropylene (PP) pipe or tubing, 1'/,inches or larger 4 10, PVC pipe 4 10, Steel tubing 8 10 Steel pipe 12 15 For SI 1 inch — 25 4 mm, 1 foot= 304 8 min a See Section 301 18 b The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed c Mid-storyguide alcoves where the working space clearances are in accordance with the equipment or appliance manufac- turer's installation instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed passage- way measuring not less than 36 inches (914 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accessed by an opening or door and an unobstructed pas- sageway measuring not less than 24 inches (610 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep and the height of the appli- ance, but not less than 30 inches (762 min), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed passage- way large enough to allow removal of the largest appliance. 2012 INTERNATIONAL MECHANICAL CODE® 25 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nmmbsx1oovco189 oc SIP so.2.o19o14v PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, ',ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS The passageway shall not be less than 30 inches (762 mm) high and 22 inches (559 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passage- way shall have continuous solid flooring not less than 24 inches (610 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions 1. The passageway and level service space are not required where the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1829 mm) high and 22 inches (559 mm) wide for its entire length, the passageway shall be not greater than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with NITA 70. 306.4 Appliances under floors. Underfloor spaces contain- ing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall not be less than 30 inches (762 mm) high and 22 inches (559 mm) wide, nor more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the appliance. If the depth of the passageway or the service space exceeds 12 inches (305 mm) below the adjoin- ing grade, the walls of the passageway shall be lined with concrete or masonry. Such concrete or masonry shall extend a minimum of 4 inches (102 mm) above the adjoining grade and shall have sufficient lateral -bearing capacity to resist col- lapse. The clear access opening dimensions shall be a mini- mum of 22 inches by 30 inches (559 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level ser- vice space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet high (1929 mm) and 22 inches (559 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with NITA 70. 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access such equipment or appli- ances, an interior or exterior means of access shall be pro- vided. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center. The uppermost rung shall be a maximum of 24 inches (610 mm) below the upper edge of the roof hatch, roof or parapet, as appli- cable. 3. Ladders shall have a toe spacing not less than 6 inches (152 mm) deep. 4. There shall be a minimum of 18 inches (457 mm) between rails. 5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1kg) load. 6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds per square foot (488.2 kg/ m'). Landing dimensions shall be not less than 18 inches (457 mm) and not less than the width of the ladder served. A guard rail shall be provided on all open sides of the landing. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be a minimum of 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintained from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15-inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed. 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches (762 mm) by 30 inches (762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Access to ladders shall be provided at all times. Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R-3 occupancies. 26 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( od,,to—by POVO d party. o,±RYb�toc P,,Uoosd Smglo mlym,ymg ando Nyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units hori- zontal (25-percent slope) or greater and having an edge more than 30 inches (762 min) above grade at such edge, a level platform shall be provided on each side of the appli- ance or equipment to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 min) in any dimension and shall be pro- vided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be con- structed so as to prevent the passage of a 21-inch diameter (533 min) sphere and shall comply with the loading requirements for guards specified in the International Building Code. Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33-percent slope). Where access involves obstructions greater than 30 inches (762 min) in height, such obstructions shall be provided with ladders installed in accordance with Section 306.5 or stairs installed in accordance with the requirements specified in the Interna- tional Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical requirements. A receptacle outlet shall be provided at or near the equipment location in accor- dance with NBPA 70. SECTION 307 CONDENSATE DISPOSAL 307.1 Fuel -burning appliances. Liquid combustion by-prod- ucts of condensing appliances shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer's installation instructions. Condensate piping shall be of approved corrosion -resistant material and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum hori- zontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1-percent slope). 307.2 Evaporators and cooling coils. Condensate drain sys- tems shall be provided for equipment and appliances contain- ing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.4. 307.2.1 Condensate disposal. Condensate from all cool- ing coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one -eighth unit vertical in 12 units horizontal (1-percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross -linked polyethylene, polybutyl- ene, polyethylene, ABS, CPVC or PVC pipe or tubing. All components shall be selected for the pressure and tempera- ture rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the International Plumbing Code relative to the material type. Condensate waste and drain line size shall be not less than '/q inch (19 min) internal diameter and shall not decrease in size from the drain pan connec- tion to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration '/q inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1l/4 inch Over 90 tons to 125 tons of refrigeration 1l/z inch Over 125 tons to 250 tons of refrigeration 2 inch 1 inch —254 Pont, 1ton —3517 kW 307.2.3 Auxiliary and secondary drain systems. In addi- tion to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel -fired appli- ance that produces condensate: An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a minimum depth of P/, inches (38 mm), shall not be less than 3 inches (76 mm) larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion -resistant mate- rial. Galvanized sheet steel pans shall have a mini- mum thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage). Nonmetallic pans shall have a minimum thickness of not less than 0.0625 inch (1.6 mm). A separate overflow drain line shall be connected to the drain pan provided with the equipment Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection. An auxiliary drain pan without a separate drain line shall be provided under the coils on which conden- sate will occur. Such pan shall be equipped with a water -level detection device conforming to UL 508 that will shut off the equipment served prior to over- flow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this sec- tion. A water -level detection device conforming to UL 508 shall be provided that will shut off the equip- ment served in the event that the primary drain is 2012 INTERNATIONAL MECHANICAL CODE® 27 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx 100760189 oc Sep V,2019o147 To (PDT) p—Pot to IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg and-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equip- ment -supplied drain pan, located at a point higher than the primary drain line connection and below the overflow rim of such pan. Exception: Fuel -fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system. 307.2.3.1 Water -level monitoring devices. On down - flow units and all other coils that do not have a second- ary drain or provisions to install a secondary or auxiliary drain pan, a water -level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be permitted. 307.2.3.2 Appliance, equipment and insulation in pans. Where appliances, equipment or insulation are subject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment and insulation shall be installed above the rim of the pan. Supports located inside of the pan to support the appliance or equipment shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. SECTION 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to combustible materials and combusti- ble assemblies for chimneys, vents, kitchen exhaust equip- ment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance with the requirements of this section except that such clearances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncom- bustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Where a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convection in such space. Protective assemblies shall not be placed less than 1 inch (25 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clear- ances to combustible assemblies or combustible materials shall be based on the utilization of a reduced clearance pro- tective assembly in accordance with Section 308.5 or 308.6. 308.5 Labeled assemblies. The allowable clearance reduc- tion shall be based on an approved reduced clearance protec- tive assembly that is listed and labeled in accordance with UL 1618. 308.6 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.6. Where required clearances are not listed in Table 308.6, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrapolation below the range of the table. 308.7 Solid fuel -burning appliances. The clearance reduc- tion methods specified in Table 308.6 shall not be utilized to reduce the clearance required for solid fuel -burning appli- ances that are labeled for installation with clearances of 12 inches (305 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (305 mm), the clearance reduction methods of Table 308.6 shall not reduce the clearance to less than 12 inches (305 mm). 308.8 Masonry chimneys. The clearance reduction methods specified in Table 308.6 shall not be utilized to reduce the clearances required for masonry chimneys as specified in Chapter 8 and the International Building Code. 308.9 Chimney connector pass-throughs. The clearance reduction methods specified in Table 308.6 shall not be uti- lized to reduce the clearances required for chimney connector pass-throughs as specified in Section 803.10.4. 308.10 Masonry fireplaces. The clearance reduction meth- ods specified in Table 308.6 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in Chapter 8 and the International Building Code. 308.11 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.6 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a shaft. [B] SECTION 309 TEMPERATURE CONTROL [B] 309.1 Space -heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space -heating systems capable of maintaining a minimum indoor temperature of 68°F (20°C) at a point 3 feet (914 mm) above floor on the design heating day. The installation of por- table space heaters shall not be used to achieve compliance with this section. Exception: Interior spaces where the primary purpose is not associated with human comfort. [F] SECTION 310 EXPLOSION CONTROL [F] 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control where required by the International Fire Code. Explosion control systems shall be designed and installed in accordance with Section 911 of the International Fire Code. 28 2012 INTERNATIONAL MECHANICAL CODE® C,Ty,ght @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 1 av PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( riR [IFod Ut.. by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE FOR REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER GENERAL REGULATIONS TABLE 308.6 CLEARANCE REDUCTION METHODSb REDUCED CLEARANCE WITH PROTECTION (inches)a Horizontal combustible assemblies Horizontal combustible assemblies located beneath the heat source and all located above the heat source vertical combustible assemblies Required clearance to combustibles Required clearance to combustibles without protection (inches)a without protection (inches) 36 18 9 6 36 18 9 6 TYPE OF PROTECTIVE ASSEMBLYa Galvanmed sheet steel, having a mwmvm thickness of 0 0236 inch (0 6010 min) (No 18 9 5 3 12 6 3 3 24 gage), mounted on 1-mch glass fiber or mmeral wool ban reinforced with wire on the back, 1 inch off the combustible assembly Galvanmed sheet steel, having a mwmvm thickness of 0 0236 inch (0 6010 min) (No 18 9 5 3 12 6 3 2 24 gage), spaced 1 inch off the combustible assembly Two layers of galvanmed sheet steel, having a mmunum thickness of 0 0236 inch 18 9 5 3 12 6 3 3 (0 6010 min) (No 24 gage), having a 1-mch airspace between layers, spaced 1 inch off the combustible assembly Two layers of galvanmed sheet steel, having a mmunum thickness of 0 0236 inch 18 9 5 3 12 6 3 3 (0 6010 min) (No 24 gage), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 0 5-mch inorganic insulating board, over 1 inch of fiberglass or mmeral wool halt, 24 12 6 4 18 9 5 3 against the combustible assembly 31/y- inch brickwall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 31/z-mch brick wall, against the combustible wall — — — — 24 12 6 5 For SI 1 inch — 25 4 min, °C — [(°F)-32]/1 8, 1 pound per cubic foot= 16 02 kg/m', 10 Btu • in/fiz • h • °F — 0 144 W/m' • K a Mineral wool and glass fiber baits (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1,500°F Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 10 Btu • in/(ft' • h • °F) or less Insulation board shall be formed of noncombustible material b For limitations on clearance reduction for solid fuel -burning appliances, masonry chimneys, connector pass-throughs, masonry fire places and kitchen ducts, see Sections 308 7 through 308 11 [F] SECTION 311 SMOKE AND HEAT VENTS [F] 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one-story buildings where required by the International Fire Code. Smoke and heat vents shall be designed and installed in accordance with the International Fire Code. SECTION 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equip- ment shall be determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183. Alterna- tively, design loads shall be determined by an approved equivalent computation procedure, using the design parame- ters specified in Chapter 3 [CE] of the International Energy Conservation Code. 2012 INTERNATIONAL MECHANICAL CODE® 29 I I I I Copyright aa?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx 100760189 oc Sep so.2.o19 o 147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUh ,Aoddtoario AYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,tocauihorisd Single —ooly, copying PodoehuodmgFokbad ANY VNAVTHORIVED REPRODUCTION ORDISIRIBVTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 30 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( rig odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED.. COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401.2 Ventilation required. Every occupied space shall be ventilated by natural means in accordance with Section 402 or by mechanical means in accordance with Section 403. Where the air infiltration rate in a dwelling unit is less than 5 air changes per hour when tested with a blower door at a pres- sure of 0.2-inch water column (50 Pa) in accordance with Section R402.4.1.2 of the International Energy Conservation Code, the dwelling unit shall be ventilated by mechanical means in accordance with Section 403. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied. 401.4 Intake opening location. Air intake openings shall comply with all of the following: 1. Intake openings shall be located a minimum of 10 feet (3048 mm) from lot lines or buildings on the same lot. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) hori- zontally from any hazardous or noxious contaminant source, such as vents, streets, alleys, parking lots and loading docks, except as specified in Item 3 or Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks pro- vided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured from the closest edge of the street or public way. Intake openings shall be located not less than 3 feet (914 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 4. Intake openings on structures in flood hazard areas shall be at or above the elevation required by Section 1612 of the International Building Code for utilities and attendant equipment. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion -resistant screens, louvers or grilles. Openings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Louvers that protect air intake openings in structures located in hurri- cane -prone regions, as defined in the International Building Code, shall comply with AMCA 550. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with the International Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING AIR INTAKE OPENINGS MINIMUM AND MAXIMUM OPENING OUTDOOR OPENING TYPE SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in Not < 1/4 inch and not > l/z inch residential occupancies Intake openings in other > 1/4 inch and not > 1 inch than residential occupancies For SI 1 inch= 25 4 Earn 401.6 Contaminant sources. Stationary local sources pro- ducing airborne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chapter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the build- ing. SECTION 402 NATURAL VENTILATION [B] 402.1 Natural ventilation. Natural ventilation of an occupied space shall be through windows, doors, louvers or other openings to the outdoors. The operating mechanism for such openings shall be provided with ready access so that the openings are readily controllable by the building occupants. [B] 402.2 Ventilation area required. The minimum open - able area to the outdoors shall be 4 percent of the floor area being ventilated. [B] 402.3 Adjoining spaces. Where rooms and spaces with- out openings to the outdoors are ventilated through an adjoin- ing room, the opening to the adjoining rooms shall be unobstructed and shall have an area not less than 8 percent of the floor area of the interior room or space, but not less than 25 square feet (2.3 m'). The minimum openable area to the outdoors shall be based on the total floor area being venti- lated. Exception: Exterior openings required for ventilation shall be permitted to open into a thermally isolated sun - room addition or patio cover, provided that the openable area between the sunroom addition or patio cover and the interior room has an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86 m'). The minimum openable area to 2012 INTERNATIONAL MECHANICAL CODE® 31 I I I I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6N„mbsx,00vco,es oc Sep so.2.o19 o, 47 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,od„dtoa oAYUP, ( ,ep,odmYo¢ebymytl,dputy,o,ANb,No,au o,sd Stoglo—ooly mpymg Pod-Pyodmgp,okb,hd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION the outdoors shall be based on the total floor area being ventilated. [B] 402.4 Openings below grade. Where openings below grade provide required natural ventilation, the outside hori- zontal clear space measured perpendicular to the opening shall be one and one-half times the depth of the opening. The depth of the opening shall be measured from the average adjoining ground level to the bottom of the opening. SECTION 403 MECHANICAL VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure. The system to convey ventilation air shall be designed and installed in accordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding that obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. 403.2.1 Recirculation of air. The outdoor air required by Section 403.3 shall not be recirculated. Air in excess of that required by Section 403.3 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other spaces where more than 10 percent of the resulting supply airstream consists of air recirculated from these spaces. 3. Where mechanical exhaust is required by Note b in Table 403.3, recirculation of air from such spaces shall be prohibited. All air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3. 4. Where mechanical exhaust is required by Note g in Table 403.3, mechanical exhaust is required and recirculation is prohibited where more than 10 per- cent of the resulting supply airstream consists of air recirculated from these spaces. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3, air transferred from occupiable spaces is not prohibited from serving as makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Sec- tion 403.3. The required outdoor airflow rates specified in Table 403.3 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor airflow rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. The occupant load utilized for design of the ventilation system shall not be less than the number determined from the esti- mated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ventilation system shall be designed to supply the required rate of ventilation air contin- uously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of smoking lounges, the ventilation rates in Table 403.3 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a smoking lounge, the ventilation system serving the space shall be designed to provide ventilation over and above that required by Table 403.3 in accordance with accepted engineering practice. Exception: The occupant load is not required to be deter- mined based on the estimated maximum occupant load rate indicated in Table 403.3 where approved statistical data document the accuracy of an alternate anticipated occupant density. 403.3.1 Zone outdoor airflow. The minimum outdoor air- flow required to be supplied to each zone shall be deter- mined as a function of occupancy classification and space air distribution effectiveness in accordance with Sections 403.3.1.1 through 403.3.1.3. 32 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 01 av PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( �ep�odUt.. byzoyUb,dparty.oPAembmoo Uoosd Single—mly mpymg Pod-PyodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION TABLE 403.3 MINIMUM VENTILATION RATES PEOPLE OUTDOOR AREA OUTDOOR EXHAUST AIRFLOW OCCUPANCY CLASSIFICATION OCCUPANT DENSITY AIRFLOW RATE IN AIRFLOW RATE IN RATE #11000 FT" BREATHING ZONE, BREATHING ZONE, CFM/FT21 R CFM/PERSON R. CFM/FT2 Correctional facilities Cells without plumbing fixtures 25 5 012 with plumbing fixtures 25 5 0 12 10 Dining halls (see food and beverage service) Guard stations 15 5 006 — Day room 30 5 006 — Booking/waiting 50 7 5 006 — Dry cleaners, laundries Coin -operated dry cleaner 20 15 — — Coin -operated laundries 20 7 5 006 — Commercial dry cleaner 30 30 Commercial laundry 10 25 Storage, pick up 30 7 5 0 12 — Education Auditoriums 150 5 006 — Corridors (see public spaces) — — — — Media center 25 10 0 12 — Sports locker rooms — — — 0 5 Music/theater/dance 35 10 006 — Smoking lounges' 70 60 — Day care (through age 4) 25 10 0 18 — Classrooms (ages 5-8) 25 10 0 12 — Classrooms (age 9 plus) 35 10 0 12 — Lecture classroom 65 7 5 006 — Lecture hall (fixed seats) 150 7 5 006 — Art classrooms 20 10 0 18 07 Science laboratories 25 10 0 18 10 Wood/metal shops 20 10 0 18 0 5 Computer lab 25 10 012 — Multiuse assembly 100 7 5 006 — Locker/dressing rooms 0 25 Food and beverage service Bars, cocktail lounges 100 7 5 0 18 — Cafeteria, fast food 100 7 5 0 18 Dining rooms 70 75 018 — Kitchens (cooking)' 07 Hospitals, nursing and convalescent homes Autopsy rooms' — — — 0 5 Medical procedure rooms 20 15 — Operating rooms 20 30 — Patient rooms 10 25 Physical therapy 20 15 Recovery and ICU 20 15 (continued) 2012 INTERNATIONAL MECHANICAL CODE® 33 I " ' C,gbtOO?.otI ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6N—bsx,00vco,es oc SIP so.2.o,so,4v PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,od„ceo—oAYUP, ( ,ep,od,Yo¢ebymytl,dputy,o,ANb,No,au o,sd Smglo only, mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION TABLE 403.3-continued MINIMUM VENTILATION RATES PEOPLE OUTDOOR AREA OUTDOOR EXHAUST AIRFLOW OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #11000 FT AIRFLOW RATE IN BREATHING ZONE, AIRFLOW RATE IN BREATHING ZONE, RATE Rp CFM/PERSON R, CFM/FT2a CFME�a Hotels, motels, resorts and dormitories Multipurpose assembly 120 5 0.06 - Bathrooms/toiletprivates 25/50` 10 Bedroom/living room 5 0.06 - Conference/meeting 5 0.06 50 Dormitory sleeping areas 5 0.06 20 Gambling casinos 7.5 0.18 - 120 Lobbies/prefunction 7.5 0.06 30 Offices Conference rooms 50 5 0.06 Office spaces 5 5 0.06 Reception areas 30 5 0.06 Telephone/data entry 60 5 0.06 Main entry lobbies 10 5 0.06 Private dwellings, single and multiple Garages, common for multiple units 0.75 Garages, separate for each dwellingb 100 cfm per car Kitchensb 25/100` Based upon number of bedrooms. First 0.35 ACH but not less Living areas` bedroom, 2; each than 15 cfm/person additional bedroom, 1 Toilet rooms and bathroomsg 20/50` Public spaces Corridors - - 0.06 - Elevator car 1.0 Shower room (per shower head)g 50/20` Smoking loungesb 70 60 - - Toilet rooms publics 50/70' Places of religious worship 120 5 0.06 - Courtrooms 70 5 0.06 - Legislative chambers 50 5 0.06 Libraries 10 5 0.12 - Museums (children's) 40 7.5 0.12 Museums/galleries 40 7.5 0.06 Retail stores, sales floors and showroom floors Sales (except as below) 15 7.5 0.12 Dressing rooms - - - 0.25 Mall common areas 40 7.5 0.06 - Shipping and receiving 0.12 Smoking loungesb 70 60 Storage rooms - - 0.12 - Warehouses (see storage) (continued) 34 2012 INTERNATIONAL MECHANICAL CODE® " C,gbt@ON I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,N-b,x1oovco189 oc Sep SO, 2019o147 PM(PDT)p-Potto IL eAg-mt,oUICC No FYUP ep,odw.no-oAYUP, ' 4 I ( riR odUto.. by POVOtput, I,ANb,to,P,,Uo„sd Single,ss¢mlym,ymgPod -Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE TRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION TABLE 403.3—continued MINIMUM VENTILATION RATES PEOPLE OUTDOOR AREA OUTDOOR EXHAUSTAIRFLOW OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #11000 FT AIRFLOW RATE IN BREATHING ZONE, AIRFLOW RATE IN BREATHING ZONE, RATE R(,CFM/PERSON Ra CFMiFTP' CFMTE Specialty shops Automotive motor -fuel dispensing stations' — — — 1 5 Barber 25 7 5 006 0 5 Beauty salons' 25 20 0 12 06 Nail salons'' 25 20 0 12 06 Embalming room' 20 Pet shops (animal areas)' 10 7 5 0 18 09 Supermarkets 8 7 5 0 06 — Sports and amusement Disco/dance floors 100 20 0 06 — Bowling alleys (seating areas) 40 10 0 12 — Game arcades 20 7 5 0 18 — Ice arenas without combustion engines — — 030 0 5 Gym, stadium, arena (play area) — — 030 — Spectator areas 150 7 5 0 06 — Swimming pools (pool and deck area) — — 048 — Health club/aerobics room 40 20 006 — Health club/weight room 10 20 006 — Storage Repair garages, enclosed parking garages" 0 75 Warehouses — — 006 — Theaters Auditoriums (see education) — — — — Lobbies 150 5 006 — Stages, studios 70 10 006 Ticket booths 60 5 0 06 — Transportation Platforms 100 7 5 0 06 Transportation waiting 100 7 5 006 — Workrooms Bank vaults/safe deposit 5 5 0 06 — Darkrooms — — — 10 Copy, printing rooms 4 5 006 0 5 Meat processing` 10 15 — — Pharmacy (prep area) 10 5 0 18 — Photo studios 10 5 0 12 — Computer (without printing) 4 5 006 — For SI 1 cubic foot per minute = 0 0004719 mg/s, 1 ton= 908 kg, 1 cubic foot per minute per square foot= 0 00508 m'/(s m'), °C= [(°F) -32111 8, 1 square foot= 0 0929 m' a Based upon net occupiable floor area b Mechanical exhaust required and the recirculation of air from such spaces is prohibited (see Section 403 2 1, Item 3) c Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous d Ventilation systems in enclosed parking garages shall comply with Section 404 e Rates are per water closet or urinal The higher rate shall be provided where the exhaust system is designed to operate intermittently The lower rate shall be permitted only where the exhaust system is designed to operate continuously while occupied f Rates are per room unless otherwise indicated The higher rate shall be provided where the exhaust system is designed to operate intermittently The lower rate shall be permitted only where the exhaust system is designed to operate continuously while occupied g Mechanical exhaust is required and recirculation is prohibited except that recirculation shall be permitted where the resulting supply airstream consists of not more than 10 percent air recirculated from these spaces (see Section 403 2 1, Items 2 and 4) h For nail salons, each nail station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station 2012 INTERNATIONAL MECHANICAL CODE® 35 I " ' C,gbtOO?.otI ICC ALL RIGHTS RESERVED Awsedby().(-)O,d6N—bsx,00vco,es oc SIP so.2.o,so,4v To (PDT) p—Pot to IL eAg—mt,oUICC No FYUP ep,od„ceo—oAYUP, ( ,ep,od,Yo¢ebymytl,dputy,o,ANb,No,au o,sd Stoglo only, mpymg Pod-Pyoc,p,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION 403.3.1.1 Breathing zone outdoor airflow. The out- door airflow rate required in the breathing zone (Vj of the occupiable space or spaces in a zone shall be deter- mined in accordance with Equation 4-1. Vbz = R,,P, +RGA, (Equation 4-1) where: Az — Zone floor area: the net occupiable floor area of the space or spaces in the zone. P — Zone population: the number of people in the space or spaces in the zone. R — People outdoor air rate: the outdoor airflow rate required per person from Table 403.3. R — Area outdoor air rate: the outdoor airflow rate required per unit area from Table 403.3. 403.3.1.2 Zone air distribution effectiveness. The zone air distribution effectiveness (E) shall be deter- mined using Table 403.3.1.2. TABLE 403.3.1.2 ZONE AIR DISTRIBUTION EFFECTIVENESS,t,odRO Air Distribution Configuration E, Ceiling or floor supply of cool air 1 or Ceiling or floor supply of warts air and floor return 1 0 Ceiling supply of warts air and ceiling return 0 8a Floor supply of warts air and ceiling return 07 Makeup air drawn in on the opposite side of the room from the exhaust and/or return 08 Makeup air drawn in near to the exhaust and/or return location 05 For SI 1 foot - 304 8 min, 1 foot per minute - 0 00506 m/s, °C- h`F) - 321118 a "Cool air" is air cooler than space temperature b "Warm air" is air warmer than space temperature c "Ceiling" includes any point above the breathing zone d "Floor" includes any point below the breathing zone e "Makeup air" is air supplied or transferred to a zone to replace air removed from the zone by exhaust or return systems f Zone air distribution effectiveness of 1 2 shall be permitted for systems with a floor supply of cool air and ceiling retum, provided that low - velocity displacement ventilation achieves unidirectional flow and thermal stratification g Zone air distribution effectiveness of 10 shall be permitted for systems with a ceiling supply of warm air, provided that supply air temperature is less than 15°F above space temperature and provided that the 150 foot - per -minute supply airier reaches to within 41/y feet of floor level 403.3.1.3 Zone outdoor airflow. The zone outdoor air- flow rate (Vj, shall be determined in accordance with Equation 4-2. Vbz Vog = E L (Equation 4-2) 403.3.2 System outdoor airflow. The outdoor air required to be supplied by each ventilation system shall be deter- mined in accordance with Sections 403.3.2.1 through 403.3.2.3 as a function of system type and zone outdoor airflow rates. 403.3.2.1 Single zone systems. Where one air handler supplies a mixture of outdoor air and recirculated return air to only one zone, the system outdoor air intake flow rate (V) shall be determined in accordance with Equa- tion 4-3. Vof — VI,,, (Equation 4-3) 403.3.2.2 100-percent outdoor air systems. Where one air handler supplies only outdoor air to one or more zones, the system outdoor air intake flow rate (V) shall be determined using Equation 4-4. Vof — Eell zones Voz (Equation 4-4) 403.3.2.3 Multiple zone recirculating systems. Where one air handler supplies a mixture of outdoor air and recirculated return air to more than one zone, the sys- tem outdoor air intake flow rate (V) shall be deter- mined in accordance with Sections 403.3.2.3.1 through 403.3.2.3.4. 403.3.2.3.1 Primary outdoor air fraction. The pri- mary outdoor air fraction V) shall be determined for each zone in accordance with Equation 4-5. Zp = VOZ (Equation 4-5) VpL where: V� = Primary airflow: The airflow rate supplied to the zone from the air -handling unit at which the outdoor air intake is located. It includes outdoor intake air and recirculated air from that air -handling unit but does not include air transferred or air recirculated to the zone by other means. For design pur- poses, V shall be the zone design primary PZ airflow rate, except for zones with variable air volume supply and V shall be the lowest expected primary airflow rate to the zone when it is fully occupied. 403.3.2.3.2 System ventilation efficiency. The sys- tem ventilation efficiency (E) shall be determined using Table 403.3.2.3.2 or Appendix A of ASHRAE 62.1. 36 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 1007601e9 oc Sep SO, 2019 o 147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP epoodw.noa oAYUP, 4 I IT �ep4olY,o.. by mythdparty.o,AeTb�to,P,,Uoosd Single—mly mpymg Pod o,yo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION TABLE 403.3.2.3.2 SYSTEM VENTILATION EFFICIENCYa,b Max (Z) E 5015 1 5025 09 <035 08 5045 07 5055 06 5065 05 5075 04 >075 03 a Mar (Z) is the largest value of Z, calculated using Equation 4-5 among all the zones served by the system b Interpolating between table values shall be permitted 403.3.2.3.3 Uncorrected outdoor air intake. The uncorrected outdoor air intake flow rate (V J shall be determined in accordance with Equation 4-6. Von = DEallzones"pPz+ Ea11z0nes"a`4z (Equation 4-6) where: D = Occupant diversity: the ratio of the system population to the sum of the zone popula- tions, determined in accordance with Equa- tion 4-7. D = PG (Equation 4-7) fall zonesPz where: P = System population: The total number of occupants in the area served by the system. For design purposes, P shall be the maxi- mum number of occupants expected to be concurrently in all zones served by the sys- tem. 403.3.2.3.4 Outdoor air intake flow rate. The out- door air intake flow rate ( V r) shall be determined in accordance with Equation 4-8. �— Von VC Ey (Equation 4-8) 403.4 Exhaust ventilation. Exhaust airflow rate shall be pro- vided in accordance with the requirements in Table 403.3. Exhaust makeup air shall be permitted to be any combination of outdoor air, recirculated air and transfer air, except as lim- ited in accordance with Section 403.2. 403.5 System operation. The minimum flow rate of outdoor air that the ventilation system must be capable of supplying during its operation shall be permitted to be based on the rate per person indicated in Table 403.3 and the actual number of occupants present. 403.6 Variable air volume system control. Variable air vol- ume air distribution systems, other than those designed to supply only 100-percent outdoor air, shall be provided with controls to regulate the flow of outdoor air. Such control sys- tem shall be designed to maintain the flow rate of outdoor air at a rate of not less than that required by Section 403.3 over the entire range of supply air operating rates. 403.7 Balancing. The ventilation air distribution system shall be provided with means to adjust the system to achieve at least the minimum ventilation airflow rate as required by Sections 403.3 and 403.4. Ventilation systems shall be bal- anced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying and exhausting the airflow rates required by Sections 403.3 and 403.4. SECTION 404 ENCLOSED PARKING GARAGES 404.1 Enclosed parking garages. Mechanical ventilation systems for enclosed parking garages shall be permitted to operate intermittently in accordance with Item 1, Item 2 or both. 1. The system shall be arranged to operate automatically upon detection of vehicle operation or the presence of occupants by approved automatic detection devices. 2. The system shall be arranged to operate automatically by means of carbon monoxide detectors applied in con- junction with nitrogen dioxide detectors. Such detec- tors shall be installed in accordance with their manufacturers' recommendations. 404.2 Minimum ventilation. Automatic operation of the sys- tem shall not reduce the ventilation airflow rate below 0.05 cfm per square foot (0.00025 m3/s • m') of the floor area and the system shall be capable of producing a ventilation airflow rate of 0.75 cfm per square foot (0.0038 m3/s •m') of floor area. 404.3 Occupied spaces accessory to public garages. Con- necting offices, waiting rooms, ticket booths and similar uses that are accessory to a public garage shall be maintained at a positive pressure and shall be provided with ventilation in accordance with Section 403.3. SECTION 405 SYSTEMS CONTROL 405.1 General. Mechanical ventilation systems shall be pro- vided with manual or automatic controls that will operate such systems whenever the spaces are occupied. Air-condi- tioning systems that supply required ventilation air shall be provided with controls designed to automatically maintain the required outdoor air supply rate during occupancy. 2012 INTERNATIONAL MECHANICAL CODE® 37 I II I CopyngbtOO?.ot I ICC ALL RIGHTS RESERVED A-P—dby().(-)Obd6 Nmmbsx 100760189 oc Sep so.2.o19o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER VENTILATION SECTION 406 VENTILATION OF UNINHABITED SPACES 406.1 General. Uninhabited spaces, such as crawl spaces and attics, shall be provided with natural ventilation openings as required by the International Building Code or shall be pro- vided with a mechanical exhaust and supply air system. The mechanical exhaust rate shall be not less than 0.02 cfm per square foot (0.00001 m3/s • m') of horizontal area and shall be automatically controlled to operate when the relative humid- ity in the space served exceeds 60 percent. 38 2012 INTERNATIONAL MECHANICAL CODE® l I C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO,2019 01 av PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, Rk S I ( ,Fod,Y..1yPoytlu,dparty.oPANb�toc UoFsd Smglo mlym,ymgand-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDRRAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER 5 EXHAUST SYSTEMS SECTION 501 GENERAL 501.1 Scope. This chapter shall govern the design, construc- tion and installation of mechanical exhaust systems, includ- ing exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke con- trol systems; energy recovery ventilation systems and other systems specified in Section 502. 501.2 Independent system required. Single or combined mechanical exhaust systems for environmental air shall be independent of all other exhaust systems. Dryer exhaust shall be independent of all other systems. Type I exhaust systems shall be independent of all other exhaust systems except as provided in Section 506.3.5. Single or combined Type II exhaust systems for food -processing operations shall be inde- pendent of all other exhaust systems. Kitchen exhaust sys- tems shall be constructed in accordance with Section 505 for domestic equipment and Sections 506 through 509 for com- mercial equipment. 501.3 Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.3.1. The air shall be dis- charged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space. Exceptions: 1. Whole -house ventilation -type attic fans shall be per- mitted to discharge into the attic space of dwelling units having private attics. 2. Commercial cooking recirculating systems. 501.3.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts discharging to the out- doors shall be located with the following minimum dis- tances: 1. For ducts conveying explosive or flammable vapors, fumes or dusts: 30 feet (9144 mm) from property lines; 10 feet (3048 mm) from operable openings into buildings; 6 feet (1829 mm) from exterior walls and roofs; 30 feet (9144 mm) from combustible walls and operable openings into buildings which are in the direction of the exhaust discharge; 10 feet (3048 mm) above adjoining grade. 2. For other product -conveying outlets: 10 feet (3048 mm) from the property lines; 3 feet (914 mm) from exterior walls and roofs; 10 feet (3048 mm) from operable openings into buildings; 10 feet (3048 mm) above adjoining grade. 3. For all environmental air exhaust: 3 feet (914 mm) from property lines; 3 feet (914 mm) from operable openings into buildings for all occupancies other than Group U, and 10 feet (3048 mm) from mechan- ical air intakes. Such exhaust shall not be considered hazardous or noxious. 4. Exhaust outlets serving structures in flood hazard areas shall be installed at or above the elevation required by Section 1612 of the International Build- ing Code for utilities and attendant equipment. 5. For specific systems see the following sections: 5.1. Clothes dryer exhaust, Section 504.4. 5.2. Kitchen hoods and other kitchen exhaust equipment, Sections 506.3.13, 506.4 and 506.5. 5.3. Dust stock and refuse conveying systems, Section 511.2. 5.4. Subslab soil exhaust systems, Section 512.4. 5.5. Smoke control systems, Section 513.10.3. 5.6. Refrigerant discharge, Section 1105.7. 5.7. Machinery room discharge, Section 1105.6.1. 501.3.1.1 Exhaust discharge. Exhaust air shall not be directed onto walkways. 501.3.2 Exhaust opening protection. Exhaust openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. Openings in screens, louvers and grilles shall be sized not less than '/q inch (6 mm) and not larger than '/z inch (13 min). Openings shall be protected against local weather conditions. Louvers that protect exhaust openings in structures located in hurri- cane -prone regions, as defined in the International Build- ing Code, shall comply with AMCA Standard 550. Outdoor openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accor- dance with the International Building Code. 501.4 Pressure equalization. Mechanical exhaust systems shall be sized to remove the quantity of air required by this chapter to be exhausted. The system shall operate when air is required to be exhausted. Where mechanical exhaust is required in a room or space in other than occupancies in R-3 and dwelling units in R-2, such space shall be maintained with a neutral or negative pressure. If a greater quantity of air is supplied by a mechanical ventilating supply system than is removed by a mechanical exhaust for a room, adequate means shall be provided for the natural or mechanical exhaust of the excess air supplied. If only a mechanical exhaust sys- tem is installed for a room or if a greater quantity of air is removed by a mechanical exhaust system than is supplied by a mechanical ventilating supply system for a room, adequate makeup airconsisting of supply air, transfer air or outdoor air shall be provided to satisfy the deficiency. The calculated 2012 INTERNATIONAL MECHANICAL CODE® 39 I II I C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS building infiltration rate shall not be used to satisfy the requirements of this section. 501.5 Ducts. Where exhaust duct construction is not speci- fied in this chapter, such construction shall comply with Chapter 6. SECTION 502 REQUIRED SYSTEMS 502.1 General. An exhaust system shall be provided, main- tained and operated as specifically required by this section and for all occupied areas where machines, vats, tanks, fur- naces, forges, salamanders and other appliances, equipment and processes in such areas produce or throw off dust or par- ticles sufficiently light to float in the air, or which emit heat, odors, fumes, spray, gas or smoke, in such quantities so as to be irritating or injurious to health or safety. 502.1.1 Exhaust location. The inlet to an exhaust system shall be located in the area of heaviest concentration of contaminants. [F] 502.1.2 Fuel -dispensing areas. The bottom of an air inlet or exhaust opening in fuel -dispensing areas shall be located not more than 18 inches (457 mm) above the floor. 502.1.3 Equipment, appliance and service rooms. Equipment, appliance and system service rooms that house sources of odors, fumes, noxious gases, smoke, steam, dust, spray or other contaminants shall be designed and constructed so as to prevent spreading of such contam- inants to other occupied parts of the building. [F] 502.1.4 Hazardous exhaust The mechanical exhaust of high concentrations of dust or hazardous vapors shall conform to the requirements of Section 510. [F] 502.2 Aircraft fueling and defueling. Compartments housing piping, pumps, air eliminators, water separators, hose reels and similar equipment used in aircraft fueling and defueling operations shall be adequately ventilated at floor level or within the floor itself. [F] 502.3 Battery -charging areas for powered industrial trucks and equipment Ventilation shall be provided in an approved manner in battery -charging areas for powered industrial trucks and equipmentto prevent a dangerous accu- mulation of flammable gases. [F] 502.4 Stationary storage battery systems. Stationary storage battery systems, as regulated by Section 608 of the International Fire Code, shall be provided with ventilation in accordance with this chapter and Section 502.4.1 or 502.4.2. Exception: Lithium -ion and lithium metal polymer batter- ies shall not require additional ventilation beyond that which would normally be required for human occupancy of the space. [F] 502.4.1 Hydrogen limit in rooms. For flooded lead acid, flooded nickel cadmium and VRLA batteries, the ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total vol- ume of the room. [F] 502.4.2 Ventilation rate in rooms. Continuous venti- lation shall be provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft') [0.00508 m3/(s . m')] of floor area of the room. 502.4.3 Supervision. Mechanical ventilation systems required by Section 502.4 shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on -site location. [F] 502.5 Valve -regulated lead -acid batteries in cabinets. Valve -regulated lead -acid (VRLA) batteries installed in cabi- nets, as regulated by Section 608.6.2 of the International Fire Code, shall be provided with ventilation in accordance with Section 502.5.1 or 502.5.2. [F] 502.5.1 Hydrogen limit in cabinets. The cabinet ven- tilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total vol- ume of the cabinet during the worst -case event of simulta- neous boost charging of all batteries in the cabinet. [F] 502.5.2 Ventilation rate in cabinets. Continuous cab- inet ventilation shall be provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft') [0.00508 m3/(s . m')] of the floor area covered by the cabinet. The room in which the cabinet is installed shall also be venti- lated as required by Section 502.4.1 or 502.4.2. 502.5.3 Supervision. Mechanical ventilation systems required by Section 502.5 shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on -site location. [F] 502.6 Dry cleaning plants. Ventilation in dry cleaning plants shall be adequate to protect employees and the public in accordance with this section and DOL 29 CFR Part 1910.1000, where applicable. [F] 502.6.1 Type II systems. Type II dry cleaning systems shall be provided with a mechanical ventilation system that is designed to exhaust 1 cubic foot of air per minute for each square foot of floor area (1 cfm/ft') [0.00508 m3/ is . m')] in dry cleaning rooms and in drying rooms. The ventilation system shall operate automatically when the dry cleaning equipmentis in operation and shall have man- ual controls at an approved location. [F] 502.6.2 Type IV and V systems. Type IV and V dry cleaning systems shall be provided with an automatically activated exhaust ventilation system to maintain a mini- mum of 100 feet per minute (0.51 m/s) air velocity through the loading door when the door is opened. Exception: Dry cleaning units are not required to be provided with exhaust ventilation where an exhaust hood is installed immediately outside of and above the 40 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( [,FodUto,,by POVOtpN PLOI,±bs �to,P,,UoFd Single—oPIA PTymg PodoNyodpl mgokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE PEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS loading door which operates at an airflow rate as fol- lows: Q = 100 x ALD (Equation 5-1) where: Q —Flow rate exhausted through the hood, cubic feet per minute. A,,=Area of the loading door, square feet. [F] 502.6.3 Spotting and pretreating. Scrubbing tubs, scouring, brushing or spotting operations shall be located such that solvent vapors are captured and exhausted by the ventilating system. [F] 502.7 Application of flammable finishes. Mechanical exhaust as required by this section shall be provided for oper- ations involving the application of flammable finishes. [F] 502.7.1 During construction. Ventilation shall be provided for operations involving the application of mate- rials containing flammable solvents in the course of con- struction, alteration or demolition of a structure. [F] 502.7.2 Limited spraying spaces. Positive mechani- cal ventilation which provides a minimum of six complete air changes per hour shall be installed in limited spraying spaces. Such system shall meet the requirements of the International Fire Code for handling flammable vapors. Explosion venting is not required. [F] 502.7.3 Flammable vapor areas. Mechanical ventila- tion of flammable vapor areas shall be provided in accor- dance with Sections 502.7.3.1 through 502.7.3.6. [F] 502.7.3.1 Operation. Mechanical ventilation shall be kept in operation at all times while spraying opera- tions are being conducted and for a sufficient time thereafter to allow vapors from drying coated articles and finishing material residue to be exhausted. Spray- ing equipment shall be interlocked with the ventilation of the flammable vapor area such that spraying opera- tions cannot be conducted unless the ventilation system is in operation. [F] 502.7.3.2 Recirculation. Air exhausted from spray- ing operations shall not be recirculated. Exceptions: 1. Air exhausted from spraying operations shall be permitted to be recirculated as makeup air for unmanned spray operations provided that: 1.1. The solid particulate has been removed. 1.2. The vapor concentration is less than 25 percent of the lower flammable limit (-FL). 1.3. Approved equipment is used to moni- tor the vapor concentration. 1.4. An alarm is sounded and spray oper- ations are automatically shut down if the vapor concentration exceeds 25 percent of the LFL. 1.5. In the event of shutdown of the vapor concentration monitor, 100 percent of the air volume specified in Section 510 is automatically exhausted. 2. Air exhausted from spraying operations is allowed to be recirculated as makeup air to manned spraying operations where all of the conditions provided in Exception 1 are included in the installation and documents have been prepared to show that the installa- tion does not pose a life safety hazard to per- sonnel inside the spray booth, spraying space or spray room. [F] 502.7.3.3 Air velocity. Ventilation systems shall be designed, installed and maintained such that the aver- age air velocity over the open face of the booth, or booth cross section in the direction of airflow during spraying operations, is not less than 100 feet per minute (0.51 m/s). [F] 502.7.3.4 Ventilation obstruction. Articles being sprayed shall be positioned in a manner that does not obstruct collection of overspray. [F] 502.7.3.5 Independent ducts. Each spray booth and spray room shall have an independent exhaust duct system discharging to the outdoors. Exceptions 1. Multiple spray booths having a combined frontal area of 18 square feet (1.67 m') or less are allowed to have a common exhaust where identical spray -finishing material is used in each booth. If more than one fan serves one booth, such fans shall be interconnected so that all fans operate simultaneously. 2. Where treatment of exhaust is necessary for air pollution control or energy conservation, ducts shall be allowed to be manifolded if all of the following conditions are met: 2.1. The sprayed materials used are com- patible and will not react or cause ignition of the residue in the ducts. 2.2. Nitrocellulose -based finishing mate- rial shall not be used. 2.3. A filtering system shall be provided to reduce the amount of overspray carried into the duct manifold. 2.4. Automatic sprinkler protection shall be provided at the junction of each booth exhaust with the manifold, in addition to the protection required by this chapter. [F] 502.7.3.6 Fan motors and belts. Electric motors driving exhaust fans shall not be placed inside booths or ducts. Fan rotating elements shall be nonferrous or nonsparking or the casing shall consist of, or be lined 2012 INTERNATIONAL MECHANICAL CODE® 41 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o19o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS with, such material. Belts shall not enter the duct or booth unless the belt and pulley within the duct are tightly enclosed. [F] 502.7.4 Dipping operations. Flammable vapor areas of dip tank operations shall be provided with mechanical ventilation adequate to prevent the dangerous accumula- tion of vapors. Required ventilation systems shall be so arranged that the failure of any ventilating fan will auto- matically stop the dipping conveyor system. [F] 502.7.5 Electrostatic apparatus. The flammable vapor area in spray -finishing operations involving electro- static apparatus and devices shall be ventilated in accor- dance with Section 502.7.3. [F] 502.7.6 Powder coating. Exhaust ventilation for pow- der -coating operations shall be sufficient to maintain the atmosphere below one-half of the minimum explosive concentration for the material being applied. Nondepos- tted, air -suspended powders shall be removed through exhaust ducts to the powder recovery system. [F] 502.7.7 Floor resurfacing operations. To prevent the accumulation of flammable vapors during floor resurfac- ing operations, mechanical ventilation at a minimum rate of 1 cfm/ft' [0.00508 m3/(s . m')] of area being finished shall be provided. Such exhaust shall be by approved tem- porary or portable means. Vapors shall be exhausted to the exterior of the building. [F] 502.8 Hazardous materials —general requirements. Exhaust ventilation systems for structures containing hazard- ous materials shall be provided as required in Sections 502.8.1 through 502.8.5. [F] 502.8.1 Storage in excess of the maximum allowable quantities. Indoor storage areas and storage buildings for hazardous materials in amounts exceeding the maximum allowable quantity per control area shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored. Exceptions: 1. Storage areas for flammable solids complying with Section 5904 of the International Fire Code. 2. Storage areas and storage buildings for fireworks and explosives complying with Chapter 56 of the International Fire Code. [F] 502.8.1.1 System requirements. Exhaust ventila- tion systems shall comply with all of the following: 1. The installation shall be in accordance with this code. 2. Mechanical ventilation shall be provided at a rate of not less than 1 cfm per square foot [0.00508 m3/(s . m')] of floor area over the storage area. 3. The systems shall operate continuously unless alternate designs are approved. 4. A manual shutoff control shall be provided out- side of the room in a position adjacent to the access door to the room or in another approved location. The switch shall be a break -glass or other approved type and shall be labeled: VEN- TILATION SYSTEM EMERGENCY SHUT- OFF. 5. The exhaust ventilation shall be designed to con- sider the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (305 mm) of the floor. For fumes or vapors that are lighter than air, exhaust shall be taken from a point within 12 inches (305 mm) of the highest point of the room. 6. The location of both the exhaust and inlet air openings shall be designed to provide air move- ment across all portions of the floor or room to prevent the accumulation of vapors. 7. The exhaust air shall not be recirculated to occu- pied areas if the materials stored are capable of emitting hazardous vapors and contaminants have not been removed. Air contaminated with explosive or flammable vapors, fumes or dusts; flammable, highly toxic or toxic gases; or radio- active materials shall not be recirculated. [F] 502.8.2 Gas rooms, exhausted enclosures and gas cabinets. The ventilation system for gas rooms, exhausted enclosures and gas cabinets for any quantity of hazardous material shall be designed to operate at a negative pressure in relation to the surrounding area. Highly toxic and toxic gases shall also comply with Sections 502.9.7.1, 502.9.7.2 and 502.9.8.4. [F] 502.8.3 Indoor dispensing and use. Indoor dispens- ing and use areas for hazardous materials in amounts exceeding the maximum allowable quantity per control area shall be provided with exhaust ventilation in accor- dance with Section 502.8.1. Exception: Ventilation is not required for dispensing and use of flammable solids other than finely divided particles. [F] 502.8.4 Indoor dispensing and use —point sources. Where gases, liquids or solids in amounts exceeding the maximum allowable quantity per control area and having a hazard ranking of 3 or 4 in accordance with NFPA 704 are dispensed or used, mechanical exhaust ventilation shall be provided to capture gases, fumes, mists or vapors at the point of generation. Exception: Where it can be demonstrated that the gases, liquids or solids do not create harmful gases, fumes, mists or vapors. [F] 502.8.5 Closed systems. Where closed systems for the use of hazardous materials in amounts exceeding the max- imum allowable quantity per control area are designed to be opened as part of normal operations, ventilation shall be provided in accordance with Section 502.8.4. [F] 502.9 Hazardous materials —requirements for specific materials. Exhaust ventilation systems for specific hazardous materials shall be provided as required in Section 502.8 and Sections 502.9.1 through 502.9.11. 42 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I IT [,Fod Uto,,by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS [F] 502.9.1 Compressed gases —medical gas systems. Rooms for the storage of compressed medical gases in amounts exceeding the permit amounts for compressed gases in the International Fire Code, and that do not have an exterior wall, shall be exhausted through a duct to the exterior of the building. Both separate airstreams shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior. Approved mechanical ventilation shall be provided at a minimum rate of 1 cfm/ft' [0.00508 m3/(s . m')] of the area of the room. Gas cabinets for the storage of compressed medical gases in amounts exceeding the permit amounts for com- pressed gases in the International Fire Code shall be con- nected to an exhaust system. The average velocity of ventilation at the face of access ports or windows shall be not less than 200 feet per minute (1.02 m/s) with a mini- mum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window. [F] 502.9.2 Corrosives. Where corrosive materials in amounts exceeding the maximum allowable quantity per control area are dispensed or used, mechanical exhaust ventilation in accordance with Section 502.8.4 shall be provided. [F] 502.9.3 Cryogenics. Storage areas for stationary or portable containers of cryogenic fluids in any quantity shall be ventilated in accordance with Section 502.8. Indoor areas where cryogenic fluids in any quantity are dispensed shall be ventilated in accordance with the requirements of Section 502.8.4 in a manner that captures any vapor at the point of generation. Exception: Ventilation for indoor dispensing areas is not required where it can be demonstrated that the cryo- genic fluids do not create harmful vapors. [F] 502.9.4 Explosives. Squirrel cage blowers shall not be used for exhausting hazardous fumes, vapors or gases in operating buildings and rooms for the manufacture, assembly or testing of explosives. Only nonferrous fan blades shall be used for fans located within the ductwork and through which hazardous materials are exhausted. Motors shall be located outside the duct. [F] 502.9.5 Flammable and combustible liquids. Exhaust ventilation systems shall be provided as required by Sections 502.9.5.1 through 502.9.5.5 for the storage, use, dispensing, mixing and handling of flammable and combustible liquids. Unless otherwise specified, this sec- tion shall apply to any quantity of flammable and combus- tible liquids. Exception: This section shall not apply to flammable and combustible liquids that are exempt from the Inter- national Fire Code. [F] 502.9.5.1 Vaults. Vaults that contain tanks of Class I liquids shall be provided with continuous ventilation at a rate of not less than 1 cfm/ft2 of floor area [0.00508 m3/(s . m')], but not less than 150 cfm (4 m'/min). Fail- ure of the exhaust airflow shall automatically shut down the dispensing system. The exhaust system shall be designed to provide air movement across all parts of the vault floor. Supply and exhaust ducts shall extend to a point not greater than 12 inches (305 mm) and not less than 3 inches (76 mm) above the floor. The exhaust system shall be installed in accordance with the provi- sions of NBPA 91. Means shall be provided to automat- ically detect any flammable vapors and to automatically shut down the dispensing system upon detection of such flammable vapors in the exhaust duct at a concentration of 25 percent of the LFL. [F] 502.9.5.2 Storage rooms and warehouses. Liquid storage rooms and liquid storage warehouses for quan- tities of liquids exceeding those specified in the Inter- national Fire Code shall be ventilated in accordance with Section 502.8.1. [F] 502.9.5.3 Cleaning machines. Areas containing machines used for parts cleaning in accordance with the International Fire Code shall be adequately ventilated to prevent accumulation of vapors. [F] 502.9.5.4 Use, dispensing and mixing. Continuous mechanical ventilation shall be provided for the use, dispensing and mixing of flammable and combustible liquids in open or closed systems in amounts exceeding the maximum allowable quantity per control area and for bulk transfer and process transfer operations. The ventilation rate shall be not less than 1 cfm/ft' [0.00508 m3/(s . m')] of floor area over the design area. Provi- sions shall be made for the introduction of makeup air in a manner that will include all floor areas or pits where vapors can collect. Local or spot ventilation shall be provided where needed to prevent the accumulation of hazardous vapors. Exception: Where natural ventilation can be shown to be effective for the materials used, dispensed or mixed. [F] 502.9.5.5 Bulk plants or terminals. Ventilation shall be provided for portions of properties where flam- mable and combustible liquids are received by tank vessels, pipelines, tank cars or tank vehicles and which are stored or blended in bulk for the purpose of distrib- uting such liquids by tank vessels, pipelines, tank cars, tank vehicles or containers as required by Sections 502.9.5.5.1 through 502.9.5.5.3. [F] 502.9.5.5.1 General. Ventilation shall be pro- vided for rooms, buildings and enclosures in which Class I liquids are pumped, used or transferred. Design of ventilation systems shall consider the rel- atively high specific gravity of the vapors. Where natural ventilation is used, adequate openings in outside walls at floor level, unobstructed except by louvers or coarse screens, shall be provided. Where natural ventilation is inadequate, mechanical venti- lation shall be provided. [F] 502.9.5.5.2 Basements and pits. Class I liquids shall not be stored or used within a building having a basement or pit into which flammable vapors can travel, unless such area is provided with ventilation designed to prevent the accumulation of flammable vapors therein. 2012 INTERNATIONAL MECHANICAL CODE® 43 I II I Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg Podortuodmgp4okbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS [F] 502.9.5.5.3 Dispensing of Class I liquids. Con- tainers of Class I liquids shall not be drawn from or filled within buildings unless a provision is made to prevent the accumulation of flammable vapors in hazardous concentrations. Where mechanical venti- lation is required, it shall be kept in operation while flammable vapors could be present. [F] 502.9.6 Highly toxic and toxic liquids. Ventilation exhaust shall be provided for highly toxic and toxic liquids as required by Sections 502.9.6.1 and 502.9.6.2. [F] 502.9.6.1 Treatment system. This provision shall apply to indoor and outdoor storage and use of highly toxic and toxic liquids in amounts exceeding the maxi- mum allowable quantities per control area. Exhaust scrubbers or other systems for processing vapors of highly toxic liquids shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure. [F] 502.9.6.2 Open and closed systems. Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in open systems in accordance with Section 502.8.4. Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in closed systems in accordance with Section 502.8.5. Exception: Liquids or solids that do not generate highly toxic or toxic fumes, mists or vapors. [F] 502.9.7 Highly toxic and toxic compressed gases any quantity. Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections 502.9.7.1 and 502.9.7.2. [F] 502.9.7.1 Gas cabinets. Gas cabinets containing highly toxic or toxic compressed gases in any quantity shall comply with Section 502.8.2 and the following requirements: 1. The average ventilation velocity at the face of gas cabinet access ports or windows shall be not less than 200 feet per minute (1.02 m/s) with a mini- mum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window. 2. Gas cabinets shall be connected to an exhaust system. 3. Gas cabinets shall not be used as the sole means of exhaust for any room or area. [F] 502.9.7.2 Exhausted enclosures. Exhausted enclo- sures containing highly toxic or toxic compressed gases in any quantity shall comply with Section 502.8.2 and the following requirements: 1. The average ventilation velocity at the face of the enclosure shall be not less than 200 feet per min- ute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s). 2. Exhausted enclosures shall be connected to an exhaust system. 3. Exhausted enclosures shall not be used as the sole means of exhaust for any room or area. [F] 502.9.8 Highly toxic and toxic compressed gases quantities exceeding the maximum allowable quantity per control area. Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in amounts exceeding the maximum allowable quantities per control area as required by Sections 502.9.8.1 through 502.9.8.6. [F] 502.9.8.1 Ventilated areas. The room or area in which indoor gas cabinets or exhausted enclosures are located shall be provided with exhaust ventilation. Gas cabinets or exhausted enclosures shall not be used as the sole means of exhaust for any room or area. [F] 502.9.8.2 Local exhaust for portable tanks. A means of local exhaust shall be provided to capture leakage from indoor and outdoor portable tanks. The local exhaust shall consist of portable ducts or collec- tion systems designed to be applied to the site of a leak in a valve or fitting on the tank. The local exhaust sys- tem shall be located in a gas room. Exhaust shall be directed to a treatment system where required by the International Fire Code. [F] 502.9.8.3 Piping and controls —stationary tanks. Filling or dispensing connections on indoor stationary tanks shall be provided with a means of local exhaust. Such exhaust shall be designed to capture fumes and vapors. The exhaust shall be directed to a treatment system where required by the International Fire Code. [F] 502.9.8.4 Gas rooms. The ventilation system for gas rooms shall be designed to operate at a negative pressure in relation to the surrounding area. The exhaust ventilation from gas rooms shall be directed to an exhaust system. [F] 502.9.8.5 Treatment system. The exhaust ventila- tion from gas cabinets, exhausted enclosures and gas rooms, and local exhaust systems required in Sections 502.9.8.2 and 502.9.8.3 shall be directed to a treatment system where required by the International Fire Code. [F] 502.9.8.6 Process equipment. Effluent from indoor and outdoor process equipment containing highly toxic or toxic compressed gases which could be discharged to the atmosphere shall be processed through an exhaust scrubber or other processing sys- tem. Such systems shall be in accordance with the International Fire Code. [F] 502.9.9 Ozone gas generators. Ozone cabinets and ozone gas -generator rooms for systems having a maxi- mum ozone -generating capacity of '/z pound (0.23 kg) or more over a 24-hour period shall be mechanically venti- lated at a rate of not less than six air changes per hour. For cabinets, the average velocity of ventilation at makeup air openings with cabinet doors closed shall be not less than 200 feet per minute (1.02 m/s). [F] 502.9.10 LP -gas distribution facilities. LP -gas distri- bution facilities shall be ventilated in accordance with NFPA 58. [F] 502.9.10.1 Portable container use. Above -grade underfloor spaces or basements in which portable LP - gas containers are used or are stored awaiting use or 44 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I IT �ep4od,,to—by POVO d party. o,±RYb�toc P,,Uoosd Smglo mlym,ymg ando Nyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS resale shall be provided with an approved means of ventilation. Exception: Department of Transportation (DOT) specification cylinders with a maximum water capacity of 2.5 pounds (1 kg) for use in completely self-contained hand torches and similar applications. The quantity of LP -gas shall not exceed 20 pounds (9 kg) [F] 502.9.11 Silane gas. Exhausted enclosures and gas cabinets for the indoor storage of silane gas in amounts exceeding the maximum allowable quantities per control area shall comply with Chapter 64 of the International Fire Code. [F] 502.10 Hazardous production materials (HPM). Exhaust ventilation systems and materials for ducts utilized for the exhaust of HPM shall comply with this section, other applicable provisions of this code, the International Building Code and the International Fire Code. [F] 502.10.1 Where required. Exhaust ventilation sys- tems shall be provided in the following locations in accor- dance with the requirements of this section and the International Building Code. 1. Fabrication areas: Exhaust ventilation for fabrication areas shall comply with the International Building Code. Additional manual control switches shall be provided where required by the code official. 2. Workstations: A ventilation system shall be pro- vided to capture and exhaust gases, fumes and vapors at workstations. 3. Liquid storage rooms: Exhaust ventilation for liquid storage rooms shall comply with Section 502.8.1.1 and the International Building Code. 4. HPM rooms: Exhaust ventilation for HPM rooms shall comply with Section 502.8.1.1 and the Interna- tional Building Code. 5. Gas cabinets: Exhaust ventilation for gas cabinets shall comply with Section 502.8.2. The gas cabinet ventilation system is allowed to connect to a work- station ventilation system. Exhaust ventilation for gas cabinets containing highly toxic or toxic gases shall also comply with Sections 502.9.7 and 502.9.8. 6. Exhausted enclosures: Exhaust ventilation for exhausted enclosures shall comply with Section 502.8.2. Exhaust ventilation for exhausted enclo- sures containing highly toxic or toxic gases shall also comply with Sections 502.9.7 and 502.9.8. 7. Gas rooms: Exhaust ventilation for gas rooms shall comply with Section 502.8.2. Exhaust ventilation for gas rooms containing highly toxic or toxic gases shall also comply with Sections 502.9.7 and 502.9.8. 8. Cabinets containing pyrophoric liquids or Class 3 water -reactive liquids: Exhaust ventilation for cabi- nets in fabrication areas containing pyrophoric liq- uids shall be as required in Section 2705.2.3.4 of the International Fire Code. [F] 502.10.2 Penetrations. Exhaust ducts penetrating fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies con- structed in accordance with Section 711 of the Interna- tional Building Code shall be contained in a shaft of equivalent fire -resistance -rated construction. Exhaust ducts shall not penetrate fire walls. Fire dampers shall not be installed in exhaust ducts. [F] 502.10.3 Treatment systems. Treatment systems for highly toxic and toxic gases shall comply with the Interna- tional Fire Code. 502.11 Motion picture projectors. Motion picture projec- tors shall be exhausted in accordance with Section 502.11.1 or 502.11.2. 502.11.1 Projectors with an exhaust discharge. Projec- tors equipped with an exhaust discharge shall be directly connected to a mechanical exhaust system. The exhaust system shall operate at an exhaust rate as indicated by the manufacturer's installation instructions. 502.11.2 Projectors without exhaust connection. Projec- tors without an exhaust connection shall have contami- nants exhausted through a mechanical exhaust system. The exhaust rate for electric arc projectors shall be a mini- mum of 200 cubic feet per minute (cfm) (0.09 m3/s) per lamp. The exhaust rate for xenon projectors shall be a min- imum of 300 cfm (0.14 m3/s) per lamp. Xenon projector exhaust shall be at a rate such that the exterior temperature of the lamp housing does not exceed MOAT (54°C). The lamp and projection room exhaust systems, whether com- bined or independent, shall not be interconnected with any other exhaust or return system within the building. [F] 502.12 Organic coating processes. Enclosed structures involving organic coating processes in which Class I liquids are processed or handled shall be ventilated at a rate of not less than 1 cfm/ft' [0.00508 m3/(s . m')] of solid floor area. Ventilation shall be accomplished by exhaust fans that intake at floor levels and discharge to a safe location outside the structure. Noncontaminated intake air shall be introduced in such a manner that all portions of solid floor areas are pro- vided with continuous uniformly distributed air movement. 502.13 Public garages. Mechanical exhaust systems for pub- lic garages, as required in Chapter 4, shall operate continu- ously or in accordance with Section 404. 502.14 Motor vehicle operation. In areas where motor vehi- cles operate, mechanical ventilation shall be provided in accordance with Section 403. Additionally, areas in which stationary motor vehicles are operated shall be provided with a source capture system that connects directly to the motor vehicle exhaust systems. Exceptions: 1. This section shall not apply where the motor vehi- cles being operated or repaired are electrically pow- ered. 2. This section shall not apply to one- and two-family dwellings. 2012 INTERNATIONAL MECHANICAL CODE® 45 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o14v PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS 3. This section shall not apply to motor vehicle service areas where engines are operated inside the building only for the duration necessary to move the motor vehicles in and out of the building. [F] 502.15 Repair garages. Where Class I liquids or LP -gas are stored or used within a building having a basement or pit wherein flammable vapors could accumulate, the basement or pit shall be provided with ventilation designed to prevent the accumulation of flammable vapors therein. [F] 502.16 Repair garages for natural gas- and hydrogen - fueled vehicles. Repair garages used for the repair of natural gas- or hydrogen -fueled vehicles shall be provided with an approved mechanical ventilation system. The mechanical ventilation system shall be in accordance with Sections 502.16.1 and 502.16.2. Exception: Where approved by the code official, natural ventilation shall be permitted in lieu of mechanical venti- lation. [F] 502.16.1 Design. Indoor locations shall be ventilated utilizing air supply inlets and exhaust outlets arranged to provide uniform air movement to the extent practical. Inlets shall be uniformly arranged on exterior walls near floor level. Outlets shall be located at the high point of the room in exterior walls or the roof. Ventilation shall be by a continuous mechanical venti- lation system or by a mechanical ventilation system acti- vated by a continuously monitoring natural gas detection system, or for hydrogen, a continuously monitoring flam- mable gas detection system, each activating at a gas con- centration of 25 percent of the lower flammable limit (-FL). In all cases, the system shall shut down the fueling system in the event of failure of the ventilation system. The ventilation rate shall be at least 1 cubic foot per minute per 12 cubic feet [0.00138 m3/(s • m3)] of room vol- ume. [F] 502.16.2 Operation. The mechanical ventilation sys- tem shall operate continuously. Exceptions: 1. Mechanical ventilation systems that are inter- locked with a gas detection system designed in accordance with the International Fire Code. 2. Mechanical ventilation systems in garages that are used only for the repair of vehicles fueled by liquid fuels or odorized gases, such as CNG, where the ventilation system is electrically inter- locked with the lighting circuit. 502.17 Tire rebuilding or recapping. Each room where rub- ber cement is used or mixed, or where flammable or combus- tible solvents are applied, shall be ventilated in accordance with the applicable provisions of NFPA 91. 502.17.1 Buffing machines. Each buffing machine shall be connected to a dust -collecting system that prevents the accumulation of the dust produced by the buffing process. 502.18 Specific rooms. Specific rooms, including bath- rooms, locker rooms, smoking lounges and toilet rooms, shall be exhausted in accordance with the ventilation requirements of Chapter 4. 502.19 Indoor firing ranges. Ventilation shall be provided in an approved manner in areas utilized as indoor firing ranges. Ventilation shall be designed to protect employees and the public in accordance with DOL 29 CFR 1910.1025 where applicable. SECTION 503 MOTORS AND FANS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flamma- ble vapors or dusts shall be of a type approved for such envi- ronments. A manually operated remote control installed at an approved location shall be provided to shut off fans or blow- ers in flammable vapor or dust systems. Electrical equipment and appliances used in operations that generate explosive or flammable vapors, fumes or dusts shall be interlocked with the ventilation system so that the equipment and appliances cannot be operated unless the ventilation fans are in opera- tion. Motors for fans used to convey flammable vapors or dusts shall be located outside the duct or shall be protected with approved shields and dustproofing. Motors and fans shall be provided with a means of access for servicing and maintenance. 503.2 Fans. Parts of fans in contact with explosive or flam- mable vapors, fumes or dusts shall be of nonferrous or non - sparking materials, or their casing shall be lined or constructed of such material. When the size and hardness of materials passing through a fan are capable of producing a spark, both the fan and the casing shall be of nonsparking materials. When fans are required to be spark resistant, their bearings shall not be within the airstream, and all parts of the fan shall be grounded. Fans in systems -handling materials that are capable of clogging the blades, and fans in buffing or woodworking exhaust systems, shall be of the radial -blade or tube -axial type. 503.3 Equipment and appliance identification plate. Equipment and appliances used to exhaust explosive or flam- mable vapors, fumes or dusts shall bear an identification plate stating the ventilation rate for which the system was designed. 503.4 Corrosion -resistant fans. Fans located in systems conveying corrosives shall be of materials that are resistant to the corrosive or shall be coated with corrosion -resistant mate- rials. SECTION 504 CLOTHES DRYER EXHAUST 504.1 Installation. Clothes dryers shall be exhausted in accordance with the manufacturer's instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building. Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers. 46 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( �ep4od,,to—by POVOt put, I, ANb�to, P,,UoFsd Smglo mlym,ymgandoNyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS 504.2 Exhaust penetrations. Where a clothes dryer exhaust duct penetrates a wall or ceiling membrane, the annular space shall be sealed with noncombustible material, approved fire caulking or a noncombustible dryer exhaust duct wall recep tacle. Ducts that exhaust clothes dryers shall not penetrate or be located within any fireblocking, draftstopping or any wall, floor/ceiling or other assembly required by the International Building Code to be fire -resistance rated, unless such duct is constructed of galvanized steel or aluminum of the thickness specified in Section 603.4 and the fire -resistance rating is maintained in accordance with the International Building Code. Fire dampers, combination fire/smoke dampers and any similar devices that will obstruct the exhaust flow shall be prohibited in clothes dryer exhaust ducts. 504.3 Cleanout Each vertical riser shall be provided with a means for cleanout. 504.4 Exhaust installation. Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the exhaust flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums. 504.5 Makeup air. Installations exhausting more than 200 cfm (0.09m3/s) shall be provided with makeup air. Where a closet is designed for the installation of a clothes dryer, an opening having an area of not less than 100 square inches (0.0645 m') shall be provided in the closet enclosure or makeup air shall be provided by other approved means. 504.6 Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers shall conform to the requirements of Sections 504.6.1 through 504.6.7. 504.6.1 Material and size. Exhaust ducts shall have a smooth interior finish and shall be constructed of metal a minimum 0.016 inch (0.4 mm) thick. The exhaust duct size shall be 4 inches (102 min) nominal in diameter. 504.6.2 Duct installation. Exhaust ducts shall be sup- ported at 4-foot (1219 min) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude into the inside of the duct. 504.6.3 Transition ducts. Transition ducts used to con- nect the dryer to the exhaust duct system shall be a single length that is listed and labeled in accordance with UL 2158A. Transition ducts shall be a maximum of 8 feet (2438 min) in length and shall not be concealed within construction. 504.6.4 Duct length. The maximum allowable exhaust duct length shall be determined by one of the methods specified in Section 504.6.4.1 or 504.6.4.2. 504.6.4.1 Specified length. The maximum length of the exhaust duct shall be 35 feet (10 668 mm) from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accor- dance with Table 504.6.4.1. TABLE 504.6.4.1 DRYER EXHAUST DUCT FITTING EQUIVALENT LENGTH DRYER EXHAUST DUCT FITTING TYPE EQUIVALENT LENGTH 4" radius mitered 45-degree elbow 2 feet 6 inches 4" radius mitered 90-degree elbow 5 feet 6" radius smooth 45-degree elbow 1 foot 6" radius smooth 90-degree elbow 1 foot 9 inches 8" radius smooth 45-degree elbow 1 foot 8" radius smooth 90-degree elbow 1 foot 7 inches IEEEsmooth 45-degree elbow 9 inches 10" radius smooth 90-degree elbow 1 foot 6 inches For SI 1 inch - 25 4 min, 1 foot - 304 8 min, 1 degree - 0 0175 rad 504.6.4.2 Manufacturer's instructions. The maxi- mum length of the exhaust duct shall be determined by the dryer manufacturer's installation instructions. The code official shall be provided with a copy of the instal- lation instructions for the make and model of the dryer. Where the exhaust duct is to be concealed, the installa- tion instructions shall be provided to the code official prior to the concealment inspection. In the absence of fitting equivalent length calculations from the clothes dryer manufacturer, Table 504.6.4.1 shall be used. 504.6.5 Length identification. Where the exhaust duct is concealed within the building construction, the equivalent length of the exhaust duct shall be identified on a perma- nent label or tag. The label or tag shall be located within 6 feet (1829 mm) of the exhaust duct connection. 504.6.6 Exhaust duct required. Where space for a clothes dryer is provided, an exhaust duct system shall be installed. Where the clothes dryer is not installed at the time of occupancy, the exhaust duct shall be capped at the location of the future dryer. Exception: Where a listed condensing clothes dryer is installed prior to occupancy of structure. 504.6.7 Protection required. Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all framing members where there is less than P/, inches (32 min) between the duct and the finished face of the framing member. Protective shield plates shall be constructed of steel, have a thickness of 0.062 inch (1.6 mm) and extend a minimum of 2 inches (51 mm) above sole plates and below top plates. 504.7 Commercial clothes dryers. The installation of dryer exhaust ducts serving commercial clothes dryers shall com- ply with the appliance manufacturer's installation instruc- tions. Exhaust fan motors installed in exhaust systems shall be located outside of the airstream. In multiple installations, the fan shall operate continuously or be interlocked to operate when any individual unit is operating. Ducts shall have a min- imum clearance of 6 inches (152 mm) to combustible materi- als. Clothes dryer transition ducts used to connect the 2012 INTERNATIONAL MECHANICAL CODE® 47 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc Sep so.2.o19o147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet (2438 mm) in length and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction. 504.8 Common exhaust systems for clothes dryers located in multistory structures. Where a common multistory duct system is designed and installed to convey exhaust from mul- tiple clothes dryers, the construction of the system shall be in accordance with all of the following: 1. The shaft in which the duct is installed shall be con- structed and fire -resistance rated as required by the International Building Code. 2. Dampers shall be prohibited in the exhaust duct. Pen- etrations of the shaft and ductwork shall be protected in accordance with Section 607.5.5, Exception 2. 3. Rigid metal ductwork shall be installed within the shaft to convey the exhaust. The ductwork shall be constructed of sheet steel having a minimum thick- ness of 0.0187 inch (0.4712 mm) (No. 26 gage) and in accordance with SMACNA Duct Construction Stan- dards. 4. The ductwork within the shaft shall be designed and installed without offsets. 5. The exhaust fan motor design shall be in accordance with Section 503.2. 6. The exhaust fan motor shall be located outside of the airstream. 7. The exhaust fan shall run continuously, and shall be connected to a standby power source. 8. Exhaust fan operation shall be monitored in an approved location and shall initiate an audible or visual signal when the fan is not in operation. 9. Makeup air shall be provided for the exhaust system. 10. A cleanout opening shall be located at the base of the shaft to provide access to the duct to allow for clean- ing and inspection. The finished opening shall be not less than 12 inches by 12 inches (305 mm by 305 mm). 11. Screens shall not be installed at the termination. 12. The common multistory duct system shall serve only clothes dryers and shall be independent of other exhaust systems. SECTION 505 DOMESTIC KITCHEN EXHAUST EQUIPMENT 505.1 Domestic systems. Where domestic range hoods and domestic appliances equipped with downdraft exhaust are located within dwelling units, such hoods and appliances shall discharge to the outdoors through sheet metal ducts con- structed of galvanized steel, stainless steel, aluminum or cop- per. Such ducts shall have smooth inner walls, shall be air tight, shall be equipped with a backdraft damper, and shall be I independent of all other exhaust systems. Exceptions: 1. Where installed in accordance with the manufac- turer's installation instructions and where mechani- cal or natural ventilation is otherwise provided in accordance with Chapter 4, listed and labeled duct- less range hoods shall not be required to discharge to the outdoors. 2. Ducts for domestic kitchen cooking appliances equipped with downdraft exhaust systems shall be permitted to be constructed of Schedule 40 PVC pipe and fittings provided that the installation com- plies with all of the following: 2.1. The duct shall be installed under a concrete slab poured on grade. 2.2. The underfloor trench in which the duct is installed shall be completely backfilled with sand or gravel. 2.3. The PVC duct shall extend not more than 1 inch (25 mm) above the indoor concrete floor surface. 2.4. The PVC duct shall extend not more than 1 inch (25 mm) above grade outside of the building. 2.5. The PVC ducts shall be solvent cemented. 505.2 Makeup air required. Exhaust hood systems capable of exhausting in excess of 400 cfm (0.19 m3/s) shall be pro- vided with makeup air at a rate approximately equal to the exhaust air rate. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system. SECTION 506 COMMERCIAL KITCHEN HOOD VENTILATION SYSTEM DUCTS AND EXHAUST EQUIPMENT 506.1 General. Commercial kitchen hood ventilation ducts and exhaust equipmentshall comply with the requirements of this section. Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood served. 506.2 Corrosion protection. Ducts exposed to the outside atmosphere or subject to a corrosive environment shall be protected against corrosion in an approved manner. 506.3 Ducts serving Type I hoods. Type I exhaust ducts shall be independent of all other exhaust systems except as provided in Section 506.3.5. Commercial kitchen duct sys- tems serving Type I hoods shall be designed, constructed and installed in accordance with Sections 506.3.1 through 506.3.13.3. 506.3.1 Duct materials. Ducts serving Type I hoods shall be constructed of materials in accordance with Sections 506.3.1.1 and 506.3.1.2. 48 2012 INTERNATIONAL MECHANICAL CODE® 4 I Co,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, (,Fod,Yo,,bymytl,dputy,o,ie,bto,auoosd Single—mly mpymg Pod-PyodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDRRAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS 506.3.1.1 Grease duct materials. Grease ducts serving Type I hoods shall be constructed of steel having a min- imum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) or stainless steel not less than 0.0450 inch (1.14 mm) (No. 18 gage) in thickness. Exception: Factory -built commercial kitchen grease ducts listed and labeled in accordance with UL 1978 and installed in accordance with Section 304.1. 506.3.1.2 Makeup air ducts. Makeup air ducts con- necting to or within 18 inches (457 mm) of a Type I hood shall be constructed and installed in accordance with Sections 603.1, 603.3, 603.4, 603.9, 603.10 and 603.12. Duct insulation installed within 18 inches (457 mm) of a Type I hood shall be noncombustible or shall be listed for the application. 506.3.2 Joints, seams and penetrations of grease ducts. Joints, seams and penetrations of grease ducts shall be made with a continuous liquid -tight weld or braze made on the external surface of the duct system. Exceptions: 1. Penetrations shall not be required to be welded or brazed where sealed by devices that are listed for the application. 2. Internal welding or brazing shall not be prohib- ited provided that the joint is formed or ground smooth and is provided with ready access for inspection. 3. Factory -built commercial kitchen grease ducts listed and labeled in accordance with UL 1978 and installed in accordance with Section 304.1. 506.3.2.1 Duct joint types. Duct joints shall be butt joints, welded flange joints with a maximum flange depth of V, inch (12.7 mm) or overlapping duct joints of either the telescoping or bell type. Overlapping joints shall be installed to prevent ledges and obstruc- tions from collecting grease or interfering with gravity drainage to the intended collection point. The differ- ence between the inside cross -sectional dimensions of overlapping sections of duct shall not exceed '/q inch (6 min). The length of overlap for overlapping duct joints shall not exceed 2 inches (51 mm). 506.3.2.2 Duct -to -hood joints. Duct -to -hood joints shall be made with continuous internal or external liq- uid -tight welded or brazed joints. Such joints shall be smooth, accessible for inspection, and without grease traps. Exceptions: This section shall not apply to: 1. A vertical duct -to -hood collar connection made in the top plane of the hood in accor- dance with all of the following: 1.1. The hood duct opening shall have a 1-inch-deep (25 mm), full perimeter, welded flange turned down into the hood interior at an angle of 90 degrees (1.57 rad) from the plane of the opening. 1.2. The duct shall have a 1-inch-deep (25 mm) flange made by a 1-inch by 1—inch (25 mm by 25 mm) angle iron welded to the full perimeter of the duct not less than 1 inch (25 mm) above the bottom end of the duct. 1.3. A gasket rated for use at not less than 1,500OF (815°C) is installed between the duct flange and the top of the hood. 1.4. The duct -to -hood joint shall be secured by stud bolts not less than (/4 inch (6.4 mm) in diameter welded to the hood with a spacing not greater than 4 inches (102 mm) on center for the full perimeter of the opening. All bolts and nuts are to be secured with lockwashers. 2. Listed and labeled duct -to -hood collar connec- tions installed in accordance with Section 304.1. 506.3.2.3 Duct -to -exhaust fan connections. Duct -to - exhaust fan connections shall be flanged and gasketed at the base of the fan for vertical discharge fans; shall be flanged, gasketed and bolted to the inlet of the fan for side -inlet utility fans; and shall be flanged, gasketed and bolted to the inlet and outlet of the fan for in -line fans. Gasket and sealing materials shall be rated for continuous duty at a temperature of not less than 1500OF (8160C). 506.3.2.4 Vibration isolation. A vibration isolation connector for connecting a duct to a fan shall consist of noncombustible packing in a metal sleeve joint of approved design or shall be a coated -fabric flexible duct connector listed and labeled for the application. Vibration isolation connectors shall be installed only at the connection of a duct to a fan inlet or outlet. 506.3.2.5 Grease duct test Prior to the use or conceal- ment of any portion of a grease duct system, a leakage test shall be performed. Ducts shall be considered to be concealed where installed in shafts or covered by coat- ings or wraps that prevent the ductwork from being visually inspected on all sides. The permit holder shall be responsible to provide the necessary equipment and perform the grease duct leakage test. A light test shall be performed to determine that all welded and brazed joints are liquid tight. A light test shall be performed by passing a lamp having a power rating of not less than 100 watts through the entire section of ductwork to be tested. The lamp shall be open so as to emit light equally in all directions perpendicular to the duct walls. A test shall be performed for the entire duct system, including the hood -to -duct connection. The duct work shall be per- mitted to be tested in sections, provided that every joint is tested. For listed factory -built grease ducts, this test 2012 INTERNATIONAL MECHANICAL CODE® 49 I II I CoTy,ght @ zoI I ICC ALL RIGHTS RESERVED Awsed by().(-)O,d,,Nombsx1ooveo189 oe SIP so.2.o19o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg Podortuodmgp4okbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS shall be limited to duct joints assembled in the field and shall exclude factory welds. 506.3.3 Grease duct supports. Grease duct bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of the Interna- tional Building Code. Bolts, screws, rivets and other mechanical fasteners shall not penetrate duct walls. 506.3.4 Air velocity. Grease duct systems serving a Type I hood shall be designed and installed to provide an air velocity within the duct system of not less than 500 feet per minute (2.5 m/s). Exception: The velocity limitations shall not apply within duct transitions utilized to connect ducts to dif- ferently sized or shaped openings in hoods and fans, provided that such transitions do not exceed 3 feet (914 mm) in length and are designed to prevent the trapping of grease. 506.3.5 Separation of grease duct system. A separate grease duct system shall be provided for each Type I hood. A separate grease duct system is not required where all of the following conditions are met: 1. All interconnected hoods are located within the same story. 2. All interconnected hoods are located within the same room or in adjoining rooms. 3. Interconnecting ducts do not penetrate assemblies required to be fire -resistance rated. 4. The grease duct system does not serve solid -fuel - fired appliances. 506.3.6 Grease duct clearances. Where enclosures are not required, grease duct systems and exhaust equipment serving a Type I hood shall have a clearance to combusti- ble construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construction and gypsum wallboard attached to noncombustible structures of not less than 3 inches (76 mm). Exceptions: 1. Factory -built commercial kitchen grease ducts listed and labeled in accordance with UL 1978. 2. Listed and labeled exhaust equipment installed in accordance with Section 304.1. 3. Where commercial kitchen grease ducts are con- tinuously covered on all sides with a listed and labeled field -applied grease duct enclosure mate- rial, system, product or method of construction specifically evaluated for such purpose in accor- dance with ASTM E 2336, the required clear- ance shall be in accordance with the listing of such material, system, product or method. 506.3.7 Prevention of grease accumulation in grease ducts. Duct systems serving a Type I hood shall be con- structed and installed so that grease cannot collect in any portion thereof, and the system shall slope not less than one-fourth unit vertical in 12 units horizontal (2-percent slope) toward the hood or toward a grease reservoir designed and installed in accordance with Section 506.3.7.1. Where horizontal ducts exceed 75 feet (22 860 mm) in length, the slope shall be not less than one unit ver- tical in 12 units horizontal (8.3 percent slope). 506.3.7.1 Grease reservoirs. Grease reservoirs shall: 1. Be constructed as required for the grease duct they serve. 2. Be located on the bottom of the horizontal duct or the bottommost section of the duct riser. 3. Have a length and width of not less than 12 inches (305 mm). Where the grease duct is less than 12 inches (305 mm) in a dimension, the res- ervoir shall be not more than 2 inches (51 mm) smaller than the duct in that dimension. 4. Have a depth of not less than 1 inch (25.4 mid. 5. Have a bottom that is sloped to a point for drain- age. 6. Be provided with a cleanout opening constructed in accordance with Section 506.3.8 and installed to provide direct access to the reservoir. The cleanout opening shall be located on a side or on top of the duct so as to permit cleaning of the res- ervoir. 7. Be installed in accordance with the manufac- turer's instructions where manufactured devices are utilized. 506.3.8 Grease duct cleanouts and openings. Grease duct cleanouts and openings shall comply with all of the following: 1. Grease ducts shall not have openings except where required for the operation and maintenance of the system. 2. Sections of grease ducts that are inaccessible from the hood or discharge openings shall be provided with cleanout openings. 3. Cleanouts and openings shall be equipped with tight -fitting doors constructed of steel having a thickness not less than that required for the duct. 4. Cleanout doors shall be installed liquid tight. 5. Door assemblies including any frames and gaskets shall be approved for the application and shall not have fasteners that penetrate the duct. 6. Gasket and sealing materials shall be rated for not less than 1500°F (816°C). 7. Listed door assemblies shall be installed in accor- dance with the manufacturer's instructions. 506.3.8.1 Personnel entry. Where ductwork is large enough to allow entry of personnel, not less than one approved or listed opening having dimensions not less than 22 inches by 20 inches (559 mm by 508 mm) shall be provided in the horizontal sections, and in the top of vertical risers. Where such entry is provided, the duct and its supports shall be capable of supporting the addi- 50 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 01 av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I IT od,,to—by POVO d party. o,±RYb�toc P,,Uoosd Smglo mly, So, Pod o Nyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS tional load, and the cleanouts specified in Section 506.3.8 are not required. 506.3.8.2 Cleanouts serving in -line fans. A cleanout shall be provided for both the inlet side and outlet side of an in -line fan except where a duct does not connect to the fan. Such cleanouts shall be located within 3 feet (914 mm) of the fan duct connections. 506.3.9 Grease duct horizontal cleanouts. Cleanouts serving horizontal sections of grease ducts shall: 1. Be spaced not more than 20 feet (6096 mm) apart. 2. Be located not more than 10 feet (3048 mm) from changes in direction that are greater than 45 degrees (.79 rad). 3. Be located on the bottom only where other locations are not available and shall be provided with internal damming of the opening such that grease will flow past the opening without pooling. Bottom cleanouts and openings shall be approved for the application and installed liquid -tight. 4. Not be closer than 1 inch (25.4 mm) from the edges of the duct. 5. Have opening dimensions of not less than 12 inches by 12 inches (305 mm by 305 mm). Where such dimensions preclude installation, the opening shall be not less than 12 inches (305 mm) on one side and shall be large enough to provide access for cleaning and maintenance. 6. Shall be located at grease reservoirs. 506.3.10 Underground grease duct installation. Under- ground grease duct installations shall comply with all of the following: 1. Underground grease ducts shall be constructed of steel having a minimum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) and shall be coated to provide protection from corrosion or shall be con- structed of stainless steel having a minimum thick- ness of 0.0450 inch (1.140 mm) (No. 18 gage). 2. The underground duct system shall be tested and approved in accordance with Section 506.3.2.5 prior to coating or placement in the ground. 3. The underground duct system shall be completely encased in concrete with a minimum thickness of 4 inches (102 mm). 4. Ducts shall slope toward grease reservoirs. 5. A grease reservoir with a cleanout to allow cleaning of the reservoir shall be provided at the base of each vertical duct riser. 6. Cleanouts shall be provided with access to permit cleaning and inspection of the duct in accordance with Section 506.3. 7. Cleanouts in horizontal ducts shall be installed on the topside of the duct. 8. Cleanout locations shall be legibly identified at the point of access from the interior space. 506.3.11 Grease duct enclosures. A grease duct serving a Type I hood that penetrates a ceiling, wall, floor or any concealed spaces shall be enclosed from the point of pene- tration to the outlet terminal. A duct shall penetrate exte- rior walls only at locations where unprotected openings are permitted by the International Building Code. The duct enclosure shall serve a single grease duct and shall not contain other ducts, piping or wiring systems. Duct enclosures shall be either field -applied or factory -built. Duct enclosures shall have a fire -resistance rating of not less than that of the assembly penetrated and not less than 1 hour. Duct enclosures shall be as prescribed by Section 506.3.11.1, 506.3.11.2 or 506.3.11.3. 506.3.11.1 Shaft enclosure. Commercial kitchen grease ducts constructed in accordance with Section 506.3.1 shall be permitted to be enclosed in accordance with the International Building Code requirements for shaft construction. Such grease duct systems and exhaust equipment shall have a clearance to combusti- ble construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construc- tion and gypsum wallboard attached to noncombustible structures of not less than 6 inches (152 mm). Duct enclosures shall be sealed around the duct at the point of penetration and vented to the outside of the building through the use of weather -protected openings. 506.3.11.2 Field -applied grease duct enclosure. Commercial kitchen grease ducts constructed in accor- dance with Section 506.3.1 shall be enclosed by a field - applied grease duct enclosure that is a listed and labeled material, system, product, or method of construction specifically evaluated for such purpose in accordance with ASTM E 2336. The surface of the duct shall be continuously cov- ered on all sides from the point at which the duct origi- nates to the outlet terminal. Duct penetrations shall be protected with a through -penetration fire -stop system classified in accordance with ASTM E 814 or UL 1479 and having a 'T" and "T" rating equal to the fire -resis- tance rating of the assembly being penetrated. Such systems shall be installed in accordance with the listing and the manufacturer's installation instructions. Partial application of a field -applied grease duct enclosure sys- tem shall not be installed for the sole purpose of reduc- ing clearances to combustibles at isolated sections of grease duct. Exposed duct -wrap systems shall be pro- tected where subject to physical damage. 506.3.11.3 Factory -built grease duct assemblies. Fac- tory -built grease duct assemblies incorporating integral enclosure materials shall be listed and labeled for use as commercial kitchen grease duct assemblies in accor- dance with UL 2221. Duct penetrations shall be pro- tected with a through -penetration firestop system classified in accordance with ASTM E 814 or UL 1479 and having an " F" and "T" rating equal to the fire -resis- tance rating of the assembly being penetrated. Such assemblies shall be installed in accordance with the list- ing and the manufacturer's installation instructions. 2012 INTERNATIONAL MECHANICAL CODE® 51 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS 506.3.11.4 Duct enclosure not required. A duct enclosure shall not be required for a grease duct that penetrates only a nonfire-resistance-rated roof/ceiling assembly. 506.3.12 Grease duct fire -resistive access opening. Where cleanout openings are located in ducts within a fire - resistance -rated enclosure, access openings shall be pro- vided in the enclosure at each cleanout point. Access openings shall be equipped with tight -fitting sliding or hinged doors that are equal in fire -resistive protection to that of the shaft or enclosure. An approved sign shall be placed on access opening panels with wording as follows: "ACCESS PANEL. DO NOT OBSTRUCT." 506.3.13 Exhaust outlets serving Type I hoods. Exhaust outlets for grease ducts serving Type I hoods shall con- form to the requirements of Sections 506.3.13.1 through 506.3.13.3. 506.3.13.1 Termination above the roof. Exhaust out- lets that terminate above the roof shall have the dis- charge opening located not less than 40 inches (1016 mm) above the roof surface. 506.3.13.2 Termination through an exterior wall. Exhaust outlets shall be permitted to terminate through exterior walls where the smoke, grease, gases, vapors and odors in the discharge from such terminations do not create a public nuisance or a fire hazard. Such ter- minations shall not be located where protected open- ings are required by the International Building Code. Other exterior openings shall not be located within 3 feet (914 mm) of such terminations. 506.3.13.3 Termination location. Exhaust outlets shall be located not less than 10 feet (3048 mm) horizontally from parts of the same or contiguous buildings, adja- cent buildings and adjacent property lines and shall be located not less than 10 feet (3048 mm) above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet (3048 mm) horizontally from or not less than 3 feet (914 mm) above air intake openings into any building. Exception: Exhaust outlets shall terminate not less than 5 feet (1524 mm) horizontally from parts of the same or contiguous building, an adjacent building, adjacent property line and air intake openings into a building where air from the exhaust outlet dis- charges away from such locations. 506.4 Ducts serving Type II hoods. Commercial kitchen exhaust systems serving Type II hoods shall comply with Sections 506.4.1 and 506.4.2. 506.4.1 Ducts. Ducts and plenums serving Type II hoods shall be constructed of rigid metallic materials. Duct con- struction, installation, bracing and supports shall comply with Chapter 6. Ducts subject to positive pressure and ducts conveying moisture -laden or waste -heat -laden air shall be constructed, joined and sealed in an approved manner. 506.4.2 Type II terminations. Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all of the following: 1. Exhaust outlets shall terminate not less than 3 feet (914 mm) in any direction from openings into the building. 2. Outlets shall terminate not less than 10 feet (3048 mm) from property lines or buildings on the same lot. 3. Outlets shall terminate not less than 10 feet (3048 mm) above grade. 4. Outlets that terminate above a roof shall terminate not less than 30 inches (762 mm) above the roof sur- face. 5. Outlets shall terminate not less than 30 inches (762 mm) from exterior vertical walls 6. Outlets shall be protected against local weather con- ditions. 7. Outlets shall not be directed onto walkways. 8. Outlets shall meet the provisions for exterior wall opening protectives in accordance with the Intema- tional Building Code. 506.5 Exhaust equipment. Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.5 and shall be of an approved design or shall be listed for the application. 506.5.1 Exhaust fans. Exhaust fan housings serving a Type I hood shall be constructed as required for grease ducts in accordance with Section 506.3.1.1. Exception: Fans listed and labeled in accordance with UL 762. 506.5.1.1 Fan motor. Exhaust fan motors shall be located outside of the exhaust airstream. 506.5.2 Exhaust fan discharge. Exhaust fans shall be positioned so that the discharge will not impinge on the roof, other equipment or appliances or parts of the struc- ture. A vertical discharge fan shall be manufactured with an approved drain outlet at the lowest point of the housing to permit drainage of grease to an approved grease reser- voir. 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches (457 mm) above the roof surface. 506.5.4 Clearances. Exhaust equipment serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm). Exception: Factory -built exhaust equipment installed in accordance with Section 304.1 and listed for a lesser clearance. 52 2012 INTERNATIONAL MECHANICAL CODE® Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( od,,to—by POVO d party. o,±RYb�toc P,,Uoosd Smglo mly, So, Pod o Nyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS 506.5.5 Termination location. The outlet of exhaust equipment serving Type I hoods shall be in accordance with Section 506.3.13. Exception: The minimum horizontal distance between vertical discharge fans and parapet -type building struc- tures shall be 2 feet (610 mm) provided that such struc- tures are not higher than the top of the fan discharge opening. SECTION 507 COMMERCIAL KITCHEN HOODS 507.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of this section. Hoods shall be Type I or II and shall be designed to capture and confine cooking vapors and residues. Commercial kitchen exhaust hood systems shall operate during the cooking operation. Exceptions: 1. Factory -built commercial exhaust hoods that are listed and labeled in accordance with UL 710, and installed in accordance with Section 304.1 shall not be required to comply with Sections 507.4, 507.5, 507.7, 507.11, 507.12, 507.13, 507.14, and 507.15. 2. Factory -built commercial cooking recirculating sys- tems that are listed and labeled in accordance with UL 71013, and installed in accordance with Section 304.1 shall not be required to comply with Sections 507.4, 507.5, 507.7, 507.11, 507.12, 507.13, 507.14, and 507.15. Spaces in which such systems are located shall be considered to be kitchens and shall be ventilated in accordance with Table 403.3. For the purpose of determining the floor area required to be ventilated, each individual appliance shall be considered as occupying not less than 100 square feet (9.3 m'). 3. Net exhaust volumes for hoods shall be permitted to be reduced during part -load cooking conditions, where engineered or listed multispeed or variable - speed controls automatically operate the exhaust system to maintain capture and removal of cooking effluents as required by this section. Reduced vol- umes shall not be below that required to maintain capture and removal of effluents from the idle cook- ing appliances that are operating in a standby mode. 507.2 Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down -draft exhaust systems and such appliances and exhaust systems are listed and labeled for the applica- tion in accordance with NITA 96, a hood shall not be required at or above them. 507.2.1 Type I hoods. Type I hoods shall be installed I where cooking appliances produce grease or smoke as a result of the cooking process. Type I hoods shall be installed over medium -duty, heavy-duty and extra -heavy- duty cooking appliances. Type I hoods shall be installed over lightdutycooking appliances that produce grease or smoke. Exception: A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm (0.236 in') in accordance with Section 17 of UL 710B 507.2.1.1 Operation. Type I hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. A method of interlock between an exhaust hood system and appliances equipped with standing pilot burners shall not cause the pilot burners to be extinguished. A method of interlock between an exhaust hood system and cooking appliances shall not involve or depend upon any component of a fire extinguishing system. 507.2.1.2 Exhaust flow rate label. Type I hoods shall bear a label indicating the minimum exhaust flow rate in cfm per linear foot (1.55 L/s per linear meter) of hood that provides for capture and containment of the exhaust effluent for the cooking appliances served by the hood, based on the cooking appliance duty classifi- cations defined in this code. 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. Type II hoods shall be installed above all appliances that produce products of combustion and do not produce grease or smoke as a result of the cooking pro- cess. Spaces containing cooking appliances that do not require Type II hoods shall be provided with exhaust at a rate of 0.70 cfm per square foot (0.00033 m3/s). For the purpose of determining the floor area required to be exhausted, each individual appliance that is not required to be installed under a Type II hood shall be considered as occupying not less than 100 square feet (9.3 m'). Such additional square footage shall be provided with exhaust at a rate of 0.70 cfm per square foot [.00356 m3/(s - m')]. 507.2.3 Domestic cooking appliances used for commer- cial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or Type II hoods as required for the type of appliances and processes in accordance with Sections 507.2, 507.2.1 and 507.2.2. 2012 INTERNATIONAL MECHANICAL CODE® 53 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS 507.2.4 Extra -heavy-duty. Type I hoods for use over extra -heavy-duty cooling appliances shall not cover heavy, medium- or lightdutyappliances. Such hoods shall discharge to an exhaust system that is independent of other exhaust systems. 507.3 Fuel -burning appliances. Where vented fuel -burning appliances are located in the same room or space as the hood, provisions shall be made to prevent the hood system from interfering with normal operation of the appliance vents. 507.4 Type I materials. Type I hoods shall be constructed of steel having a minimum thickness of 0.0466 inch (1.181 mm) (No. 18 gage) or stainless steel not less than 0.0335 inch [0.8525 mm (No. 20 MSG)] in thickness. 507.5 Type II hood materials. Type II hoods shall be con- structed of steel having a minimum thickness of 0.0296 inch (0.7534 mm) (No. 22 gage) or stainless steel not less than 0.0220 inch (0.5550 min) (No. 24 gage) in thickness, copper sheets weighing not less than 24 ounces per square foot (7.3 kg/m') or of other approved material and gage. 507.6 Supports. Type I hoods shall be secured in place by non-combustible supports. All Type I and Type II hood sup- ports shall be adequate for the applied load of the hood, the unsupported ductwork, the effluent loading and the possible weight of personnel working in or on the hood. 507.7 Hood joints, seams and penetrations. Hood joints, seams and penetrations shall comply with Sections 507.7.1 and 507.7.2. 507.7.1 Type I hoods. External hood joints, seams and penetrations for Type I hoods shall be made with a contin- uous external liquid -tight weld or braze to the lowest out- ermost perimeter of the hood. Internal hood joints, seams, penetrations, filter support frames and other appendages attached inside the hood shall not be required to be welded or brazed but shall be otherwise sealed to be grease tight. Exceptions: 1. Penetrations shall not be required to be welded or brazed where sealed by devices that are listed for the application. 2. Internal welding or brazing of seams, joints and penetrations of the hood shall not be prohibited provided that the joint is formed smooth or ground so as to not trap grease, and is readily cleanable. 507.7.2 Type II hoods. Joints, seams and penetrations for Type II hoods shall be constructed as set forth in Chapter 6, shall be sealed on the interior of the hood and shall pro- vide a smooth surface that is readily cleanable and water tight. 507.8 Cleaning and grease gutters. A hood shall be designed to provide for thorough cleaning of the entire hood. Grease gutters shall drain to an approved collection recepta- cle that is fabricated, designed and installed to allow access for cleaning. 507.9 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm). Exception: Clearance shall not be required from gypsum wallboard or '/z inch (12.7 mm) or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombusti- ble material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood. 507.10 Hoods penetrating a ceiling. Type I hoods or por- tions thereof penetrating a ceiling, wall or furred space shall comply with Section 506.3.11. Field -applied grease duct enclosure systems, as addressed in Section 506.3.11.2, shall not be utilized to satisfy the requirements of this section. 507.11 Grease filters. Type I hoods shall be equipped with grease filters listed and labeled in accordance with UL 1046 and designed for the specific purpose. Grease -collecting equipment shall be provided with access for cleaning. The lowest edge of a grease filter located above the cooking sur- face shall be not less than the height specified in Table 507.11. TABLE 507.11 MINIMUM DISTANCE BETWEEN THE LOWEST EDGE OF A GREASE FILTER AND THE COOKING SURFACE OR THE HEATING SURFACE TYPE OF COOKING APPLIANCES HEIGHT ABOVE COOKING SURFACE (feet) Without exposed flame 0.5 Exposed flame and burners 2 Exposed charcoal and charbroil type 3.5 For SI 1 foot - 304 8 min 507.11.1 Criteria. Filters shall be of such size, type and arrangement as will permit the required quantity of air to pass through such units at rates not exceeding those for which the filter or unit was designed or approved. Filter units shall be installed in frames or holders so as to be readily removable without the use of separate tools, unless designed and installed to be cleaned in place and the sys- tem is equipped for such cleaning in place. Removable fil- ter units shall be of a size that will allow them to be cleaned in a dishwashing machine or pot sink. Filter units shall be arranged in place or provided with drip-intercept- Ing devices to prevent grease or other condensate from dripping into food or on food preparation surfaces. 507.11.2 Mounting position. Filters shall be installed at an angle of not less than 45 degrees (0.79 rad) from the horizontal and shall be equipped with a drip tray beneath the lower edge of the filters. 507.12 Canopy size and location. The inside lower edge of canopy -type Type I and II commercial hoods shall overhang or extend a horizontal distance of not less than 6 inches (152 min) beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the 54 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O[d6 Nombsx/00760/89 oc SIP SO, 20/90/47 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( [,FodAt.. by mythdparty.o,±RYb�tocP,,UoFPd Single—oPIA PTymg Pod o Nyodmg ploIRbUd ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE FOR REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS front lower lip of the hood and such surface shall not exceed 4 feet (1219 mm). Exception: The hood shall be permitted to be flush with the outer edge of the cooking surface where the hood is closed to the appliance side by a noncombustible wall or panel. 507.13 Capacity of hoods. Commercial food service hoods shall exhaust a minimum net quantity of air determined in accordance with this section and Sections 507.13.1 through 507.13.5. The net quantity of exhaust air shall be calculated by subtracting any airflow supplied directly to a hood cavity from the total exhaust flow rate of a hood. Where any combi- nation of heavy-duty, medium -duty and lightdutycooking appliances are utilized under a single hood, the exhaust rate required by this section for the heaviest duty appliance cov- ered by the hood shall be used for the entire hood. 507.13.1 Extra -heavy-duty cooking appliances. The minimum net airflow for hoods, as determined by Section 507.2, used for extra -heavy-duty cooking appliances shall be determined as follows: Type of Hood CFM per linear foot of hood Backshelf/pass-over Not allowed Double island canopy (per side) 550 Eyebrow Not allowed Single island canopy 700 Wall -mounted canopy 550 For SI 1 cfm per linear foot= 1 55 L/s per linear meter 507.13.2 Heavy-duty cooking appliances. The minimum net airflow for hoods, as determined by Section 507.2, used for heavy-duty cooking appliances shall be deter- mined as follows: Type of Hood CFM per linear foot of hood Backshelf/pass-over 400 Double island canopy 400 (per side) Eyebrow Not allowed Single island canopy 600 Wall -mounted canopy 400 For SI 1 cfm per linear foot= 1 55 L/s per linear meter 507.13.3 Medium -duty cooking appliances. The mini- mum net airflow for hoods, as determined by Section 507.2, used for medium -duty cooking appliances shall be determined as follows: Type of Hood CFM per linear foot of hood Backshelf/pass-over 300 Double island canopy 300 (per side) Eyebrow 250 Single island canopy 500 Wall -mounted canopy 300 For SI 1 cfm per linear foot= 1 55 L/s per linear meter 507.13.4 Light -duty cooking appliances. The minimum net airflow for hoods, as determined by Section 507.2, used for lightdutycooking appliances and food service preparation shall be determined as follows: Type of Hood CFM per linear foot of hood Backshelf/pass-over 250 Double island canopy 250 (per side) Eyebrow 250 Single island canopy 400 Wall -mounted canopy 200 For SI 1 cfm per linear foot= 1 55 L/s per linear meter 507.13.5 Dishwashing appliances. The minimum net air- flow for Type II hoods used for dishwashing appliances shall be 100 CFM per linear foot of hood length. Exception: Dishwashing appliances and equipment installed in accordance with Section 507.2.2. 507.14 Noncanopy size and location. Noncanopy-type hoods shall be located a maximum of 3 feet (914 fund above the cooking surface. The edge of the hood shall be set back a maximum of 1 foot (305 fund from the edge of the cooking surface. 507.15 Exhaust outlets. Exhaust outlets located within the hood shall be located so as to optimize the capture of particu- late matter. Each outlet shall serve not more than a 12-foot (3658 mm) section of hood. 507.16 Performance test. A performance test shall be con- ducted upon completion and before final approval of the installation of a ventilation system serving commercial cook- ing appliances. The test shall verify the rate of exhaust air- flow required by Section 507.13, makeup airflow required by Section 508 and proper operation as specified in this chapter. The permit holder shall furnish the necessary test equipment and devices required to perform the tests. 507.16.1 Capture and containment test. The permit holder shall verify capture and containment performance of the exhaust system. This field test shall be conducted with all appliances under the hood at operating tempera- tures, with all sources of outdoor air providing makeup air for the hood operating and with all sources of recirculated air providing conditioning for the space in which the hood is located operating. Capture and containment shall be ver- ified visually by observing smoke or steam produced by actual or simulated cooking, such as with smoke candles, smoke puffers, etc. SECTION 508 COMMERCIAL KITCHEN MAKEUP AIR 508.1 Makeup air. Makeup air shall be supplied during the operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances. The amount of makeup airsupplied to the building from all sources shall be approximately equal to the amount of exhaust air for all exhaust systems for the building. The makeup air shall not reduce the effectiveness of the exhaust system. Makeup air shall be provided by gravity or mechanical means or both. Mechanical makeup air systems shall be automatically con- 2012 INTERNATIONAL MECHANICAL CODE® 55 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS trolled to start and operate simultaneously with the exhaust system. Makeup air intake opening locations shall comply with Section 401.4. 508.1.1 Makeup air temperature. The temperature dif- ferential between makeup airand the air in the conditioned space shall not exceed 10°F (6°C) except where the added heating and cooling loads of the makeup air do not exceed the capacity of the HVAC system. 508.2 Compensating hoods. Manufacturers of compensating hoods shall provide a label indicating minimum exhaust flow and/or maximum makeup airflow that provides capture and containment of the exhaust effluent. Exception: Compensating hoods with makeup air sup- plied only from the front face discharge and side face dis- charge openings shall not be required to be labeled with the maximum makeup airflow. SECTION 509 FIRE SUPPRESSION SYSTEMS 509.1 Where required. Commercial cooking appliances required by Section 507.2.1 to have a Type I hood shall be provided with an approved automatic fire suppression system complying with the International Building Code and the International Fire Code. SECTION 510 HAZARDOUS EXHAUST SYSTEMS 510.1 General. This section shall govern the design and con- struction of duct systems for hazardous exhaust and shall determine where such systems are required. Hazardous exhaust systems are systems designed to capture and control hazardous emissions generated from product handling or pro- cesses, and convey those emissions to the outdoors. Hazard- ous emissions include flammable vapors, gases, fumes, mists or dusts, and volatile or airborne materials posing a health hazard, such as toxic or corrosive materials. For the purposes of this section, the health hazard rating of materials shall be as specified in NFPA 704. For the purposes of the provisions of Section 510, a labo- ratory shall be defined as a facility where the use of chemi- cals is related to testing, analysis, teaching, research or developmental activities. Chemicals are used or synthesized on a nonproduction basis, rather than in a manufacturing pro- cess. 510.2 Where required. A hazardous exhaust system shall be required wherever operations involving the handling or pro- cessing of hazardous materials, in the absence of such exhaust systems and under normal operating conditions, have the potential to create one of the following conditions: 1. A flammable vapor, gas, fume, mist or dust is present in concentrations exceeding 25 percent of the lower flammability limit of the substance for the expected room temperature. 3. A vapor, gas, fume, mist or dust with a health -hazard rating of 1, 2 or 3 is present in concentrations exceed- ing 1 percent of the median lethal concentration of the substance for acute inhalation toxicity. Exception: Laboratories, as defined in Section 510.1, except where the concentrations listed in Item 1 are exceeded or a vapor, gas, fume, mist or dust with a health - hazard rating of 1, 2, 3 or 4 is present in concentrations exceeding 1 percent of the median lethal concentration of the substance for acute inhalation toxicity. [F] 510.2.1 Lumber yards and woodworking facilities. Equipment or machinery located inside buildings at lum- ber yards and woodworking facilities which generates or emits combustible dust shall be provided with an approved dust -collection and exhaust system installed in confor- mance with this section and the International Fire Code. Equipment and systems that are used to collect, process or convey combustible dusts shall be provided with an approved explosion -control system. [F] 510.2.2 Combustible fibers. Equipment or machinery within a building which generates or emits combustible fibers shall be provided with an approved dust -collecting and exhaust system. Such systems shall comply with this code and the International Fire Code. 510.3 Design and operation. The design and operation of the exhaust system shall be such that flammable contaminants are diluted in noncontaminated air to maintain concentrations in the exhaust flow below 25 percent of the contaminant's lower flammability limit. 510.4 Independent system. Hazardous exhaust systems shall be independent of other types of exhaust systems. Incompati- ble materials, as defined in the International Fire Code, shall not be exhausted through the same hazardous exhaust system. Hazardous exhaust systems shall not share common shafts with other duct systems, except where such systems are haz- ardous exhaust systems originating in the same fire area. Exception: The provision of this section shall not apply to laboratory exhaust systems where all of the following con- ditions apply: 1. All of the hazardous exhaust ductwork and other laboratory exhaust within both the occupied space and the shafts are under negative pressure while in operation. 2. The hazardous exhaust ductwork manifolded together within the occupied space must originate within the same fire area. 3. Each control branch has a flow regulating device. 4. Perchloric acid hoods and connected exhaust shall be prohibited from manifolding. 5. Radioisotope hoods are equipped with filtration and/ or carbon beds where required by the registered design professional. 6. Biological safety cabinets are filtered. 2. A vapor, gas, fume, mist or dust with a health -hazard 7. Provision is made for continuous maintenance of rating of 4 is present in any concentration. negative static pressure in the ductwork. 56 2012 INTERNATIONAL MECHANICAL CODE® 17 Co,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( N ,Fod,Yo,,bymytl,dputy,o,Abau�to,o,sd Single—mlym,ymg and-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS Contaminated air shall not be recirculated to occupiable areas. Air containing explosive or flammable vapors, fumes or dusts; flammable, highly toxic or toxic gases; or radioac- tive material shall be considered to be contaminated. 510.5 Design. Systems for removal of vapors, gases and smoke shall be designed by the constant velocity or equal friction methods. Systems conveying particulate matter shall be designed employing the constant velocity method. 510.5.1 Balancing. Systems conveying explosive or radioactive materials shall be prebalanced by duct sizing. Other systems shall be balanced by duct sizing with bal- ancing devices, such as dampers. Dampers provided to balance airflow shall be provided with securely fixed min- imum -position blocking devices to prevent restricting flow below the required volume or velocity. 510.5.2 Emission control. The design of the system shall be such that the emissions are confined to the area in which they are generated by air currents, hoods or enclo- sures and shall be exhausted by a duct system to a safe location or treated by removing contaminants. 510.5.3 Hoods required. Hoods or enclosures shall be used where contaminants originate in a limited area of a space. The design of the hood or enclosure shall be such that air currents created by the exhaust systems will cap- ture the contaminants and transport them directly to the exhaust duct. 510.5.4 Contaminant capture and dilution. The velocity and circulation of air in work areas shall be such that con- taminants are captured by an airstream at the area where the emissions are generated and conveyed into a product - conveying duct system. Contaminated air from work areas where hazardous contaminants are generated shall be diluted below the thresholds specified in Section 510.2 with air that does not contain other hazardous contami- nants. 510.5.5 Makeup air. Makeup air shall be provided at a rate approximately equal to the rate that air is exhausted by the hazardous exhaust system. Makeup -air intakes shall be located so as to avoid recirculation of contaminated air. 510.5.6 Clearances. The minimum clearance between hoods and combustible construction shall be the clearance required by the duct system. 510.5.7 Ducts. Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through ducts and plenums. 510.6 Penetrations. Penetrations of structural elements by a hazardous exhaust system shall conform to Sections 510.6.1 through 510.6.4. Exception: Duct penetrations within H-5 occupancies as allowed by the International Building Code. 510.6.1 Fire dampers and smoke dampers. Fire dampers and smoke dampers are prohibited in hazardous exhaust ducts. 510.6.2 Floors. Hazardous exhaust systems that penetrate a floor/ceiling assembly shall be enclosed in a fire -resis- tance -rated shaft constructed in accordance with the Inter- national Building Code. 510.6.3 Wall assemblies. Hazardous exhaust duct systems that penetrate fire -resistance -rated wall assemblies shall be enclosed in fire -resistance -rated construction from the point of penetration to the outlet terminal, except where the interior of the duct is equipped with an approved auto- matic fire suppression system. Ducts shall be enclosed in accordance with the International Building Code require- ments for shaft construction and such enclosure shall have a minimum fire -resistance -rating of not less than the high- est fire -resistance -rated wall assembly penetrated. 510.6.4 Fire walls. Ducts shall not penetrate a fire wall. 510.7 Suppression required. Ducts shall be protected with an approved automatic fire suppression system installed in accordance with the International Building Code. Exceptions 1. An approved automatic fire suppression system shall not be required in ducts conveying materials, fumes, mists and vapors that are nonflammable and noncombustible under all conditions and at any con- centrations. 2. Automatic fire suppression systems shall not be required in metallic and noncombustible, nonmetal- lic exhaust ducts in semiconductor fabrication facili- ties. 3. An approved automatic fire suppression system shall not be required in ducts where the largest cross -sectional diameter of the duct is less than 10 inches (254 mm). 4. For laboratories, as defined in Section 510.1, auto- matic fire protection systems shall not be required in laboratory hoods or exhaust systems 510.8 Duct construction. Ducts used to convey hazardous exhaust shall be constructed of approved G90 galvanized sheet steel, with a minimum nominal thickness as specified in Table 510.8. Nonmetallic ducts used in systems exhausting nonflammable corrosive fumes or vapors shall be listed and labeled Nonmetallic ducts shall have a flame spread index of 25 or less and a smoke -developed index of 50 or less, when tested in accordance with ASTM E 84 or UL 723. Ducts shall be approved for installation in such an exhaust system. Where the products being exhausted are detrimental to the duct material, the ducts shall be constructed of alternative materi- als that are compatible with the exhaust. 2012 INTERNATIONAL MECHANICAL CODE® 57 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,iNb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS TABLE 510.8 MINIMUM DUCT THICKNESS DIAMETER OF MINIMUM NOMINAL THICKNESS Nonabrasive/ DUCT OR MAXIMUM SIDE Nonabrasive Abrasive Abrasive DIMENSION materials materials materials 0-8 inches 0.028 inch 0.034 inch 0.040 inch (No. 24 gage) (No. 22 gage) (No. 20 gage) 0.034 inch 0.040 inch 0.052 inch 9-18 inches (No. 22 gage) (No. 20 gage) (No. 18 gage) 19-30 inches 0.040 inch 0.052 inch 0.064 inch (No. 20 gage) (No. 18 gage) (No. 16 gage) Over 30 inches 0.052 inch 0.064 inch 0.079 inch (No. 18 gage) (No. 16 gage) (No. 14 gage) For SI 1 inch — 25 4 min 510.8.1 Duct joints. Ducts shall be made tight with lap joints having a minimum lap of 1 inch (25 mm). Joints used in ANSUSMACNA Round Industrial Duct Construc- tion Standards and ANSUSMACNA Rectangular Indus- trial Duct Construction Standards are also acceptable. 510.8.2 Clearance to combustibles. Ducts shall have a clearance to combustibles in accordance with Table 510.8.2. Exhaust gases having temperatures in excess of 600OF (316°C) shall be exhausted to a chimney in accor- dance with Section 511.2. TABLE 510.8.2 CLEARANCE TO COMBUSTIBLES TYPE OF EXHAUST OR TEMPERATURE OF EXHAUST (OF) CLEARANCE TO COMBUSTIBLES (inches) Less than 100 1 100-600 12 Flammable vapors 6 For SI 1 inch — 25 4 min, oC — [ff)- 32f 1 8 510.8.3 Explosion relief. Systems exhausting potentially explosive mixtures shall be protected with an approved explosion relief system or by an approved explosion pre- vention system designed and installed in accordance with NFPA 69. An explosion relief system shall be designed to minimize the structural and mechanical damage resulting from an explosion or deflagration within the exhaust sys- tem. An explosion prevention system shall be designed to prevent an explosion or deflagration from occurring. ports shall be constructed of noncombustible materials and shall be located on the exterior of the building or structure. A collector or separator shall not be located nearer than 10 feet (3048 mm) to combustible construction or to an unprotected wall or floor opening, unless the collector is provided with a metal vent pipe that extends above the highest part of any roof with a distance of 30 feet (9144 mm). Exceptions: 1. Collectors such as "Point of Use" collectors, close extraction weld fume collectors, spray fin- ishing booths, stationary grinding tables, sanding booths, and integrated or machine -mounted col- lectors shall be permitted to be installed indoors provided the installation is in accordance with the International Fire Code and NFPA 70. 2. Collectors in independent exhaust systems han- dling combustible dusts shall be permitted to be installed indoors provided that such collectors are installed in compliance with the International Fire Code and NFPA 70. 511.1.2 Discharge pipe. Discharge piping shall conform to the requirements for ducts, including clearances required for high -heat appliances, as contained in this code. A delivery pipe from a cyclone collector shall not convey refuse directly into the firebox of a boiler, furnace, dutch oven, refuse burner, incinerator or other appliance. 511.1.3 Conveying systems exhaust discharge. An exhaust system shall discharge to the outside of the build- ing either directly by flue or indirectly through the bin or vault into which the system discharges except where the contaminants have been removed. Exhaust system dis- charge shall be permitted to be recirculated provided that the solid particulate has been removed at a minimum effi- ciency of 99.9 percent at 10 microns (10.01 mm), vapor concentrations are less than 25 percent of the LFL, and approved equipment is used to monitor the vapor concen- tration. 511.1.4 Spark protection. The outlet of an open-air exhaust terminal shall be protected with an approved metal or other noncombustible screen to prevent the entry of sparks. 510.9 Supports. Ducts shall be supported at intervals not 511.1.5 Explosion relief vents. A safety or explosion exceeding 10 feet (3048 mm). Supports shall be constructed relief vent shall be provided on all systems that convey of noncombustible material. combustible refuse or stock of an explosive nature, in accordance with the requirements of the International SECTION 511 DUST, STOCK AND REFUSE CONVEYING SYSTEMS 511.1 Dust, stock and refuse conveying systems. Dust, stock and refuse conveying systems shall comply with the provisions of Section 510 and Sections 511.1.1 through 511.2. 511.1.1 Collectors and separators. Collectors and sepa- rators involving such systems as centrifugal separators, bag filter systems and similar devices, and associated sup- Building Code 511.1.5.1 Screens. Where a screen is installed in a safety relief vent, the screen shall be attached so as to permit ready release under the explosion pressure. 511.1.5.2 Hoods. The relief vent shall be provided with an approved noncombustible cowl or hood, or with a counterbalanced relief valve or cover arranged to pre- vent the escape of hazardous materials, gases or liquids. 511.2 Exhaust outlets. Outlets for exhaust that exceed 600°F (315°C) shall be designed as a chimney in accordance with Table 511.2. 58 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O[d6 Nombsx/00760/89 oc SIP SO, 20/90/47 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( riR [,FodUto,,by mythdparty.o,±, Yb�tocP,,UoFPd Single—oPIA mpymg Pod oNyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE FOR REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS TABLE 511.2 CONSTRUCTION, CLEARANCE AND TERMINATION REQUIREMENTS FOR SINGLE -WALL METAL CHIMNEYS MINIMUM THICKNESS TERMINATION CLEARANCE Combustible Above Above any part of construction Noncombustible roof building within (feet) (inches) construction F25 T50 Interior Exterior I CHIMNEYS Walls opening SERVING (inch) Lining (feet) 10 inst. I inst. Interior inst. Exterior inst. High -heat appliances 0.127 4'/," laid (Over 2,000'F)' (No. 10 MSG) on 4'/," bed 20 20 See Note c Low -heat appliances 0.127 3 2 18 6 (1,000'F normal operation) I (No.10MSG) none Up to 18" Up to 18" diameter, 2" Medium -heat appliances 0.127 dia.2'/z" Over 18" diameter, 4" (2,000°F maximum)s (No. 10 MSG) Over 18" 4'/," 10 10 36 24 On 4'/," bed For SI 1 inch- 25 4 mm, 1 foot- 304 8 mm, °C - [(°F)-32I/1 8 a Lining shall extend from bottom to top of outlet b Lining shall extend from 24 inches below connector to 24 feet above c Clearance shall be as specified by the design engineer and shall have sufficient clearance from buildings and structures to avoid overheating combustible materials (maximum 160'F) SECTION 512 SUBSLAB SOIL EXHAUST SYSTEMS 512.1 General. When a subslab soil exhaust system is pro- vided, the duct shall conform to the requirements of this sec- tion. 512.2 Materials. Subslab soil exhaust system duct material shall be air duct material listed and labeled to the require- ments of UL 181 for Class 0 air ducts, or any of the following piping materials that comply with the International Plumbing Code as building sanitary drainage and vent pipe: cast iron; galvanized steel; brass or copper pipe; copper tube of a weight not less than that of copper drainage tube, Type DWV; and plastic piping. 512.3 Grade. Exhaust system ducts shall not be trapped and shall have a minimum slope of one -eighth unit vertical in 12 units horizontal (1-percent slope). 512.4 Termination. Subslab soil exhaust system ducts shall extend through the roof and terminate at least 6 inches (152 mm) above the roof and at least 10 feet (3048 mm) from any operable openings or air intake. 512.5 Identification. Subslab soil exhaust ducts shall be per- manently identified within each floor level by means of a tag, stencil or other approved marking. SECTION 513 SMOKE CONTROL SYSTEMS [F] 513.1 Scope and purpose. This section applies to mechanical and passive smoke control systems that are required by the International Building Code or the Interna- tional Fire Code. The purpose of this section is to establish minimum requirements for the design, installation and accep- tance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or reloca- tion of occupants. These provisions are not intended for the preservation of contents, the timely restoration of operations, or for assistance in fire suppression or overhaul activities. Smoke control systems regulated by this section serve a dif- ferent purpose than the smoke- and heat -venting provisions found in Section 910 of the International Building Code or the International Fire Code. [F] 513.2 General design requirements. Buildings, struc- tures, or parts thereof required by the International Building Code or the International Fire Code to have a smoke control system or systems shall have such systems designed in accor- dance with the applicable requirements of Section 909 of the International Building Code and the generally accepted and well -established principles of engineering relevant to the design. The construction documents shall include sufficient information and detail to describe adequately the elements of the design necessary for the proper implementation of the smoke control systems. These documents shall be accompa- nied with sufficient information and analysis to demonstrate compliance with these provisions. [F] 513.3 Special inspection and test requirements. In addition to the ordinary inspection and test requirements which buildings, structures and parts thereof are required to undergo, smoke control systems subject to the provisions of Section 909 of the International Building Code shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its final installed condition. The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests. Such commissioning shall be in accordance with generally accepted engineering practice and, where possible, based on published standards for the particular testing involved. The special inspections and tests required by this section shall be conducted under the same terms as found in Section 1704 of the International Building Code. [F] 513.4 Analysis. A rational analysis supporting the types of smoke control systems to be employed, their methods of operation, the systems supporting them and the methods of construction to be utilized shall accompany the submitted 2012 INTERNATIONAL MECHANICAL CODE" 59 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O[d6 Nombsxlow6ole9 oc SIP V,2019o147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS construction documents and shall include, but not be limited to, the items indicated in Sections 513.4.1 through 513.4.6. [F] 513.4.1 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effects will not adversely interfere with the system's capa- bilities. In determining the maximum probable stack effects, altitude, elevation, weather history and interior temperatures shall be used. [F] 513.4.2 Temperature effect of fire. Buoyancy and expansion caused by the design fire in accordance with Section 513.9 shall be analyzed. The system shall be designed such that these effects do not adversely interfere with its capabilities. [F] 513.4.3 Wind effect. The design shall consider the adverse effects of wind. Such consideration shall be con- sistent with the wind -loading provisions of the Interna- tional Building Code. [F] 513.4.4 HVAC systems. The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis shall include all permutations of systems' status. The design shall consider the effects of fire on the HVAC systems. [F] 513.4.5 Climate. The design shall consider the effects of low temperatures on systems, property and occupants. Air inlets and exhausts shall be located so as to prevent snow or ice blockage. [F] 513.4.6 Duration of operation. All portions of active or passive smoke control systems shall be capable of con- tinued operation after detection of the fire event for a period of not less than either 20 minutes or 1.5 times the calculated egress time, whichever is less. [F] 513.5 Smoke barrier construction. Smoke barriers shall comply with the International Building Code. Smoke barriers shall be constructed and sealed to limit leakage areas exclu- sive of protected openings. The maximum allowable leakage area shall be the aggregate area calculated using the follow- ing leakage area ratios: 1. Walls: AIA,,,= 0.00100 2. Interior exit stairways and ramps and exit passageways: AIAw = 0.00035 3. Enclosed exit access stairways and ramps and all other shafts: AIAw=0.00150 4. Floors and roofs: A/AF= 0.00050 where: A = Total leakage area, square feet (m'). AF = Unit floor or roof area of barrier, square feet (m'). Aw = Unit wall area of barrier, square feet W) The leakage area ratios shown do not include openings due to doors, operable windows or similar gaps. These shall be included in calculating the total leakage area. [F] 513.5.1 Leakage area. Total leakage area of the bar- rier is the product of the smoke barrier gross area times the allowable leakage area ratio, plus the area of other open- ings such as gaps and operable windows. Compliance shall be determined by achieving the minimum air pres- sure difference across the barrier with the system in the smoke control mode for mechanical smoke control sys- tems. Passive smoke control systems tested using other approved means such as door fan testing shall be as approved by the code official. [F] 513.5.2 Opening protection. Openings in smoke bar- riers shall be protected by automatic -closing devices actu- ated by the required controls for the mechanical smoke control system. Door openings shall be protected by door assemblies complying with the requirements of the Inter- national Building Code for doors in smoke barriers. Exceptions: 1. Passive smoke control systems with automatic - closing devices actuated by spot -type smoke detectors listed for releasing service installed in accordance with the International Building Code. 2. Fixed openings between smoke zones which are protected utilizing the airflow method. 3. In Group I-2 where such doors are installed across corridors, a pair of opposite -swinging doors without a center mullion shall be installed having vision panels with approved fire -rated glazing materials in approved fire -rated frames, the area of which shall not exceed that tested. The doors shall be close -fitting within operational tol- erances, and shall not have undercuts, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and auto- matic -closing devices. Positive latching devices are not required. 4. Group I-3. 5. Openings between smoke zones with clear ceil- ing heights of 14 feet (4267 mm) or greater and bank down capacity of greater than 20 minutes as determined by the design fire size. [F] 513.5.2.1 Ducts and air transfer openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 250°F (121°C) smoke damper complying with the International Building Code. [F] 513.6 Pressurization method. The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke control zone of fire origin. [F] 513.6.1 Minimum pressure difference. The mini- mum pressure difference across a smoke barrier shall be 0.05-inch water gage (12.4 Pa) in fully sprinklered build- ings. In buildings permitted to be other than fully sprin- Idered, the smoke control system shall be designed to achieve pressure differences at least two times the maxi- mum calculated pressure difference produced by the design fire. [F] 513.6.2 Maximum pressure difference. The maxi- mum air pressure difference across a smoke barrier shall 60 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I IT od,,to—by POVOt put, I, ANb�to, P,,UoFsd Smglo mly, So, Pod oNyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS be determined by required door -opening or closing forces. The actual force required to open exit doors when the sys- tem is in the smoke control mode shall be in accordance with the International Building Code. Opening and clos- ing forces for other doors shall be determined by standard engineering methods for the resolution of forces and reac- tions. The calculated force to set a side -hinged, swinging door in motion shall be determined by: F=FE,+K(WAD)l2(FFa) (Equation5-2) where: A = Door area, square feet (m'). d = Distance from door handle to latch edge of door, feet (m). F = Total door opening force, pounds (N). FEY= Force required to overcome closing device, pounds (N). K = Coefficient 5.2 (1.0). W = Door width, feet (m). AP— Design pressure difference, inches (Pa) water gage. [F] 513.7 Airflow design method. When approved by the code official, smoke migration through openings fixed in a permanently open position, which are located between smoke control zones by the use of the airflow method, shall be per- mitted. The design airflows shall be in accordance with this section. Airflow shall be directed to limit smoke migration from the fire zone. The geometry of openings shall be consid- ered to prevent flow reversal from turbulent effects. [F] 513.7.1 Velocity. The minimum average velocity through a fixed opening shall not be less than: v= 217.2 [h(Tf- T l(Tf+ 460)]')' (Equation 5-3) For SI: v= 119.9 [h(Tf- TlITf]')' where: H = Height of opening, feet (m). Tf = Temperature of smoke, 'F (K). T = Temperature of ambient air, 'F (K). by = Air velocity, feet per minute (m/minute). [F] 513.7.2 Prohibited conditions. This method shall not be employed where either the quantity of air or the veloc- ity of the airflow will adversely affect other portions of the smoke control system, unduly intensify the fire, disrupt plume dynamics or interfere with exiting. In no case shall airflow toward the fire exceed 200 feet per minute (1.02 m/s). Where the formula in Section 513.7.1 requires air- flow to exceed this limit, the airflow method shall not be used. [F] 513.8 Exhaust method. When approved by the building official, mechanical smoke control for large enclosed vol- umes, such as in atriums or malls, shall be permitted to utilize the exhaust method. Smoke control systems using the exhaust method shall be designed in accordance with NFPA 9213. [F] 513.8.1 Exhaust rate. The height of the lowest hori- zontal surface of the accumulating smoke layer shall be maintained at least 6 feet (1829 mm) above any walking surface which forms a portion of a required egress system within the smoke zone. [F] 513.9 Design fire. The design fire shall be based on a rational analysis performed by the registered design profes- sional and approved by the code official. The design fire shall be based on the analysis in accordance with Section 513.4 and this section. [F] 513.9.1 Factors considered. The engineering analysis shall include the characteristics of the fuel, fuel load, effects included by the fire and whether the fire is likely to be steady or unsteady. [F] 513.9.2 Design fire fuel. Determination of the design fire shall include consideration of the type of fuel, fuel spacing and configuration. [F] 513.9.3 Heat -release assumptions. The analysis shall make use of the best available data from approved sources and shall not be based on excessively stringent limitations of combustible material. [F] 513.9.4 Sprinkler effectiveness assumptions. A doc- umented engineering analysis shall be provided for condi- tions that assume fire growth is halted at the time of sprinkler activation. [F] 513.10 Equipment Equipment such as, but not limited to, fans, ducts, automatic dampers and balance dampers shall be suitable for their intended use, suitable for the probable exposure temperatures that the rational analysis indicates, and as approved by the code official. [F] 513.10.1 Exhaust fans. Components of exhaust fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise shall be computed by: T = (Qlmr) + (T where: (Equation 5-4) c = Specific heat of smoke at smoke -layer temperature, Btu/lb'F (kj/kg. K). m = Exhaust rate, pounds per second (kg/s). Q, = Convective heat output of fire, Btu/s (kW). T = Ambient temperature, AT (K). T = Smoke temperature, AT (K). Exception: Reduced T as calculated based on the assurance of adequate dilution air. [F] 513.10.2 Ducts. Duct materials and joints shall be capable of withstanding the probable temperatures and pressures to which they are exposed as determined in accordance with Section 513.10.1. Ducts shall be con- structed and supported in accordance with Chapter 6. Ducts shall be leak tested to 1.5 times the maximum design pressure in accordance with nationally accepted practices. Measured leakage shall not exceed 5 percent of 2012 INTERNATIONAL MECHANICAL CODE® 61 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx 100760189 oc Sep so.2.o19o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS design flow. Results of such testing shall be a part of the documentation procedure. Ducts shall be supported directly from fire -resistance -rated structural elements of the building by substantial, noncombustible supports. Exception: Flexible connections, for the purpose of vibration isolation, that are constructed of approved fire -resistance -rated materials. [F] 513.10.3 Equipment, inlets and outlets. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard. Outdoor air inlets shall be located so as to minimize the potential for intro- ducing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard. [F] 513.10.4 Automatic dampers. Automatic dampers, regardless of the purpose for which they are installed within the smoke control system, shall be listed and con- form to the requirements of approved recognized stan- dards. [F] 513.10.5 Fans. In addition to other requirements, belt - driven fans shall have 1.5 times the number of belts required for the design duty with the minimum number of belts being two. Fans shall be selected for stable perfor- mance based on normal temperature and, where applica- ble, elevated temperature. Calculations and manufacturer's fan curves shall be part of the documentation procedures. Fans shall be supported and restrained by noncombustible devices in accordance with the structural design require- ments of the International Building Code. Motors driving fans shall not be operating beyond their nameplate horse- power (kilowatts) as determined from measurement of actual current draw. Motors driving fans shall have a min- imum service factor of 1.15. [F] 513.11 Power systems. The smoke control system shall be supplied with two sources of power. Primary power shall be the normal building power systems. Secondary power shall be from an approved standby source complying with Chapter 27 of the International Building Code. The standby power source and its transfer switches shall be in a room sep- arate from the normal power transformers and switch gear and ventilated directly to and from the exterior. The room shall be enclosed with not less than 1-hour fire -resistance - rated fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the Interna- tional Building Code, or both. Transfer to full standby power shall be automatic and within 60 seconds of failure of the pri- mary power. The systems shall comply with NFPA 70. [F] 513.11.1 Power sources and power surges. Elements of the smoke management system relying on volatile memories or the like shall be supplied with uninterruptible power sources of sufficient duration to span 15-minute pri- mary power interruption. Elements of the smoke manage- ment system susceptible to power surges shall be suitably protected by conditioners, suppressors or other approved means. [F] 513.12 Detection and control systems. Fire detection systems providing control input or output signals to mechani- cal smoke control systems or elements thereof shall comply with NFPA 72 and the requirements of Chapter 9 of the Inter- national Building Code or the International Fire Code. Such I systems shall be equipped with a control unit complying with UL 864 and listed as smoke control equipment. Control systems for mechanical smoke control systems shall include provisions for verification. Verification shall include positive confirmation of actuation, testing, manual override, the presence of power downstream of all discon- nects and, through a preprogrammed weekly test sequence report, abnormal conditions audibly, visually and by printed report. [F] 513.12.1 Wiring. In addition to meeting the require- ments of NBPA 70, all wiring, regardless of voltage, shall be fully enclosed within continuous raceways. [F] 513.12.2 Activation. Smoke control systems shall be activated in accordance with the International Building Code or the International Fire Code. [F] 513.12.3 Automatic control. Where completely auto- matic control is required or used, the automatic control sequences shall be initiated from an appropriately zoned automatic sprinkler system complying with Section 903.3.1.1 of the International Fire Code, from manual controls that are readily accessible to the fire department, and any smoke detectors required by engineering analysis. [F] 513.13 Control -air tubing. Control -air tubing shall be of sufficient size to meet the required response times. Tubing shall be flushed clean and dry prior to final connections. Tub- ing shall be adequately supported and protected from dam- age. Tubing passing through concrete or masonry shall be sleeved and protected from abrasion and electrolytic action. [F] 513.13.1 Materials. Control -air tubing shall be hard - drawn copper, Type L, ACR in accordance with ASTM B 42, ASTM B 43, ASTM B 68, ASTM B 88, ASTM B 251 and ASTM B 280. Fittings shall be wrought copper or brass, solder type in accordance with ASME B 16.18 or ASME B 16.22. Changes in direction shall be made with appropriate tool bends. Brass compression -type fittings shall be used at final connection to devices; other joints shall be brazed using a BCuP5 brazing alloy with solidus above 1,100°F (593°C) and liquids below 1,500°F (816°C). Brazing flux shall be used on copper -to -brass joints only. Exception: Nonmetallic tubing used within control panels and at the final connection to devices provided all of the following conditions are met: 1. Tubing shall comply with the requirements of I Section 602.2.1.3. 2. Tubing and connected device shall be completely enclosed within a galvanized or paint -grade steel enclosure having a minimum thickness of 0.0296 inch (0.7534 mm) (No. 22 gage). Entry to the enclosure shall be by copper tubing with a protec- 62 2012 INTERNATIONAL MECHANICAL CODE® Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( [,Fod Uto,,by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EXHAUST SYSTEMS live grommet of Neoprene or Teflon or by suit- able brass compression to male barbed adapter. 3. Tubing shall be identified by appropriately docu- mented coding. 4. Tubing shall be neatly tied and supported within the enclosure. Tubing bridging cabinets and doors or moveable devices shall be of sufficient length to avoid tension and excessive stress. Tub- ing shall be protected against abrasion. Tubing serving devices on doors shall be fastened along hinges. [F] 513.13.2 Isolation from other functions. Control tub- ing serving other than smoke control functions shall be isolated by automatic isolation valves or shall be an inde- pendent system. [F] 513.13.3 Testing. Test control -air tubing at three times the operating pressure for not less than 30 minutes without any noticeable loss in gauge pressure prior to final connec- tion to devices. [F] 513.14 Marking and identification. The detection and control systems shall be clearly marked at all junctions, accesses and terminations. [F] 513.15 Control diagrams. Identical control diagrams shall be provided and maintained as required by the Interna- tional Fire Code. [F] 513.16 Fire fighter's smoke control panel. A fire fighter's smoke control panel for fire department emergency response purposes only shall be provided in accordance with the International Fire Code. [F] 513.17 System response time. Smoke control system activation shall comply with the International Fire Code. [F] 513.18 Acceptance testing. Devices, equipment, compo- nents and sequences shall be tested in accordance with the International Fire Code. [F] 513.19 System acceptance. Acceptance of the smoke control system shall be in accordance with the International Fire Code. SECTION 514 ENERGY RECOVERY VENTILATION SYSTEMS 514.1 General. Energy recovery ventilation systems shall be installed in accordance with this section. Where required for purposes of energy conservation, energy recovery ventilation systems shall also comply with the International Energy Conservation Code. Ducted heat recovery ventilators shall be listed and labeled in accordance with UL 1812. Nonducted heat recovery ventilators shall be listed and labeled in accor- dance with UL 1815. 514.2 Prohibited applications. Energy recovery ventilation systems shall not be used in the following systems: 1. Hazardous exhaust systems covered in Section 510. 2. Dust, stock and refuse systems that convey explosive or flammable vapors, fumes or dust. 3. Smoke control systems covered in Section 513. 4. Commercial kitchen exhaust systems serving Type I and Type II hoods. 5. Clothes dryer exhaust systems covered in Section 504. 514.3 Access. A means of access shall be provided to the heat exchanger and other components of the system as required for service, maintenance, repair or replacement. 514.4 Recirculated air. Air conveyed within energy recov- ery systems shall not be considered as recirculated air where the energy recovery ventilation system is constructed to limit cross -leakage between air streams to less than 10 percent of the total airflow design capacity. 2012 INTERNATIONAL MECHANICAL CODE® 63 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlowcole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,iNb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 64 2012 INTERNATIONAL MECHANICAL CODE® 17i''' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc SIP SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( �ep�odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mp,YEmdoehuodmg plokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as oth- erwise specified in Chapters 5 and 7. Exception: Ducts discharging combustible material directly into any combustion chamber shall conform to the requirements of NITA 82. [B] 601.2 Air movement in egress elements. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts. Exceptions: Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor clos- ets, shall be permitted, provided that each such cor- ridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor. 2. Where located within a dwelling unit, the use of cor- ridors for conveying return air shall not be prohib- ited. 3. Where located within tenant spaces of 1,000 square feet (93 m') or less in area, use of corridors for con- veying return air is permitted. 4. Incidental air movement from pressurized rooms within health care facilities, provided that the corri- dor is not the primary source of supply or return to the room. [B] 601.2.1 Corridor ceiling. Use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum is permitted for one or more of the fol- lowing conditions: 1. The corridor is not required to be of fire -resistance - rated construction; 2. The corridor is separated from the plenum by fire - resistance -rated construction; 3. The air -handling system serving the corridor is shut down upon activation of the air -handling unit smoke detectors required by this code; 4. The air -handling system serving the corridor is shut down upon detection of sprinkler waterflow where the building is equipped throughout with an auto- matic sprinkler system; or 5. The space between the corridor ceiling and the floor or roof structure above the corridor is used as a com- ponent of an approved engineered smoke control system. [B] 601.3 Exits. Equipment and ductwork for exit enclosure ventilation shall comply with one of the following items: 1. Such equipmentand ductwork shall be located exterior to the building and shall be directly connected to the exit enclosure by ductwork enclosed in construction as required by the International Building Code for shafts. 2. Where such equipment and ductwork is located within the exit enclosure, the intake air shall be taken directly from the outdoors and the exhaust air shall be dis- charged directly to the outdoors, or such air shall be conveyed through ducts enclosed in construction as required by the International Building Code for shafts. 3. Where located within the building, such equipment and ductwork shall be separated from the remainder of the building, including other mechanical equipment, with construction as required by the International Building Code for shafts. In each case, openings into fire -resistance -rated construc- tion shall be limited to those needed for maintenance and operation and shall be protected by self closing fire -resis- tance -rated devices in accordance with the International Building Code for enclosure wall opening protectives. Exit enclosure ventilation systems shall be independent of other building ventilation systems. 601.4 Contamination prevention. Exhaust ducts under posi- tive pressure, chimneys and vents shall not extend into or pass through ducts or plenums. Exceptions 1. Exhaust systems located in ceiling return air ple- nums over spaces that are permitted to have 10 per- cent recirculation in accordance with Section 403.2.1, Item 4. The exhaust duct joints, seams and connections shall comply with Section 603.9. 2. This section shall not apply to chimneys and vents that pass through plenums where such venting sys- tems comply with one of the following require- ments: 2.1. The venting system shall be listed for posi- tive pressure applications and shall be sealed in accordance with the vent manu- facturer's instructions. 2.2. The venting system shall be installed such that fittings and joints between sections are not installed in the above ceiling space. 2.3. The venting system shall be installed in a conduit or enclosure with sealed joints sep- arating the interior of the conduit or enclo- sure from the ceiling space. 2012 INTERNATIONAL MECHANICAL CODE® 65 I II I C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS SECTION 602 PLENUMS 602.1 General. Supply, return, exhaust, relief and ventilation air plenums shall be limited to uninhabited crawl spaces, areas above a ceiling or below the floor, attic spaces and mechanical equipmentrooms. Plenums shall be limited to one fire area. Fuel -fired appliances shall not be installed within a plenum. 602.2 Construction. Plenum enclosures shall be constructed of materials permitted for the type of construction classifica- tion of the building. The use of gypsum boards to form plenums shall be lim- ited to systems where the air temperatures do not exceed 125°F (52°C) and the building and mechanical system design conditions are such that the gypsum board surface tempera- ture will be maintained above the airstream dew -point tem- perature. Air plenums formed by gypsum boards shall not be incorporated in air -handling systems utilizing evaporative coolers. 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within ple- nums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke -developed index of not more than 50 when tested in accordance with ASTM E 84 or UL 723. Exceptions: 1. Rigid and flexible ducts and connectors shall conform to Section 603. 2. Duct coverings, linings, tape and connectors shall conform to Sections 603 and 604. 3. This section shall not apply to materials exposed within plenums in one- and two-family dwell- ings. 4. This section shall not apply to smoke detectors. 5. Combustible materials fully enclosed within one of the following: 5.1. Continuous noncombustible raceways or enclosures. 5.2. Approved gypsum board assemblies. 5.3. Materials listed and labeled for installa- tion within a plenum. 6. Materials in Group H, Division 5 fabrication areas and the areas above and below the fabrica- tion area that share a common air recirculation path with the fabrication area. 602.2.1.1 Wiring. Combustible electrical wires and cables and optical fiber cables exposed within a plenum shall be listed as having a maximum peak optical den- sity of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 feet (1524 mm) or less when tested in accordance with NFPA 262 or shall be installed in metal raceways or metal sheathed cable. Combustible optical fiber and communication raceways exposed within a plenum shall be listed as having a maximum peak optical den- sity of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 feet (1524 mm) or less when tested in accordance with ANSUUL 2024. Only plenum -rated wires and cables shall be installed in plenum -rated raceways. Electrical wires and cables, optical fiber cables and raceways addressed in this section shall be listed and labeled and shall be installed in accordance with NFPA 70. 602.2.1.2 Fire sprinkler piping. Plastic fire sprinkler piping exposed within a plenum shall be used only in wet pipe systems and shall have a peak optical density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread of not greater than 5 feet (1524 mm) when tested in accordance with UL 1887. Piping shall be listed and labeled. 602.2.1.3 Pneumatic tubing. Combustible pneumatic tubing exposed within a plenum shall have a peak opti- cal density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread of not greater than 5 feet (1524 mm) when tested in accor- dance with UL 1820. Combustible pneumatic tubing shall be listed and labeled. 602.2.1.4 Electrical equipment in plenums. Electrical equipment exposed within a plenum shall comply with Sections 602.2.1.4.1 and 602.2.1.4.2. 602.2.1.4.1 Equipment in metallic enclosures. Electrical equipment with metallic enclosures exposed within a plenum shall be permitted. 602.2.1.4.2 Equipment in combustible enclosures. Electrical equipment with combustible enclosures exposed within a plenum shall be listed and labeled for such use in accordance with UL 2043. 602.2.1.5 Foam plastic insulation. Foam plastic insu- lation used as interior wall or ceiling finish, or as inte- rior trim, in plenums shall exhibit a flame spread index of 75 or less and a smoke -developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723 and shall also comply with one or more of Sections 602.2.1.5.1, 602.2.1.5.2 and 602.2.1.5.3. 602.2.1.5.1 Separation required. The foam plastic insulation shall be separated from the plenum by a thermal barrier complying with Section 2603.4 of the International Building Code and shall exhibit a flame spread index of 75 or less and a smoke -devel- oped index of 450 or less when tested in accordance with ASTM E 84 or UL 723 at the thickness and density intended for use. 602.2.1.5.2 Approval. The foam plastic insulation shall exhibit a flame spread index of 25 or less and a smoke -developed index of 50 or less when tested in accordance with ASTM E 84 or UL 723 at the thick- ness and density intended for use and shall meet the acceptance criteria of Section 803.1.2 of the Interna- tional Building Code when tested in accordance with NFPA 286. 66 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( odUto.. by POVOtput, I,ANb�to,P,,UoFsd Single—mly mpymg Pod oNyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS The foam plastic insulation shall be approved based on tests conducted in accordance with Section 2603.10 of the International Building Code. 602.2.1.5.3 Covering. The foam plastic insulation shall be covered by corrosion -resistant steel having a base metal thickness of not less than 0.0160 inch (0.4 mm) and shall exhibit a flame spread index of 75 or less and a smoke -developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723 at the thickness and density intended for use. 602.3 Stud cavity and joist space plenums. Stud wall cavi- ties and the spaces between solid floor joists to be utilized as air plenums shall comply with the following conditions: 1. Such cavities or spaces shall not be utilized as a plenum for supply air. 2. Such cavities or spaces shall not be part of a required fire -resistance -rated assembly. 3. Stud wall cavities shall not convey air from more than one floor level. 4. Stud wall cavities and joist space plenums shall comply with the floor penetration protection requirements of the International Building Code. 5. Stud wall cavities and joist space plenums shall be iso- lated from adjacent concealed spaces by approved fire - blocking as required in the International Building Code. 6. Studwall cavities in the outside walls of building enve- lope assemblies shall not be utilized as air plenums. [B] 602.4 Flood hazard. For structures located in flood haz- ard areas, plenum spaces shall be located above the elevation required by Section 1612 of the International Building Code for utilities and attendant equipment or shall be designed and constructed to prevent water from entering or accumulating within the plenum spaces during floods up to such elevation. If the plenum spaces are located below the elevation required by Section 1612 of the International Building Code for utili- ties and attendant equipment, they shall be capable of resist- ing hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to such elevation. SECTION 603 DUCT CONSTRUCTION AND INSTALLATION 603.1 General. An air distribution system shall be designed and installed to supply the required distribution of air. The installation of an air distribution system shall not affect the fire protection requirements specified in the International Building Code. Ducts shall be constructed, braced, reinforced and installed to provide structural strength and durability. 603.2 Duct sizing. Ducts installed within a single dwelling unit shall be sized in accordance with ACCA Manual D or other approved methods. Ducts installed within all other buildings shall be sized in accordance with the ASHRAE Handbook of Fundamentals or other equivalent computation procedure. 603.3 Duct classification. Ducts shall be classified based on the maximum operating pressure of the duct at pressures of positive or negative 0.5, 1.0, 2.0, 3.0, 4.0, 6.0 or 10.0 inches (1 inch w.c. = 248.7 Pa) of water column. The pressure classi- fication of ducts shall equal or exceed the design pressure of the air distribution in which the ducts are utilized. 603.4 Metallic ducts. All metallic ducts shall be constructed as specified in the SMACNA HFACDuct Construction Stan- dards -Metal and Flexible. Exception: Ducts installed within single dwelling units shall have a minimum thickness as specified in Table 603.4. 603.4.1 Minimum fasteners. Round metallic ducts shall be mechanically fastened by means of at least three sheet metal screws or rivets spaced equally around the joint. Exception: Where a duct connection is made that is partially inaccessible, three screws or rivets shall be equally spaced on the exposed portion so as to prevent a hinge effect. 603.5 Nonmetallic ducts. Nonmetallic ducts shall be con- structed with Class 0 or Class 1 duct material and shall com- ply with UL 181. Fibrous duct construction shall conform to the SMACNA Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct Construction Standards. The air temperature within nonmetallic ducts shall not exceed 250'F (121 °C). 603.5.1 Gypsum ducts. The use of gypsum boards to form air shafts (ducts) shall be limited to return air sys- tems where the air temperatures do not exceed 125'F TABLE 603.4 DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESSES FOR SINGLE DWELLING UNITS GALVANIZED ALUMINUM Minimum thickness (in.) Equivalent galvanized gage no. DUCT SIZE MINIMUM THICKNESS (in.) Round ducts and enclosed rectangular ducts 14 inches or less 0.0157 28 0.0175 16 and 18 inches 0.0187 26 0.018 20 inches and over 0.0236 24 0.023 Exposed rectangular ducts 14 inches or less 0.0157 28 0.0175 Over 14 inches' 0.0187 26 0.018 For SI 1 inch — 25 4 min, 1 inch Evatergage — 249 Pa a For duct gages and reinforcement requirements at static pressures of I/y inch, 1-inch and 2-inch Ev g , SMACNA HFAC Duct Construction Standards, Tables 2-1, 2-2 and 2-3, shall apply 2012 INTERNATIONAL MECHANICAL CODE® 67 I I I I Copyngbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 1007601e9 oc Sep so.2.o19 o 147 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,oddtoa oAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg Pod-Pyoc-gFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS (52°C) and the gypsum board surface temperature is main- tained above the airstream dew -point temperature. Air ducts formed by gypsum boards shall not be incorporated in air -handling systems utilizing evaporative coolers. 603.6 Flexible air ducts and flexible air connectors. Flexi- ble air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1, 603.6.1.1, 603.6.3 and 603.6.4. Flexi- ble air connectors, both metallic and nonmetallic, shall com- ply with Sections 603.6.2 through 603.6.4. 603.6.1 Flexible air ducts. Flexible air ducts, both metal- lic and nonmetallic, shall be tested in accordance with UL 181. Such ducts shall be listed and labeled as Class 0 or Class 1 flexible air ducts and shall be installed in accor- dance with Section 304.1. 603.6.1.1 Duct length. Flexible air ducts shall not be limited in length. 603.6.2 Flexible air connectors. Flexible air connectors, both metallic and nonmetallic, shall be tested in accor- dance with UL 181. Such connectors shall be listed and labeled as Class 0 or Class 1 flexible air connectors and shall be installed in accordance with Section 304.1. 603.6.2.1 Connector length. Flexible air connectors shall be limited in length to 14 feet (4267 min). 603.6.2.2 Connector penetration limitations. Flexible air connectors shall not pass through any wall, floor or ceiling. 603.6.3 Air temperature. The design temperature of air to be conveyed in flexible air ducts and flexible air con- nectors shall be less than 250°F (121°C). 603.6.4 Flexible air duct and air connector clearance. Flexible air ducts and air connectors shall be installed with a minimum clearance to an appliance as specified in the appliance manufacturer's installation instructions. 603.7 Rigid duct penetrations. Duct system penetrations of walls, floors, ceilings and roofs and air transfer openings in such building components shall be protected as required by Section 607. Ducts in a private garage that penetrate a wall or ceiling that separates a dwelling from a private garage shall be continuous, shall be constructed of sheet steel having a thickness of not less than 0.0187 inch (0.4712 mm) (No.26 gage) and shall not have openings into the garage. Fire and smoke dampers are not required in such ducts passing through the wall or ceiling separating a dwelling from a pri- vate garage except where required by Chapter 7 of the Inter- national Building Code. 603.8 Underground ducts. Ducts shall be approved for underground installation. Metallic ducts not having an approved protective coating shall be completely encased in a minimum of 2 inches (51 mm) of concrete. 603.8.1 Slope. Ducts shall have a minimum slope of V' inch per foot (10.4 mm/m) to allow drainage to a point provided with access. 603.8.2 Sealing. Ducts shall be sealed and secured prior to pouring the concrete encasement. 603.8.3 Plastic ducts and fittings. Plastic ducts shall be constructed of PVC having a minimum pipe stiffness of 8 psi (55 kPa) at 5-percent deflection when tested in accor- dance with ASTM D 2412. Plastic duct fittings shall be constructed of either PVC or high -density polyethylene. Plastic duct and fittings shall be utilized in underground installations only. The maximum design temperature for systems utilizing plastic duct and fittings shall be 150°F (66°C). 603.9 Joints, seams and connections. All longitudinal and transverse joints, seams and connections in metallic and non- metallic ducts shall be constructed as specified in SMACNA HFAC Duct Construction StandardsMetaland Flexible and NAIMA Fibrous Glass Duct Construction Standards. All joints, longitudinal and transverse seams and connections in ductwork shall be securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic -plus -embedded -fabric systems, liquid sealants or tapes. Closure systems used to seal ductwork listed and labeled in accordance with UL 181A shall be marked "181A-P" for pressure -sensitive tape, "181 A-M" for mastic or "181 A -IT' for heat -sensitive tape. Clo- sure systems used to seal flexible air ducts and flexible air connectors shall comply with UL 181 B and shall be marked "181 B-17V for pressure -sensitive tape or "181 B-M" for mas- tic. Duct connections to flanges of air distribution system equipment shall be sealed and mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181B and shall be marked "181 B-C." Closure systems used to seal metal ductwork shall be installed in accordance with the manufacturer's installa- tion instructions. Unlisted duct tape is not permitted as a seal- I ant on any duct. Exception: Continuously welded and locking -type longi- tudinal joints and seams in ducts operating at static pres- sures less than 2 inches of water column (500 Pa) pressure classification shall not require additional closure systems. 603.10 Supports. Ducts shall be supported at intervals not to exceed 12 feet (3658 mm) and shall be in accordance with SMACNA HFAC Duct Construction StandardsMetaland Flexible. Flexible and other factory -made ducts shall be sup- ported in accordance with the manufacturer's instructions. 603.11 Furnace connections. Ducts connecting to a furnace shall have a clearance to combustibles in accordance with the furnace manufacturer's installation instructions. 603.12 Condensation. Provisions shall be made to prevent the formation of condensation on the exterior of any duct. [B] 603.13 Flood hazard areas. For structures in flood haz- ard areas, ducts shall be located above the elevation required by Section 1612 of the International Building Code for utili- ties and attendant equipment or shall be designed and con- structed to prevent water from entering or accumulating within the ducts during floods up to such elevation. If the ducts are located below the elevation required by Section 1612 of the International Building Code for utilities and attendant equipment, the ducts shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to such elevation. 68 2012 INTERNATIONAL MECHANICAL CODE® C,Ty,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( [,Fod,... by POVOtpN PLOI,±bs �to,P,,UoFd Single—oPIA PTymg PodoNyodpl mgokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE PEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS 603.14 Location. Ducts shall not be installed in or within 4 inches (102 mm) of the earth, except where such ducts com- ply with Section 603.8. 603.15 Mechanical protection. Ducts installed in locations where they are exposed to mechanical damage by vehicles or from other causes shall be protected by approved barriers. 603.16 Weather protection. All ducts including linings, cov- erings and vibration isolation connectors installed on the exterior of the building shall be protected against the ele- ments. 603.17 Air dispersion systems. Air dispersion systems shall: 1. Be installed entirely in exposed locations. 2. Be utilized in systems under positive pressure. 3. Not pass through or penetrate fire -resistant -rated con- struction. 4. Be listed and labeled in compliance with UL 2518. 603.18 Registers, grilles and diffusers. Duct registers, grilles and diffusers shall be installed in accordance with the manufacturer's installation instructions. Volume dampers or other means of supply air adjustment shall be provided in the branch ducts or at each individual duct register, grille or dif- fuser. Each volume damper or other means of supply air adjustment used in balancing shall be provided with access. 603.18.1 Floor registers. Floor registers shall resist, with- out structural failure, a 200-pound (90.8 kg) concentrated load on a 2-inch-diameter (51 mm) disc applied to the most critical area of the exposed face. 603.18.2 Prohibited locations. Diffusers, registers and grilles shall be prohibited in the floor or its upward exten- sion within toilet and bathing rooms required by the Inter- national Building Code to have smooth, hard, nonabsorbent surfaces. Exception: Dwelling units. SECTION 604 INSULATION 604.1 General. Duct insulation shall conform to the require- ments of Sections 604.2 through 604.13 and the International Energy Conservation Code. 604.2 Surface temperature. Ducts that operate at tempera- tures exceeding 120°F (49°C) shall have sufficient thermal insulation to limit the exposed surface temperature to 120OF (49°C). 604.3 Coverings and linings. Coverings and linings, includ- ing adhesives when used, shall have a flame spread index not more than 25 and a smoke -developed index not more than 50, when tested in accordance with ASTM E 84 or UL 723, using the specimen preparation and mounting procedures of ASTM E 2231. Duct coverings and linings shall not flame, glow, smolder or smoke when tested in accordance with ASTM C 411 at the temperature to which they are exposed in service. The test temperature shall not fall below 250OF (121 °C). Cov- erings and linings shall be listed and labeled. 604.4 Foam plastic insulation. Foam plastic used as duct coverings and linings shall conform to the requirements of Section 604. 604.5 Appliance insulation. Listed and labeled appliances that are internally insulated shall be considered as conform- ing to the requirements of Section 604. 604.6 Penetration of assemblies. Duct coverings shall not penetrate a wall or floor required to have a fire -resistance rat- ing or required to be fireblocked. 604.7 Identification. External duct insulation, except spray polyurethane foam, and factory -insulated flexible duct shall be legibly printed or identified at intervals not greater than 36 inches (914 mm) with the name of the manufacturer, the ther- mal resistance R-value at the specified installed thickness and the flame spread and smoke -developed indexes of the com- posite materials. All duct insulation product R-values shall be based on insulation only, excluding air films, vapor retarders or other duct components, and shall be based on tested C-val- ues at 75°F (24°C) mean temperature at the installed thick- ness, in accordance with recognized industry procedures. The installed thickness of duct insulation used to determine its R- value shall be determined as follows: 1. For duct board, duct liner and factory -made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used. 2. For duct wrap, the installed thickness shall be assumed to be 75 percent (25 percent compression) of nominal thickness. 3. For factory -made flexible air ducts, the installed thick- ness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two. 4. For spray polyurethane foam, the aged R-value per inch, measured in accordance with recognized industry standards, shall be provided to the customer in writing at the time of foam application. 604.8 Lining installation. Linings shall be interrupted at the area of operation of a fire damper and at a minimum of 6 inches (152 mm) upstream of and 6 inches (152 mm) down- stream of electric -resistance and fuel -burning heaters in a duct system. Metal nosings or sleeves shall be installed over exposed duct liner edges that face opposite the direction of airflow. 604.9 Thermal continuity. Where a duct liner has been interrupted, a duct covering of equal thermal performance shall be installed. 604.10 Service openings. Service openings shall not be con- cealed by duct coverings unless the exact location of the opening is properly identified. 604.11 Vapor retarders. Where ducts used for cooling are externally insulated, the insulation shall be covered with a vapor retarder having a maximum permeance of 0.05 perm [2.87 ng/(Pa . s . m')] or aluminum foil having a minimum thickness of 2 mils (0.051 mm). Insulations having a perme- ance of 0.05 perm [2.87 ng/(Pa . s . m' )] or less shall not be 2012 INTERNATIONAL MECHANICAL CODE® 69 I II I Copy,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P-dby().(-)O,d,,Nombsxlowcole9 oc SIP V,2019o147 PM(PDT)p-Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single -oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS required to be covered. All joints and seams shall be sealed to maintain the continuity of the vapor retarder. 604.12 Weatherproof barriers. Insulated exterior ducts shall be protected with an approved weatherproof barrier. 604.13 Internal insulation. Materials used as internal insula- tion and exposed to the airstream in ducts shall be shown to be durable when tested in accordance with UL 181. Exposed internal insulation that is not impermeable to water shall not be used to line ducts or plenums from the exit of a cooling coil to the downstream end of the drain pan. SECTION 605 AIR FILTERS 605.1 General. Heating and air-conditioning systems of the central type shall be provided with approved air filters. Filters shall be installed in the return air system, upstream from any heat exchanger or coil, in an approved convenient location. Liquid adhesive coatings used on filters shall have a flash point not lower than 325°F (163°O). 605.2 Approval. Media -type and electrostatic -type air filters shall be listed and labeled. Media -type air filters shall comply with UL 900. High efficiency particulate air filters shall com- ply with UL 586. Electrostatic -type air filters shall comply with UL 867. Air filters utilized within dwelling units shall be designed for the intended application and shall not be required to be listed and labeled. 605.3 Airflow over the filter. Ducts shall be constructed to allow an even distribution of air over the entire filter. SECTION 606 SMOKE DETECTION SYSTEMS CONTROL 606.1 Controls required. Air distribution systems shall be equipped with smoke detectors listed and labeled for installa- tion in air distribution systems, as required by this section. Duct smoke detectors shall comply with UL 268A. Other smoke detectors shall comply with UL 268. 606.2 Where required. Smoke detectors shall be installed where indicated in Sections 606.2.1 through 606.2.3. Exception: Smoke detectors shall not be required where air distribution systems are incapable of spreading smoke beyond the enclosing walls, floors and ceilings of the room or space in which the smoke is generated. 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm (0.9 m3/s), in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. 606.2.2 Common supply and return air systems. Where multiple air -handling systems share common supply or return air ducts or plenums with a combined design capac- ity greater than 2,000 cfm (0.9 m3/s), the return air system shall be provided with smoke detectors in accordance with Section 606.2.1. Exception: Individual smoke detectors shall not be required for each fan -powered terminal unit, provided that such units do not have an individual design capac- ity greater than 2,000 cfm (0.9 m3/s) and will be shut down by activation of one of the following: 1. Smoke detectors required by Sections 606.2.1 and 606.2.3. 2. An approved area smoke detector system located in the return air plenum serving such units. 3. An area smoke detector system as prescribed in the exception to Section 606.2.1. In all cases, the smoke detectors shall comply with Sec- tions 606.4 and 606.4.1. 606.2.3 Return air risers. Where return air risers serve two or more stories and serve any portion of a return air system having a design capacity greater than 15,000 cfm (7.1 m3/s), smoke detectors shall be installed at each story. Such smoke detectors shall be located upstream of the connection between the return air riser and any air ducts or plenums. [F] 606.3 Installation. Smoke detectors required by this sec- tion shall be installed in accordance with NFPA 72. The required smoke detectors shall be installed to monitor the entire airflow conveyed by the system including return air and exhaust or relief air. Access shall be provided to smoke detectors for inspection and maintenance. [F] 606.4 Controls operation. Upon activation, the smoke detectors shall shut down all operational capabilities of the air distribution system in accordance with the listing and label- ing of appliances used in the system. Air distribution systems that are part of a smoke control system shall switch to the smoke control mode upon activation of a detector. [F] 606.4.1 Supervision. The duct smoke detectors shall be connected to a fire alarm system where a fire alarm sys- tem is required by Section 907.2 of the International Fire Code. The actuation of a duct smoke detector shall acti- vate a visible and audible supervisory signal at a con- stantly attended location. Exceptions: The supervisory signal at a constantly attended location is not required where the duct smoke detector activates the building's alarm -indicating appliances. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and audible signal in an approved location. Duct smoke detector trouble conditions shall activate a visible or audible sig- nal in an approved location and shall be identi- fied as air duct detector trouble. 70 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nmmbsx 100760189 oc Sep SO, 2019 01 av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( odUto.. by POVOtput, I,ANb�to,P,,UoFsd Single—mly mpymg Pod oNyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS [B] SECTION 607 DUCT AND TRANSFER OPENINGS 607.1 General. The provisions of this section shall govern the protection of duct penetrations and air transfer openings in assemblies required to be protected. 607.1.1 Ducts that penetrate fire -resistance -rated assemblies without dampers. Ducts that penetrate fire - resistance -rated assemblies and are not required by this section to have dampers shall comply with the require- ments of Sections 714.2 through 714.3.3 of the Interna- tional Building Code. Ducts that penetrate horizontal assemblies not required to be contained within a shaft and not required by this section to have dampers shall comply with the requirements of Sections 714.4 through 714.4.2.2 of the International Building Code. 607.1.1.1 Ducts that penetrate nonfire-resistance- rated assemblies. The space around a duct penetrating a nonfire-resistance-rated floor assembly shall comply with Section 717.6.3 of the International Building Code. 607.2 Installation. Fire dampers, smoke dampers, combina- tion fire/smoke dampers and ceiling radiation dampers located within air distribution and smoke control systems shall be installed in accordance with the requirements of this section, and the manufacturer's installation instructions and listing. 607.2.1 Smoke control system. Where the installation of a fire damper will interfere with the operation of a required smoke control system in accordance with Section 909 of the International Building Code, approved alternative pro- tection shall be used. Where mechanical systems including ducts and dampers used for normal building ventilation serve as part of the smoke control system, the expected performance of these systems in smoke control mode shall be addressed in the rational analysis required by Section 909.4 of the International Building Code. 607.2.2 Hazardous exhaust ducts. Fire dampers for haz- ardous exhaust duct systems shall comply with Section 510. 607.3 Damper testing, ratings and actuation. Damper test- ing, ratings and actuation shall be in accordance with Sec- tions 607.3.1 through 607.3.3. 607.3.1 Damper testing. Dampers shall be listed and labeled in accordance with the standards in this section. Fire dampers shall comply with the requirements of UL 555. Only fire dampers labeled for use in dynamic systems shall be installed in heating, ventilation and air-condition- ing systems designed to operate with fans on during a fire. Smoke dampers shall comply with the requirements of UL 555S. Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S. Ceiling radiation dampers shall comply with the requirements of UL 555C or shall be tested as part of a fire -resistance -rated floor/ceiling or roof/ceiling assembly in accordance with ASTM El19 or UL 263. 607.3.2 Damper rating. Damper ratings shall be in accor- dance with Sections 607.3.2.1 through 607.3.2.3. 607.3.2.1 Fire damper ratings. Fire dampers shall have the minimum fire protection rating specified in Table 607.3.2.1 for the type of penetration. TABLE 607.3.2.1 FIRE DAMPER RATING MINIMUM DAMPER TYPE OF PENETRATION RATING (hour) Less than 3-hour fire -resistance -rated assemblies 1 V, 3-hour or greater fire -resistance -rated assemblies 3 607.3.2.2 Smoke damper ratings. Smoke damper leakage ratings shall be Class I or II. Elevated tempera- ture ratings shall not be less than 250°F (121°C). 607.3.2.3 Combination fire/smoke damper ratings. Combination fire/smoke dampers shall have the mini- mum fire protection rating specified for fire dampers in Table 717.3.2.1 of the International Building Code for the type of penetration and shall also have a minimum smoke damper rating as specified in Section 717.3.2.2 of the International Building Code. 607.3.3 Damper actuation. Damper actuation shall be in accordance with Sections 607.3.3.1 through 607.3.3.4 as applicable. 607.3.3.1 Fire damper actuation device. The fire damper actuation device shall meet one of the follow- ing requirements: 1. The operating temperature shall be approxi- mately 50°F (28°C) above the normal tempera- ture within the duct system, but not less than 160°F (71°C). 2. The operating temperature shall be not more than 350°F (177°C) where located in a smoke control system complying with Section 909 of the Inter- national Building Code. 607.3.3.2 Smoke damper actuation. The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Sec- tion 907.3 of the International Building Code and one of the following methods, as applicable: 1. Where a smoke damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate. 2. Where a smoke damper is installed above smoke barrier doors in a smoke barrier, a spot -type detector listed for releasing service shall be installed on either side of the smoke barrier door opening. 2012 INTERNATIONAL MECHANICAL CODE® 71 I II I C,Ty,ght @ zoI I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx/00760/89 oc Sep V,2019o147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg andortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS 3. Where a smoke damper is installed within an unducted opening in a wall, a spot -type detector listed for releasing service shall be installed within 5 feet (1524 mm) horizontally of the damper. 4. Where a smoke damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor. 5. Where a total -coverage smoke detector system is provided within areas served by a heating, venti- lation and air-conditioning (HVAC) system, smoke dampers shall be permitted to be con- trolled by the smoke detection system. 607.3.3.3 Combination fire/smoke damper actua- tion. Combination fire/smoke damper actuation shall be in accordance with Sections 607.3.3.1 and 607.3.3.2. Combination fire/smoke dampers installed in smoke control system shaft penetrations shall not be activated by local area smoke detection unless it is secondary to the smoke management system controls. 607.3.3.4 Ceiling radiation damper actuation. The operating temperature of a ceiling radiation damper actuation device shall be 50oF (28°C) above the normal temperature within the duct system, but not less than 160°F (71°C). 607.4 Access and identification. Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts. The access shall not affect the integ- rity of fire -resistance -rated assemblies. The access openings shall not reduce the fire -resistance rating of the assembly. Access points shall be permanently identified on the exterior by a label having letters not less than 0.5 inch (12.7 mm) in height reading: FIRE/SMOKE DAMPER, SMOKE DAMPER or FIRE DAMPER. Access doors in ducts shall be tight fitting and suitable for the required duct construction. 607.5 Where required. Fire dampers, smoke dampers and combination fire/smoke dampers shall be provided at the locations prescribed in Sections 607.5.1 through 607.5.7. Where an assembly is required to have both fire dampers and smoke dampers, combination fire/smoke dampers or a fire damper and smoke damper shall be required. 607.5.1 Fire walls. Ducts and air transfer openings per- mitted in fire walls in accordance with Section 706.11 of the International Building Code shall be protected with listed fire dampers installed in accordance with their list- ing. 607.5.1.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be pro- vided at each point that a duct or air transfer opening penetrates a 8re wall that serves as a horizontal exit. 607.5.2 Fire barriers. Ducts and air transfer openings that penetrate fire barriers shall be protected with listed fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate exit enclo- sures and exit passageways except as permitted by Sec- tions 1022.5 and 1023.6, respectively, of the International Building Code. Exception: Fire dampers are not required at penetra- tions of fire barriers where any of the following apply: 1. Penetrations are tested in accordance with ASTM E 119 or UL 263 as part of the fire -resistance - rated assembly. 2. Ducts are used as part of an approved smoke con- trol system in accordance with Section 513 and where the fire damper would interfere with the operation of the smoke control system. 3. Such walls are penetrated by ducted HVAC sys- tems, have a required fire -resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 of the Interna- tional Building Code. For the purposes of this exception, a ducted HVAC system shall be a duct system for the structure's HVAC system. Such a duct system shall be constructed of sheet steel not less than 26 gage [0.0217 inch (0.55 mm)] thick- ness and shall be continuous from the air -han- dling appliance or equipment to the air outlet and inlet terminals. 607.5.2.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be pro- vided at each point that a duct or air transfer opening penetrates a fire barrier that serves as a horizontal exit. 607.5.3 Fire partitions. Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing. Exception: In occupancies other than Group H, fire dampers are not required where any of the following apply: 1. Corridor walls in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 of the Inter- national Building Code and the duct is protected as a through penetration in accordance with Sec- tion 714 of the International Building Code. 2. The partitions are tenant partitions in covered and open mall buildings where the walls are not required by provisions elsewhere in the Interna- tional Building Code to extend to the underside of the floor or roof sheathing, slab or deck above. 3. The duct system is constructed of approved mate- rials in accordance with Section 603 and the duct penetrating the wall complies with all of the fol- lowing requirements: 3.1. The duct shall not exceed 100 square inches (0.06 m'). 3.2. The duct shall be constructed of steel a minimum of 0.0217 inch (0.55 mm) in thickness. 72 2012 INTERNATIONAL MECHANICAL CODE® 17 S I C,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, ( �ep� odUt.. byanytlu,dparty.oPANb�toc UoFsd Single—mly mpymgand-PyodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS 3.3. The duct shall not have openings that com- municate the corridor with adjacent spaces or rooms. 3.4. The duct shall be installed above a ceiling. 3.5. The duct shall not terminate at a wall regis- ter in the fire -resistance -rated wall. 3.6. A minimum 12-inch-long (305 mm) by 0.060-inch-thick (1.52 mm) steel sleeve shall be centered in each duct opening. The sleeve shall be secured to both sides of the wall and all four sides of the sleeve with minimum P/z inch by P/z inch by 0.060- inch (38 mm by 38 mm by 1.52 mm) steel retaining angles. The retaining angles shall be secured to the sleeve and the wall with No. 10 (M5) screws. The annular space between the steel sleeve and the wall open- ing shall be filled with rock (mineral) wool batting on all sides. 4. Such walls are penetrated by ducted HVAC sys- tems, have a required fire -resistance rating of 1 hour or less, and are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 of the Interna- tional Building Code. For the purposes of this exception, a ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure's HVAC system. Such a duct system shall be constructed of sheet steel not less than 26 gage in thickness and shall be continuous from the air -handling appliance or equipment to the air outlet and inlet terminals. 607.5.4 Corridors/smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening pene- trates a smoke barrier wall or a corridor enclosure required to have smoke and draft control doors in accordance with the International Building Code. Smoke dampers and smoke damper actuation methods shall comply with Sec- tion 607.5.4.1. Exceptions: 1. Smoke dampers are not required in corridor pene- trations where the building is equipped through- out with an approved smoke control system in accordance with Section 513 and smoke dampers are not necessary for the operation and control of the system. 2. Smoke dampers are not required in smoke barrier penetrations where the openings in ducts are lim- ited to a single smoke compartment and the ducts are constructed of steel. 3. Smoke dampers are not required in corridor pene- trations where the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and there are no openings serving the corridor. 607.5.4.1 Smoke damper. The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with the International Building Code and one of the following methods, as applicable: 1. Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. 2. Where a damper is installed above smoke barrier doors in a smoke barrier, a spot -type detector listed for releasing service shall be installed on either side of the smoke barrier door opening. 3. Where a damper is installed within an unducted opening in a wall, a spot -type detector listed for releasing service shall be installed within 5 feet (1524 mm) horizontally of the damper. 4. Where a damper is installed in a corridor wall, the damper shall be permitted to be controlled by a smoke detection system installed in the corri- dor. 5. Where a total -coverage smoke detector system is provided within all areas served by an HVAC system, dampers shall be permitted to be con- trolled by the smoke detection system. 607.5.5 Shaft enclosures. Shaft enclosures that are per- mitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing. Exceptions: 1. Fire dampers are not required at penetrations of shafts where: 1.1. Steel exhaust subducts extend at least 22 inches (559 mm) vertically in exhaust shafts provided that there is a continuous airflow upward to the outdoors; or 1.2. Penetrations are tested in accordance with ASTM E 119 or UL 263 as part of the fire -resistance -rated assembly; or 1.3. Ducts are used as part of an approved smoke control system in accordance with Section 909 of the International Building Code, and where the fire damper will interfere with the operation of the smoke control system; or 1.4. The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire -resistance -rated construction. 2. In Group B and R occupancies equipped through- out with an automatic sprinkler system in accor- dance with Section 903.3.1.1 of the International Building Code, smoke dampers are not required 2012 INTERNATIONAL MECHANICAL CODE® 73 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS at penetrations of shafts where kitchen, clothes dryer, bathroom and toilet room exhaust open- ings with steel exhaust subducts, having a mini- mum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage), extend at least 22 inches (559 mm) ver- tically and the exhaust fan at the upper terminus is powered continuously in accordance with the provisions of Section 909.11 of the International Building Code, and maintains airflow upward to the outdoors. 3. Smoke dampers are not required at penetrations of exhaust or supply shafts in parking garages that are separated from other building shafts by not less than 2-hour fire -resistance -rated con- struction. 4. Smoke dampers are not required at penetrations of shafts where ducts are used as part of an approved mechanical smoke control system designed in accordance with Section 909 of the International Building Code and where the smoke damper will interfere with the operation of the smoke control system. 5. Fire dampers and combination fire/smoke damp- ers are not required in kitchen and clothes dryer exhaust systems installed in accordance with this code. 607.5.5.1 Enclosure at the bottom. Shaft enclosures that do not extend to the bottom of the building or structure shall be protected in accordance with Section 713.11 of the International Building Code. 607.5.6 Exterior walls. Ducts and air transfer openings in fire -resistance -rated exterior walls required to have pro- tected openings in accordance with Section 705.10 of the International Building Code shall be protected with listed fire dampers installed in accordance with their listing. 607.5.7 Smoke partitions. A listed smoke damper designed to resist the passage of smoke shall be provided at each point where an air transfer opening penetrates a smoke partition. Smoke dampers and smoke damper actu- ation methods shall comply with Section 607.3.3.2. Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 513, approved alternate protection shall be used. 607.6 Horizontal assemblies. Penetrations by air ducts of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 713 and Sections 717.6.1 through 717.6.3 of the International Building Code or shall comply with Sections 607.6.1 through 607.6.3. 607.6.1 Through penetrations. In occupancies other than Groups I-2 and I-3, a duct constructed of approved materi- als in accordance with Section 603 that penetrates a fire - resistance -rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection provided that a listed fire damper is installed at the floor line or the duct is protected in accordance with Section 714.4 of the International Building Code. For air transfer openings, see item 7, Section 712.1.8 of the Inter- national Building Code. Exception: A duct is permitted to penetrate three floors or less without a fire damper at each floor provided it meets all of the following requirements. 1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage). 2. The duct shall open into only one dwelling unit or sleeping unit and the duct system shall be contin- uous from the unit to the exterior of the building. 3. The duct shall not exceed 4-inch (102 mm) nomi- nal diameter and the total area of such ducts shall not exceed 100 square inches for any 100 square feet (64 516 mm' per 9.3 m') of the floor area. 4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to ASTM E 119 or UL 263 time - temperature conditions under a minimum posi- tive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire -resistance rat- ing of the construction penetrated. 5. Grille openings located in a ceiling of a fire -resis- tance -rated floor/ceiling or roof/ceiling assembly shall be protected with a listed ceiling radiation damper installed in accordance with Section 607.6.2.1. 607.6.2 Membrane penetrations. Ducts and air transfer openings constructed of approved materials, in accordance with Section 603, that penetrate the ceiling membrane of a fire -resistance -rated floor/ceiling or roof/ceiling assembly shall be protected with one of the following: 1. A shaft enclosure in accordance with Section 713 of the International Building Code. 2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fire -resistance -rated floor/ceiling or roof/ceiling assembly. 3. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire -resistance -rated floor/ ceiling or roof/ceiling assembly. 607.6.2.1 Ceiling radiation dampers. Ceiling radia- tion dampers shall be tested in accordance with Section 607.3.1. Ceiling radiation dampers shall be installed in accordance with the details listed in the fire -resistance - rated assembly and the manufacturer's installation instructions and the listing. Ceiling radiation dampers are not required where either of the following applies: 1. Tests in accordance with ASTM E 119 or UL 263 have shown that ceiling radiation dampers are not 74 2012 INTERNATIONAL MECHANICAL CODE® 17 Co,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( N ,Fod,Yo,,bymytl,dputy,o,Abau�to,o,sd Single—mly mpymg andmg d-PyoFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER DUCT SYSTEMS necessary to maintain the fire -resistance rating of the assembly. 2. Where exhaust duct penetrations are protected in accordance with Section 714.4.1.2 of the Interna- tional Building Code, are located within the cav- ity of a wall and do not pass through another dwelling unit or tenant space. 607.6.3 Nonfire-resistance-rated floor assemblies. Duct systems constructed of approved materials in accordance with Section 603 that penetrate nonfire-resistance-rated floor assemblies shall be protected by any of the following methods: 1. A shaft enclosure in accordance with Section 713 of the International Building Code. 2. The duct connects not more than two stories, and the annular space around the penetrating duct is pro- tected with an approved noncombustible material that resists the free passage of flame and the prod- ucts of combustion. 3. The duct connects not more than three stories, and the annular space around the penetrating duct is pro- tected with an approved noncombustible material that resists the free passage of flame and the prod- ucts of combustion, and a listed fire damper is installed at each floor line. Exception: Fire dampers are not required in ducts within individual residential dwelling units. 607.7 Flexible ducts and air connectors. Flexible ducts and air connectors shall not pass through any fire -resistance -rated assembly. 2012 INTERNATIONAL MECHANICAL CODE® 75 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 76 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc SIP SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( �ep�odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mp,YEmdoehuodmg plokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDRRAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER COMBUSTION AIR SECTION 701 GENERAL 701.1 Scope. Solid fuel -burning appliances shall be provided with combustion air in accordance with the appliance manu- facturer's installation instructions. Oil -fired appliances shall be provided with combustion air in accordance with NITA 31. The methods of providing combustion air in this chapter do not apply to fireplaces, fireplace stoves and direct -vent appliances. The requirements for combustion and dilution air for gas -fired appliances shall be in accordance with the Inter- national Fuel Gas Code. 2012 INTERNATIONAL MECHANICAL CODE® 77 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,iNb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 78 2012 INTERNATIONAL MECHANICAL CODE® C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc Sep SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( �ep�odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDRRAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, main- tenance, repair and approval of factory -built chimneys, chim- ney liners, vents and connectors. This chapter shall also govern the utilization of masonry chimneys. Gas -fired appli- ances shall be vented in accordance with the International Fuel Gas Code. 801.2 General. Every fuel -burning appliance shall discharge the products of combustion to a vent, factory -built chimney or masonry chimney, except for appliances vented in accor- dance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2.1 Oil -fired appliances. Oil -fired appliances shall be vented in accordance with this code and NFPA 31. 801.3 Masonry chimneys. Masonry chimneys shall be con- structed in accordance with the International Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to con- vey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall be designed in accor- dance with this chapter or shall be approved engineered sys- tems. 801.6 Minimum size of chimney or vent. Except as other- wise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel appliance flues. The cross -sectional area of a flue serving a solid -fuel -burning appliance shall be not greater than three times the cross -sectional area of the appli- ance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pressure in the venting system, the venting system shall be designed and listed for positive pressure applications. 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory -built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory -built fireplace unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer's installa- tion instructions. 801.10.3 Connection to masonry fireplace flue. A con- nector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel prohibited. A solid fuel -burning appliance or fireplace shall not connect to a chimney passage- way venting another appliance. 801.12 Chimney entrance. Connectors shall connect to a chimney flue at a point not less than 12 inches (305 mm) above the lowest portion of the interior of the chimneyflue. 801.13 Cleanouts. Masonry chimneyflues shall be provided with a cleanout opening having a minimum height of 6 inches (152 min). The upper edge of the opening shall be located not less than 6 inches (152 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight -fitting, noncombustible cover. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are pro- vided with access through the fireplace opening. 801.14 Connections to exhauster. All appliance connec- tions to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. All joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufacturer's installation instructions for the exhauster. 801.15 Fuel -fired appliances. Masonry chimneys utilized to vent fuel -fired appliances shall be located, constructed and sized as specified in the manufacture's installation instruc- tions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appliance connected, in accordance with the appliance listing and man- ufacturer's installation instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer's installation instructions. 801.16.1 Residential and low -heat appliances (general). Flue lining systems for use with residential -type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the International Build- ng Code. 2. Listed and labeled chimney lining systems comply- ing with UL 1777. 2012 INTERNATIONAL MECHANICAL CODE® 79 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHIMNEYS AND VENTS 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and con- densate at temperatures up to 1,800°F (982°C). 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chim- neyshall not be used to vent any other appliance. This shall not prevent the installation of a separate flue lining in accor- dance with the manufacturer's installation instructions and this code. 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimneyor vent during the process of a new installation, the chimneyor vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimneyor vent shall be resized as nec- essary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appli- ances served with the required draft. For the venting of oil -fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801.18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel -burning appliance or fireplace. The flue liner, chimneyinner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creo- sote. Where an oil -fired appliance is connected to an exist- ing masonry chimney, such chimneyflue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have air- space clearance to combustibles in accordance with the International Building Code and the chimneyor vent man- ufacturer's installation instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777. The chimney clearance shall be not less than permitted by the terms of the chimmyliner listing and the manufacturer's instructions. 801.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the International Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be pro- hibited, except where all of the appliances served by the com- mon vent are located in rooms or spaces that are accessed only from the outdoors. The appliance enclosures shall not communicate with the occupiable areas of the building. 801.20 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer's installation instructions. SECTION 802 VENTS 802.1 General. All vent systems shall be listed and labeled Type L vents and pellet vents shall be tested in accordance with UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENTTYPES APPLIANCE TYPES Oil -burning appliances listed and labeled for Type L oil vents venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. Pellet vents Pellet fuel -burning appliances listed and labeled for venting with pellet vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manu- facturer's installation instructions. 802.4 Vent termination caps required. Type L vents shall terminate with a listed and labeled cap in accordance with the vent manufacturer's installation instructions. 802.5 Type L vent terminations. Type L vents shall termi- nate not less than 2 feet (610 mm) above the highest point of the roof penetration and not less than 2 feet (610 mm) higher than any portion of a building within 10 feet (3048 mm). 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 min) in vertical height above the highest connected appliance flue collar. Exceptions: Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer's instructions. 2. Appliances listed for outdoor installations incorpo- rating integral venting means shall be installed in accordance with their listings and the manufac- turer's installation instructions. 3. Pellet vents shall be installed in accordance with the appliance and the vent manufacturer's installation instructions. 802.7 Support of vents. All portions of vents shall be ade- quately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than No. 26 gage sheet metal shall be installed to provide clear- ance between the vent and the insulation material. The clear- ance shall be not less than the clearance to combustibles specified by the vent manufacturer's installation instructions. Where vents pass through attic space, the shield shall termi- nate not less than 2 inches (51 mm) above the insulation materials and shall be secured in place to prevent displace- ment. Insulation shields provided as part of a Listed vent sys- tem shall be installed in accordance with the manufacturer's installation instructions. 80 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nmmbsx 100760189 oc Sep SO, 2019 01 av To (PDT) p—Pot to IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( odUto.. by POVOtput, I,ANb�to,P,,UoFsd Single—mly mpymg Pod oNyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRTRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHIMNEYS AND VENTS SECTION 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appli- ance. 803.2 Location. Connectors shall be located entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be constructed of single -wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer's specific instructions, the con- nector area shall be not less than the combined area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. All branch connections to the vent connector shall be made in accordance with the vent manufacturer's instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel -burning appliances. 803.6 Automatic dampers. Automatic dampers shall be listed and labeled in accordance with UL 17 for oil -fired heating appliances. The dampers shall be installed in accor- dance with the manufacturer's installation instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible mate- rial. 803.8 Vent connector construction. Vent connectors shall be constructed of metal. The minimum thickness of the con- nector shall be 0.0136 inch (0.345 mm) (No. 28 gage) for gal- vanized steel, 0.022 inch (0.6 mm) (No. 26 B & S gage) for copper, and 0.020 inch (0.5 mm) (No. 24 B & S gage) for alu- minum. 803.9 Chimney connector construction. Chimney connec- tors for low -heat appliances shall be of sheet steel pipe hav- ing resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium -heat appliances and high -heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). 803.10 Installation. Connectors shall be installed in accor- dance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be sup- ported in an approved manner, and joints shall be fastened with sheet metal screws, rivets or other approved means. TABLE 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW -HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanizeci)(inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI 1 inch — 25 4 min TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM -AND HIGH -HEAT APPLIANCE EQUIVALENT ROUND AREA DIAMETER MINIMUM THICKNESS (square inches) (inches) (inches) 0.0575 0-154 0-14 (No. 16 gage) 155-201 15-16 0.075 (No. 14 gage) 202-254 17-18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) 803.10.2 Length. The maximum horizontal length of a single -wall connector shall be 75 percent of the height of the chimm yor vent. 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimm y shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently cemented in place with high -temperature cement. 803.10.4 Connector pass -through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire -resistance -rated wall assembly. Chimney connectors for domestic -type appliances shall not pass through walls or partitions constructed of combustible material to reach a masonry chimneyunless: 1. The connector is labeled for wall pass -through and is installed in accordance with the manufacturer's instructions; 2. The connector is put through a device labeled for wall pass -through; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass -through system in contact with flue gases shall be of stainless steel or equiva- lent material that resists corrosion, softening or cracking up to 1,800°F (980°C). 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one-fourth unit vertical in 12 units horizontal (2-percent slope). 2012 INTERNATIONAL MECHANICAL CODE® 81 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O[d6 Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHIMNEYS AND VENTS TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR DOMESTIC HEATING APPLIANCESa, b,c,d A 3.5-inch-thick brick wall shall be framed into the combustible wall. An 0.625-inch-thick fire -clay liner System A (ASTM C 315 or equivalend'shall be firmly cemented (12-inch in the center of the brick wall maintaining a 12-inch clearance) clearance to combustibles. The clay liner shall run from the outer surface of the bricks to the inner surface of the chimney liner. A labeled solid -insulated factory -built chimney section (1-inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9-inch clearance to combustibles shall be System B fastened to the wall surface and to the chimney sec- (9-inch lion. Fasteners shall not penetrate the chimney flue clearance) liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water -insoluble refractory cement Chimney manufac- turers' parts shall be utilized to securely fasten the chimney connector to the chimney section. A steel ventilated thimble having a minimum thick- ness of 0.0236 inch (No. 24 gage) having two 1-inch air channels shall be installed with a steel chimney System C connector. Steel supports shall be cut to maintain a 6- (6-inch inch clearance between the thimble and combustibles. clearance) The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass -fiber insulation shall fill the 6-inch space between the thimble and the supports. A labeled solid -insulated factory -built chimney section (1-inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of System 0.0236 inch (24 gage). Sheet steel supports shall be (2-inch positioned to maintain a 2-inch clearance to combusti- clearance) bles and to hold the chimney connector to ensure that a 1-inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney sec- tion shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI 1 inch — 25 from, 1 0 Btu x in/ffE . h . °F — 0 144 W/mE . K a Insulation material that is part of the wall pass -through system shall be noncombustible and shall have a thermal conductivity of 10 Btu x in/ftE . IF . IF or less b All clearances and thicknesses are minimums c Materials utilized to seal penetrations for the connector shall be noncombustible d Connectors for all systems except System B shall extend through the wall pass -through system to the inner face of the flue liner e ASTM C315 803.10.6 Clearances. Connectors shall have a minimum clearance to combustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appli- ance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combusti- bles for connectors shall be reduced only in accordance with Section 308. TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES MINIMUM CLEARANCE TYPE OF APPLIANCE I (inches) Domestic -type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid -fuel appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial -type appliances Low -heat appliances Chimney connectors Oil and solid -fuel boilers, furnace 18 and water heaters Oil unit heaters 18 Other low -heat industrial appliances 18 Medium -heat appliances Chimney connectors All oil and solid -fuel appliances 36 High -heat appliances (As determined by the Masonry or metal connectors code official) All oil and solid -fuel appliances For SI 1 inch — 25 4 min SECTION 804 DIRECT -VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct -vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the man- ufacturer's installation instructions 804.2 Appliances with integral vents. Appliances incorpo- rating integral venting means shall be installed in accordance with their listings and the manufacturer's installation instruc- tions. 804.2.1 Terminal clearances. Appliances designed for natural draft venting and incorporating integral venting means shall be located so that a minimum clearance of 9 inches (229 mm) is maintained between vent terminals and from any openings through which combustion products enter the building. Appliances using forced draft venting shall be located so that a minimum clearance of 12 inches (305 mm) is maintained between vent terminals and from any openings through which combustion products enter the building. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in accordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.7. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as 82 2012 INTERNATIONAL MECHANICAL CODE® CoSVyYght @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 100760189 oc Sep SO, 2019 o 147 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,od U:oa oAYUP, 4 I ( [,FodUto,,by mythdparty.o,AeTb�tocP,,UoFPd Single—oPIA mpymg Pod o Nyodmg plokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE FOR REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHIMNEYS AND VENTS to be gas tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically con- nected to each appliance to prevent operation of the appli- ance when the power exhauster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located a minimum of 10 feet (3048 mm) from the lot line or from adjacent buildings. The exhaust shall be directed away from the building. 804.3.4 Horizontal terminations. Horizontal termina- tions shall comply with the following requirements: 1. Where located adjacent to walkways, the termina- tion of mechanical draft systems shall be not less than 7 feet (2134 mm) above the level of the walk- way. 2. Vents shall terminate at least 3 feet (914 mm) above any forced air inlet located within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219 mm) below, 4 feet (1219 mm) horizontally from or 1 foot (305 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shall not be located closer than 3 feet (914 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent termination shall not be mounted directly above or within 3 feet (914 mm) horizontally from an oil tank vent or gas meter. 6. The bottom of the vent termination shall be located at least 12 inches (305 mm) above finished grade. 804.3.5 Vertical terminations. Vertical terminations shall comply with the following requirements: 1. Where located adjacent to walkways, the termina- tion of mechanical draft systems shall be not less than 7 feet (2134 mm) above the level of the walk- way. 2. Vents shall terminate at least 3 feet (914 mm) above any forced air inlet located within 10 feet (3048 mm) horizontally. 3. Where the vent termination is located below an adja- cent roof structure, the termination point shall be located at least 3 feet (914 mm) from such structure. 4. The vent shall terminate at least 4 feet (1219 mm) below, 4 feet (1219 mm) horizontally from or 1 foot (305 mm) above any door, window or gravity air inlet for the building. 5. A vent cap shall be installed to prevent rain from entering the vent system. 6. The vent termination shall be located at least 3 feet (914 mm) horizontally from any portion of the roof structure. 804.3.6 Exhauster connections. An appliance vented by natural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue exhauster. 804.3.7 Exhauster sizing. Mechanical flue exhausters and the vent system served shall be sized and installed in accordance with the manufacturer's installation instruc- tions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appli- ances and fireplaces where such system complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer's instructions. 2. A device shall be installed that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechanical draft device is turned on. This device shall be equipped with a battery backup if it receives power from the building wiring. 3. A smoke detector shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives power from the building wiring. SECTION 805 FACTORY -BUILT CHIMNEYS 805.1 Listing. Factory -built chimneys shall be listed and labeled and shall be installed and terminated in accordance with the manufacturer's installation instructions. 805.2 Solid fuel appliances. Factory -built chimneys installed in dwelling units with solid fuel -burning appliances shall comply with the Type HT requirements of UL 103 and shall be marked "Type HT" and "Residential Type and Building Heating Appliance Chimney. " Exception: Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked "Residential Type and Build- ing Heating Appliance Chimney. " Chimneys for use with open combustion chamber appli- ances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked "Building Heating Appliance Chimney" or "Residential Type and Building Heating Appliance Chimney. " 805.3 Factory -built chimney offsets. Where a factory -built chimney assembly incorporates offsets, no part of the chim- ney shall be at an angle of more than 30 degrees (0.52 cad) from vertical at any point in the assembly and the chimney assembly shall not include more than four elbows. 805.4 Factory -built fireplaces. Chimneys for factory -built fireplaces shall comply with the requirements of UL 127. 2012 INTERNATIONAL MECHANICAL CODE® 83 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHIMNEYS AND VENTS 805.5 Support. Where factory -built chimneys are supported by structural members, such as joists and rafters, such mem- bers shall be designed to support the additional load. 805.6 Medium -heat appliances. Factory -built chimneys for medium -heat appliances producing flue gases having a tem- perature above 1,000°F (538°C), measured at the entrance to the chimney, shall comply with UL 959. 805.7 Decorative shrouds. Decorative shrouds shall not be installed at the termination of factory -built chimneys except where such shrouds are listed and labeled for use with the specific factory -built chimney system and are installed in accordance with Section 304.1. SECTION 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 84 2012 INTERNATIONAL MECHANICAL CODE® Co,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I IT �ep4od,,to—by POVO d party. o,±RYb�toc P,,Uoosd Smglo mlym,ymg ando Nyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPBDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL -BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein and factory -built fireplaces. The approval, design, installa- tion, construction, maintenance, alteration and repair of gas - fired appliances shall be regulated by the International Fuel Gas Code. 901.2 General. The requirements of this chapter shall apply to the mechanical equipment and appliances regulated by this chapter, in addition to the other requirements of this code. 901.3 Hazardous locations. Fireplaces and solid fuel -burn- ing appliances shall not be installed in hazardous locations. 901.4 Fireplace accessories. Listed and labeled fireplace accessories shall be installed in accordance with the condi- tions of the listing and the manufacturer's instructions. Fire- place accessories shall comply with UL 907. SECTION 902 MASONRY FIREPLACES 902.1 General. Masonry fireplaces shall be constructed in accordance with the International Building Code. SECTION 903 FACTORY -BUILT FIREPLACES 903.1 General. Factory -built fireplaces shall be listed and labeled and shall be installed in accordance with the condi- tions of the listing. Factory -built fireplaces shall be tested in accordance with UL 127. 903.2 Hearth extensions. Hearth extensions of approved fac- tory -built fireplaces shall be installed in accordance with the listing of the fireplace. The hearth extension shall be readily distinguishable from the surrounding floor area. Listed and labeled hearth extensions shall comply with UL 1618. 903.3 Unvented gas log heaters. An unvented gas log heater shall not be installed in a factory -built fireplace unless the fireplace system has been specifically tested, listed and labeled for such use in accordance with UL 127. SECTION 904 PELLET FUEL -BURNING APPLIANCES 904.1 General. Pellet fuel -burning appliances shall be listed and labeled in accordance with ASTM E 1509 and shall be installed in accordance with the terms of the listing. SECTION 905 FIREPLACE STOVES AND ROOM HEATERS 905.1 General. Fireplace stoves and solid -fuel -type room heaters shall be listed and labeled and shall be installed in accordance with the conditions of the listing. Fireplace stoves shall be tested in accordance with UL 737. Solid -fuel -type room heaters shall be tested in accordance with UL 1482. Fireplace inserts intended for installation in fireplaces shall be listed and labeled in accordance with the requirements of UL 1482 and shall be installed in accordance with the manu- facturer's installation instructions. 905.2 Connection to fireplace. The connection of solid fuel appliances to chimney flues serving fireplaces shall comply with Sections 801.7 and 801.10. 905.3 Hearth extensions. Hearth extensions for fireplace stoves shall be installed in accordance with the listing of the fireplace stove. The hearth extension shall be readily distin- guishable from the surrounding floor area. Listed and labeled hearth extensions shall comply with UL 1618. SECTION 906 FACTORY -BUILT BARBECUE APPLIANCES 906.1 General. Factory -built barbecue appliances shall be of an approved type and shall be installed in accordance with the manufacturer's installation instructions, this chapter and Chapters 3, 5, 7, 8 and the International Fuel Gas Code. SECTION 907 INCINERATORS AND CREMATORIES 907.1 General. Incinerators and crematories shall be listed and labeled in accordance with UL 791 and shall be installed in accordance with the manufacturer's installation instruc- tions. SECTION 908 COOLING TOWERS, EVAPORATIVE CONDENSERS AND FLUID COOLERS 908.1 General. A cooling tower used in conjunction with an air-conditioning appliance shall be installed in accordance with the manufacturer's installation instructions. Factory -built I cooling towers shall be listed in accordance with UL 1995. 908.2 Access. Cooling towers, evaporative condensers and fluid coolers shall be provided with ready access. 908.3 Location. Cooling towers, evaporative condensers and fluid coolers shall be located to prevent the discharge vapor plumes from entering occupied spaces. Plume discharges shall be not less than 5 feet (1524 mm) above or 20 feet (6096 mm) away from any ventilation inlet to a building. Location 2012 INTERNATIONAL MECHANICAL CODE® 85 I II I CopyngbtOO?.ot I ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)pwrvantto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,FodmYo¢ebymytl,dputy,o,ANb,to,au o,sd Smglo oPIA opymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL -BURNING EQUIPMENT on the property shall be as required for buildings in accor- dance with the International Building Code. 908.4 Support and anchorage. Supports for cooling towers, evaporative condensers and fluid coolers shall be designed in accordance with the International Building Code. Seismic restraints shall be as required by the International Building Code. 908.5 Water supply. Water supplies and protection shall be as required by the International Plumbing Code. 908.6 Drainage. Drains, overflows and blowdown provisions shall be indirectly connected to an approved disposal loca- tion. Discharge of chemical waste shall be approved by the appropriate regulatory authority. 908.7 Refrigerants and hazardous fluids. Heat exchange equipment that contains a refrigerant and that is part of a closed refrigeration system shall comply with Chapter 11. Heat exhange equipment containing heat transfer fluids which are flammable, combustible or hazardous shall comply with the International Fire Code. SECTION 909 VENTED WALL FURNACES 909.1 General. Vented wall furnaces shall be installed in accordance with their listing and the manufacturer's installa- tion instructions. Oil -fired furnaces shall be tested in accor- dance with UL 730. 909.2 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fur- nishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 909.3 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 inches (305 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 909.4 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. 909.5 Manual shutoff valve. A manual shutoff valve shall be installed ahead of all controls. 909.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that must be removed for normal servicing operations shall not be attached to the building construction. SECTION 910 FLOOR FURNACES 910.1 General. Floor furnaces shall be installed in accor- dance with their listing and the manufacturer's installation instructions. Oil -fired furnaces shall be tested in accordance with UL 729. 910.2 Placement. Floor furnaces shall not be installed in the floor of any aisle or passageway of any auditorium, public hall, place of assembly, or in any egress element from any such room or space. With the exception of wall register models, a floor furnace shall not be placed closer than 6 inches (152 mm) to the near- est wall, and wall register models shall not be placed closer than 6 inches (152 mm) to a corner. The furnace shall be placed such that a drapery or similar combustible object will not be nearer than 12 inches (305 mm) to any portion of the register of the furnace. Floor fur- naces shall not be installed in concrete floor construction built on grade. The controlling thermostat for a floor furnace shall be located within the same room or space as the floor furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 910.3 Bracing. The floor around the furnace shall be braced and headed with a support framework design in accordance with the International Building Code. 910.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6-inch (152 mm) clearance from the grade level; except where the lower 6-inch (152 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be reduced to not less than 2 inches (51 mm). Where these clearances are not present, the ground below and to the sides shall be exca- vated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the fur- nace. A 12-inch (305 mm) minimum clearance shall be pro- vided on all sides except the control side, which shall have an 18-inch (457 mm) minimum clearance. SECTION 911 DUCTFURNACES 911.1 General. Duct furnaces shall be installed in accordance with the manufacturer's installation instructions. Electric duct furnaces shall comply with UL 1996. SECTION 912 INFRARED RADIANT HEATERS 912.1 General. Electric infrared radiant heaters shall com- ply with UL 499. 912.2 Support. Infrared radiant heaters shall be fixed in a position independent of fuel and electric supply lines. Hang- ers and brackets shall be noncombustible material. 912.3 Clearances. Heaters shall be installed with clearances from combustible material in accordance with the manufac- turer's installation instructions. SECTION 913 CLOTHES DRYERS 913.1 General. Clothes dryers shall be installed in accor- dance with the manufacturer's installation instructions. Elec- 86 2012 INTERNATIONAL MECHANICAL CODE® C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( od Uto.. by POVO d party. o,±RYb�toc P,,Uoosd Single—mly mpymg Pod o Nyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL -BURNING EQUIPMENT tric residential clothes dryers shall be tested in accordance with UL 2158. Electric coin -operated clothes dryers shall be tested in accordance with UL 2158. Electric commercial clothes dryers shall be tested in accordance with UL 1240. 913.2 Exhaust required. Clothes dryers shall be exhausted in accordance with Section 504. 913.3 Clearances. Clothes dryers shall be installed with clearance to combustibles in accordance with the manufac- turer's instructions. SECTION 914 SAUNA HEATERS 914.1 Location and protection. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 914.1.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of material having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 914.2 Installation. Sauna heaters shall be listed and labeled in accordance with UL 875 and shall be installed in accor- dance with their listing and the manufacturer's installation instructions. 914.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 914.4 Heat and time controls. Sauna heaters shall be equipped with a thermostat that will limit room temperature to 1940F (900C). If the thermostat is not an integral part of the sauna heater, the heat -sensing element shall be located within 6 inches (152 mm) of the ceiling. If the heat -sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protected against phys- ical damage. 914.4.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 914.5 Sauna room. A ventilation opening into the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches (102 mm by 203 mm) located near the top of the door into the sauna room. 914.5.1 Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARM- FUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The words shall contrast with the background and the wording shall be in letters not less than '/q inch (6.4 mm) high. Exception: This section shall not apply to one- and two-family dwellings. SECTION 915 ENGINE AND GAS TURBINE -POWERED EQUIPMENT AND APPLIANCES 915.1 General. The installation of liquid -fueled stationary internal combustion engines and gas turbines, including exhaust, fuel storage and piping, shall meet the requirements of NBPA 37. Stationary engine generator assemblies shall meet the requirements of UL 2200. 915.2 Powered equipment and appliances. Permanently installed equipment and appliances powered by internal com- bustion engines and turbines shall be installed in accordance with the manufacturer's installation instructions and NFPA 37. SECTION 916 POOL AND SPA HEATERS 916.1 General. Pool and spa heaters shall be installed in accordance with the manufacturer's installation instructions. Oil -fired pool and spa heaters shall be tested in accordance with UL 726. Electric pool and spa heaters shall be tested in accordance with UL 1261. SECTION 917 COOKING APPLIANCES 917.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles and barbecues, shall be listed, labeled and installed in accordance with the manufac- turer's installation instructions. Commercial electric cooking appliances shall be listed and labeled in accordance with UL 197. Household electric ranges shall be listed and labeled in accordance with UL 858. Microwave cooking appliances shall be listed and labeled in accordance with UL 923. Oil - burning stoves shall be listed and labeled in accordance with UL 896. Solid -fuel -fired ovens shall be listed and labeled in accordance with UL 2162. 917.2 Prohibited location. Cooking appliances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. 917.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cook- ing operations occur shall be listed and labeled as household - type appliances for domestic use. 2012 INTERNATIONAL MECHANICAL CODE® 87 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL -BURNING EQUIPMENT SECTION 918 FORCED -AIR WARM -AIR FURNACES 918.1 Forced -air furnaces. Oil -fired furnaces shall be tested in accordance with UL 727. Electric furnaces shall be tested in accordance with UL 1995. Solid fuel furnaces shall be tested in accordance with UL 391. Forced -air furnaces shall be installed in accordance with the listings and the manufac- turer's installation instructions. 918.2 Minimum duct sizes. The minimum unobstructed total area of the outdoor and return air ducts or openings to a forced -air warm -air furnace shall be not less than 2 square inches per 1,000 Btu/h (4402 mm'/kW) output rating capacity of the furnace and not less than that specified in the furnace manufacturer's installation instructions. The minimum unob- structed total area of supply ducts from a forced -air warm -air furnace shall not be less than 2 square inches for each 1,000 Btu/h (4402 mm'/kW) output rating capacity of the furnace and not less than that specified in the furnace manufacturer's installation instructions. Exception: The total area of the supply air ducts and out- door and return air ducts shall not be required to be larger than the minimum size required by the furnace manufac- turer's installation instructions. 918.3 Heat pumps. The minimum unobstructed total area of the outdoor and return air ducts or openings to a heat pump shall be not less than 6 square inches per 1,000 Btu/h (13 208 mm'/kW) output rating or as indicated by the conditions of listing of the heat pump. Electric heat pumps shall be tested in accordance with UL 1995. 918.4 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 918.5 Circulating air ducts for forced -air warm -air fur- naces. Circulating air for fuel -burning, forced -air -type, warm -air furnaces shall be conducted into the blower housing from outside the furnace enclosure by continuous air -tight ducts. 918.6 Prohibited sources. Outdoor or return air for forced - air heating and cooling systems shall not be taken from the following locations: 1. Less than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the out- let is 3 feet (914 mm) above the outdoor air inlet. 2. Where there is the presence of objectionable odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machineryroom as defined in this code. 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Sections 918.2 and 918.3, adjoining rooms or spaces shall be considered as a sin- gle room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not apply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned attic. Exceptions: 5.1 Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances, and serve the kitchen area only, taking return air from a kitchen shall not be prohibited. 5.2 Dedicated forced -air systems serving only a garage shall not be prohibited from obtaining return air from the garage. 6. An unconditioned crawl space by means of direct con- nection to the return side of a forced air system. Trans- fer openings in the crawl space enclosure shall not be prohibited. 7. A room or space containing a fuel -burning appliance where such room or space serves as the sole source of return air. Exceptions: 7.1. This shall not apply where the fuel -burning appliance is a direct -vent appliance. 7.2. This shall not apply where the room or space complies with the following requirements: 7.2.1. The return air shall be taken from a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9.6 L/W) of combined input rating of all fuel - burning appliances therein. 7.2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volume of return air taken from the space. 7.2.3. Return -air inlets shall not be located within 10 feet (3048 mm) of any appliance firebox or draft hood in the same room or space. 7.3. This shall not apply to rooms or spaces con- taining solid -fuel -burning appliances, pro- vided that return -air inlets are located not less than 10 feet (3048 mm) from the firebox of the appliances. 918.7 Outside opening protection. Outdoor air intake open- ings shall be protected in accordance with Section 401.5. 88 2012 INTERNATIONAL MECHANICAL CODE® 17 C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( ,Fod,Y..1yPoytlu,dparty.oPANb�toc UoFsd Single—mlym,ymgand-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL -BURNING EQUIPMENT 918.8 Return -air limitation. Return air from one dwelling unit shall not be discharged into another dwelling unit. SECTION 919 CONVERSION BURNERS 919.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8. SECTION 920 UNIT HEATERS 920.1 General. Unit heaters shall be installed in accordance with the listing and the manufacturer's installation instruc- tions. Oil -fired unit heaters shall be tested in accordance with UL 731. 920.2 Support. Suspended -type unit heaters shall be sup- ported by elements that are designed and constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. Suspended - type oil -fired unit heaters shall be installed in accordance with NFPA 31. 920.3 Ductwork. A unit heater shall not be attached to a warm -air duct system unless listed for such installation. SECTION 921 VENTED ROOM HEATERS 921.1 General. Vented room heaters shall be listed and labeled and shall be installed in accordance with the condi- tions of the listing and the manufacturer's instructions. SECTION 922 KEROSENE AND OIL -FIRED STOVES 922.1 General. Kerosene and oil -fired stoves shall be listed and labeled and shall be installed in accordance with the con- ditions of the listing and the manufacturer's installation Iinstructions. Kerosene and oil -fired stoves shall comply with NFPA 31 and UL 896. SECTION 923 SMALL CERAMIC KILNS 923.1 General. The provisions of this section shall apply to kilns that are used for ceramics, have a maximum interior volume of 20 cubic feet (0.566 m') and are used for hobby and noncommercial purposes. Electric kilns shall comply with UL 499. 923.1.1 Installation. Kilns shall be installed in accordance with the manufacturer's installation instructions and the provisions of this code. SECTION 924 STATIONARY FUEL CELL POWER SYSTEMS 924.1 General. Stationary fuel cell power systems having a power output not exceeding 10 MW shall be tested in accor- dance with ANSUCSA America FC 1 and shall be installed in accordance with the manufacturer's installation instructions, NFPA 853, the International Building Code and the Interna- tional Fire Code. SECTION 925 MASONRY HEATERS 925.1 General. Masonry heaters shall be constructed in accordance with the International Building Code. SECTION 926 GASEOUS HYDROGEN SYSTEMS 926.1 Installation. The installation of gaseous hydrogen sys- tems shall be in accordance with the applicable requirements of this code, the International Fire Code, the International Fuel Gas Code and the International Building Code. SECTION 927 RADIANT HEATING SYSTEMS 927.1 General. Electric radiant heating systems shall be installed in accordance with the manufacturer's instructions and shall be listed for the application. 927.2 Clearances. Clearances for radiant heating panels or elements to any wiring, outlet boxes and junction boxes used for installing electrical devices or mounting luminaires shall be in accordance with the International Building Code and NFPA 70. 927.3 Installation on wood or steel framing. Radiant panels installed on wood or steel framing shall conform to the fol- lowing requirements: 1. Heating panels shall be installed parallel to framing members and secured to the surface of framing mem- bers or shall be mounted between framing members. 2. Mechanical fasteners shall penetrate only the unheated portions provided for this purpose. Panels shall not be fastened at any point closer than V, inch (7 mm) to an element. Other methods of attachment of the panels shall be in accordance with the panel installation instructions. 3. Unless listed and labeled for field cutting, heating pan- els shall be installed as complete units. 927.4 Installation in concrete or masonry. Radiant heating systems installed in concrete or masonry shall conform to the following requirements: 1. Radiant heating systems shall be identified as being suitable for the installation, and shall be secured in place as specified in the manufacturer's instructions. 2. Radiant heating panels and radiant heating panel sets shall not be installed where they bridge expansion joints unless they are protected from expansion and contraction. 927.5 Finish surfaces. Finish materials installed over radiant heating panels and systems shall be installed in accordance with the manufacturer's instructions. Surfaces shall be 4m 2012 INTERNATIONAL MECHANICAL CODE® 89 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL -BURNING EQUIPMENT secured so that fasteners do not pierce the radiant heating ele- ments. SECTION 928 EVAPORATIVE COOLING EQUIPMENT 928.1 General. Evaporative cooling equipment shall: 1. Be installed in accordance with the manufacturer's instructions. 2. Be installed on level platforms in accordance with Sec- tion 304.10. 3. Have openings in exterior walls or roofs flashed in accordance with the International Building Code. 4. Be provided with potable water backflow protection in accordance with Section 608 of the International Plumbing Code. 5. Have air intake opening locations in accordance with Section 401.4. 90 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 01 av PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I ( �ep�odUt.. byzoyUb,dparty.oPAembmoo Uoosd Single—mly So, Pod-PyodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels. Exceptions: 1. Pressure vessels used for unheated water supply. 2. Portable unfired pressure vessels and Interstate Commerce Commission containers. 3. Containers for bulk oxygen and medical gas. 4. Unfired pressure vessels having a volume of 5 cubic feet (0.14 m') or less operating at pressures not exceeding 250 pounds per square inch (psi) (1724 kPa) and located within occupancies of Groups B, F, H, M, R, S and U. 5. Pressure vessels used in refrigeration systems that are regulated by Chapter 11 of this code. 6. Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other similar humidity control systems. 7. Any boiler or pressure vessel subject to inspection by federal or state inspectors. SECTION 1002 WATER HEATERS 1002.1 General. Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accordance with the manufacturer's installation instructions, the Interna- tional Plumbing Code and this code. All water heaters shall be capable of being removed without first removing a perma- nent portion of the building structure. The potable water con- nections and relief valves for all water heaters shall conform to the requirements of the International Plumbing Code. Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall comply with UL 1453. Oil -fired water heaters shall comply with UL 732. Solid -fuel -fired water heaters shall comply with UL 2523. Thermal solar water heaters shall comply with Chapter 14 and UL 174 or UL 1453. 1002.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space -heating applications shall be listed and labeled for such applications by the manufacturer and shall be installed in accordance with the manufacturer's installa- tion instructions and the International Plumbing Code. 1002.2.1 Sizing. Water heaters utilized for both potable water heating and space -heating applications shall be sized to prevent the space -heating load from diminishing the required potable water -heating capacity. 1002.2.2 Temperature limitation. Where a combination potable water -heating and space -heating system requires water for space heating at temperatures higher than 140°F (60°C), a temperature actuated mixing valve that conforms to ASSE 1017 shall be provided to temper the water sup- plied to the potable hot water distribution system to a tem- perature of 140°F (60°C) or less. 1002.3 Supplemental water -heating devices. Potable water - heating devices that utilize refrigerant -to -water heat exchang- ers shall be approved and installed in accordance with the International Plumbing Code and the manufacturer's installa- tion instructions. SECTION 1003 PRESSURE VESSELS 1003.1 General. All pressure vessels shall be in accordance with the ASME Boiler and Pressure Vessel Code, shall bear the label of an approved agency and shall be installed in accordance with the manufacturer's installation instructions. 1003.2 Piping. All piping materials, fittings, joints, connec- tions and devices associated with systems utilized in conjunc- tion with pressure vessels shall be designed for the specific application and shall be approved. 1003.3 Welding. Welding on pressure vessels shall be per- formed by approved welders in compliance with nationally recognized standards. SECTION 1004 BOILERS 1004.1 Standards. Oil -fired boilers and their control systems shall be listed and labeled in accordance with UL 726. Elec- tric boilers and their control systems shall be listed and labeled in accordance with UL 834. Solid -fuel -fired boilers shall be listed and labeled in accordance with UL 2523. Boil- ers shall be designed and constructed in accordance with the requirements of ASME CSDA and as applicable, the ASME Boiler and Pressure Vessel Code, Section I or IV; NFPA 8501; NFPA 8502 or NFPA 8504. 1004.2 Installation. In addition to the requirements of this code, the installation of boilers shall conform to the manufac- turer's instructions. Operating instructions of a permanent type shall be attached to the boiler. Boilers shall have all con- trols set, adjusted and tested by the installer. The manufac- turer's rating data and the nameplate shall be attached to the boiler. 2012 INTERNATIONAL MECHANICAL CODE® 91 I II I C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER BOILERS, WATER HEATERS AND PRESSURE VESSELS 1004.3 Working clearance. Clearances shall be maintained around boilers, generators, heaters, tanks and related equip- ment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When boilers are installed or replaced, clearance shall be provided to allow access for inspection, maintenance and repair. Passageways around all sides of boilers shall have an unobstructed width of not less than 18 inches (457 min), unless otherwise approved. 1004.3.1 Top clearance. Clearances from the tops of boil- ers to the ceiling or other overhead obstruction shall be in accordance with Table 1004.3.1. TABLE 1004.3.1 BOILER TOP CLEARANCES MINIMUM CLEARANCES FROM TOP OF BOILER TO BOILERTYPE CEILING OR OTHER OVERHEAD OBSTRUCTION (fee0 All boilers with manholes on top of the boiler except where a greater clearance is required in 3 this table. All boilers without manholes on top of the boiler except high-pressure steam boilers and 2 where a greater clearance is required in this table. High-pressure steam boilers with steam generat- ing capacity not exceeding 5,000 pounds per 3 hour. High-pressure steam boilers with steam gener- 7 ating capacity exceeding 5,000 pounds per hour. High-pressure steam boilers having heating sur- 3 face not exceeding 1,000 square feet (93 in ). High-pressure steam boilers having heating sur- 7 face in excess of 1,000 square feet (93 m't). High-pressure steam boilers with input not 3 exceeding 5,000,000 Btu/h (1465 kVv). High-pressure steam boilers with input in 7 excess of 5,000,000 Btu/h (1465 kVv). Steam -heating boilers and hot water -heating boilers with input exceeding 5,000,000 Btu/h 3 (1465 kVv). Steam -heating boilers exceeding 5,000 pounds 3 of steam per hour (2268 kg/h). Steam -heating boilers and hot water -heating boilers having heating surface exceeding 1,000 3 square feet (93 m't). For SI 1 foot= 304 8 Ern, 1 square foot - 0 0929 m', 1 pound per hour- 0 4536 Kp/h 1004.4 Mounting. Equipment shall be set or mounted on a level base capable of supporting and distributing the weight contained thereon. Boilers, tanks and equipment shall be secured in accordance with the manufacturer's installation instructions. 1004.5 Floors. Boilers shall be mounted on floors of non- combustible construction, unless listed for mounting on com- bustible flooring. 1004.6 Boiler rooms and enclosures. Boiler rooms and enclosures and access thereto shall comply with the Intema- tional Building Code and Chapter 3 of this code. Boiler rooms shall be equipped with a floor drain or other approved means for disposing of liquid waste. 1004.7 Operating adjustments and instructions. Hot water and steam boilers shall have all operating and safety controls set and operationally tested by the installing contractor. A complete control diagram and boiler operating instructions shall be furnished by the installer for each installation. SECTION 1005 BOILER CONNECTIONS 1005.1 Valves. Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple boiler or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in the supply and return piping. Exception: Shutoff valves are not required in a system having a single low-pressure steam boiler. 1005.2 Potable water supply. The water supply to all boilers shall be connected in accordance with the International Plumbing Code. SECTION 1006 SAFETY AND PRESSURE RELIEF VALVES AND CONTROLS 1006.1 Safety valves for steam boilers. All steam boilers shall be protected with a safety valve. 1006.2 Safety relief valves for hot water boilers. Hot water boilers shall be protected with a safety relief valve. 1006.3 Pressure relief for pressure vessels. All pressure vessels shall be protected with a pressure relief valve or pres- sure -limiting device as required by the manufacturer's instal- lation instructions for the pressure vessel. 1006.4 Approval of safety and safety relief valves. Safety and safety relief valves shall be listed and labeled, and shall have a minimum rated capacity for the equipment or appli- ances served. Safety and safety relief valves shall be set at a maximum of the nameplate pressure rating of the boiler or pressure vessel. 1006.5 Installation. Safety or relief valves shall be installed directly into the safety or relief valve opening on the boiler or pressure vessel. Valves shall not be located on either side of a safety or relief valve connection. The relief valve shall dis- charge by gravity. 1006.6 Safety and relief valve discharge. Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. The discharge pipe shall be the same diameter as the safety or relief valve outlet. Safety 92 2012 INTERNATIONAL MECHANICAL CODE® r I C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 100760189 oc Sep SO, 2019 o 147 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, ( �,Fod,Y.. byzoyUbdparty.oPAembmoo UoFPd Single—mly So, Pod-PyodmgFokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER BOILERS, WATER HEATERS AND PRESSURE VESSELS and relief valves shall not discharge so as to be a hazard, a potential cause of damage or otherwise a nuisance. High- pressure -steam safety valves shall be vented to the outside of the structure. Where a low-pressure safety valve or a relief valve discharges to the drainage system, the installation shall conform to the International Plumbing Code. 1006.7 Boiler safety devices. Boilers shall be equipped with controls and limit devices as required by the manufacturer's installation instructions and the conditions of the listing. 1006.8 Electrical requirements. The power supply to the electrical control system shall be from a two -wire branch cir- cuit that has a grounded conductor, or from an isolation trans- former with a two -wire secondary. Where an isolation transformer is provided, one conductor of the secondary winding shall be grounded. Control voltage shall not exceed 150 volts nominal, line to line. Control and limit devices shall interrupt the ungrounded side of the circuit. A means of man- ually disconnecting the control circuit shall be provided and controls shall be arranged so that when deenergized, the burner shall be inoperative. Such disconnecting means shall be capable of being locked in the off position and shall be provided with ready access. SECTION 1007 BOILER LOW-WATER CUTOFF 1007.1 General. All steam and hot water boilers shall be pro- tected with a low-water cutoff control. 1007.2 Operation. The low-water cutoff shall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as estab- lished by the manufacturer. SECTION 1008 STEAM BLOWOFF VALVE 1008.1 General. Every steam boiler shall be equipped with a quick -opening blowoff valve. The valve shall be installed in the opening provided on the boiler. The minimum size of the valve shall be the size specified by the boiler manufacturer or the size of the boiler blowoff-valve opening. 1008.2 Discharge. Blowoff valves shall discharge to a safe place of disposal. Where discharging to the drainage system, the installation shall conform to the International Plumbing Code. SECTION 1009 HOT WATER BOILER EXPANSION TANK 1009.1 Where required. An expansion tank shall be installed in every hot water system. For multiple boiler instal- lations, a minimum of one expansion tank is required. Expan- sion tanks shall be of the closed or open type. Tanks shall be rated for the pressure of the hot water system. 1009.2 Closed -type expansion tanks. Closed -type expan- sion tanks shall be installed in accordance with the manufac- turer's instructions. The size of the tank shall be based on the capacity of the hot -water -heating system. The minimum size of the tank shall be determined in accordance with the follow- ing equation: V _ (0.00041 T— 0.0466) Vs (Equation 10-1) (P) For SI: (0.000738 T— 0.03348) V V = (P� 11�PC where: V — Minimum volume of tanks (gallons) (L). V — Volume of system, not including expansion tanks (gallons) (L). T — Average operating temperature (OF) (OC). P — Atmospheric pressure (psi) (kPa). Pf — Fill pressure (psi) (kPa). P — Maximum operating pressure (psi) (kPa). 1009.3 Open -type expansion tanks. Open -type expansion tanks shall be located a minimum of 4 feet (1219 mm) above the highest heating element. The tank shall be adequately sized for the hot water system. An overflow with a minimum diameter of 1 inch (25 mm) shall be installed at the top of the tank. The overflow shall discharge to the drainage system in accordance with the International Plumbing Code. SECTION 1010 GAUGES 1010.1 Hot water boiler gauges. Every hot water boiler shall have a pressure gauge and a temperature gauge, or a combi- nation pressure and temperature gauge. The gauges shall indi- cate the temperature and pressure within the normal range of the system's operation. 1010.2 Steam boiler gauges. Every steam boiler shall have a water -gauge glass and a pressure gauge. The pressure gauge shall indicate the pressure within the normal range of the sys- tem's operation. 1010.2.1 Water -gauge glass. The gauge glass shall be installed so that the midpoint is at the normal boiler water level. SECTION 1011 TESTS 1011.1 Tests. Upon completion of the assembly and installa- tion of boilers and pressure vessels, acceptance tests shall be conducted in accordance with the requirements of the ASME Boiler and Pressure Vessel Code. Where field assembly of pressure vessels or boilers is required, a copy of the com- pleted U-1 Manufacturer's Data Report required by the ASME Boiler and Pressure Vessel Code shall be submitted to the code official. 2012 INTERNATIONAL MECHANICAL CODE® 93 I II I Co,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER BOILERS, WATER HEATERS AND PRESSURE VESSELS 1011.2 Test gauges. An indicating test gauge shall be con- nected directly to the boiler or pressure vessel where it is vis- ible to the operator throughout the duration of the test. The pressure gauge scale shall be graduated over a range of not less than one and one-half times and not greater than four times the maximum test pressure. All gauges utilized for test- ing shall be calibrated and certified by the test operator. 94 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,o.gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO,2019 o 147 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, Rk 4 I ( �ep4odUt. byzoyUb,dparty.oPAembmoo Uoosd Single—mly mg mpymg Pod,Pty,PFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER11 REFRIGERATION SECTION 1101 GENERAL 1101.1 Scope. This chapter shall govern the design, installa- tion, construction and repair of refrigeration systems that vaporize and liquefy a fluid during the refrigerating cycle. Refrigerant piping design and installation, including pressure vessels and pressure relief devices, shall conform to this code. Permanently installed refrigerant storage systems and other components shall be considered as part of the refrigera- tion system to which they are attached. 1101.2 Factory -built equipment and appliances. Listed and labeled self-contained, factory -built equipment and appli- ances shall be tested in accordance with UL 207, 412, 471 or 1995. Such equipmentand appliances are deemed to meet the design, manufacture and factory test requirements of this code if installed in accordance with their listing and the man- ufacturer's installation instructions. 1101.3 Protection. Any portion of a refrigeration system that is subject to physical damage shall be protected in an approved manner. 1101.4 Water connection. Water supply and discharge con- nections associated with refrigeration systems shall be made in accordance with this code and the International Plumbing Code. 1101.5 Fuel gas connection. Fuel gas devices, equipment and appliances used with refrigeration systems shall be installed in accordance with the International Fuel Gas Code. 1101.6 General. Refrigeration systems shall comply with the requirements of this code and, except as modified by this code, ASHRAE 15. Ammonia -refrigerating systems shall comply with this code and, except as modified by this code, ASHRAE 15 and IIAR 2. 1101.7 Maintenance. Mechanical refrigeration systems shall be maintained in proper operating condition, free from accu- mulations of oil, dirt, waste, excessive corrosion, other debris and leaks. 1101.8 Change in refrigerant type. The type of refrigerant in refrigeration systems having a refrigerant circuit contain- ing more than 220 pounds (99.8 kg) of Group Al or 30 pounds (13.6 kg) of any other group refrigerant shall not be changed without prior notification to the code official and compliance with the applicable code provisions for the new refrigerant type. [F] 1101.9 Refrigerant discharge. Notification of refriger- ant discharge shall be provided in accordance with the Inter- national Fire Code. 1101.10 Locking access port caps. Refrigerant circuit access ports located outdoors shall be fitted with locking -type tam- per -resistant caps or shall be otherwise secured to prevent unauthorized access. SECTION 1102 SYSTEM REQUIREMENTS 1102.1 General. The system classification, allowable refrig- erants, maximum quantity, enclosure requirements, location limitations, and field pressure test requirements shall be determined as follows: 1. Determine the refrigeration systems classification, in accordance with Section 1103.3. 2. Determine the refrigerant classification in accordance with Section 1103.1. 3. Determine the maximum allowable quantity of refriger- ant in accordance with Section 1104, based on type of refrigerant, system classification and occupancy. 4. Determine the system enclosure requirements in accor- dance with Section 1104. 5. Refrigeration equipment and appliance location and installation shall be subject to the limitations of Chapter 3. 6. Nonfactory-tested, field -erected equipment and appli- ances shall be pressure tested in accordance with Sec- tion 1108. 1102.2 Refrigerants. The refrigerant shall be that which the equipment or appliance was designed to utilize or converted to utilize. Refrigerants not identified in Table 1103.1 shall be approved before use. 1102.2.1 Mixing. Refrigerants, including refrigerant blends, with different designations in ASHRAE 34 shall not be mixed in a system. Exception: Addition of a second refrigerant is allowed where permitted by the equipment or appliance manu- facturer to improve oil return at low temperatures. The refrigerant and amount added shall be in accordance with the manufacturer's instructions. 1102.2.2 Purity. Refrigerants used in refrigeration sys- tems shall be new, recovered or reclaimed refrigerants in accordance with Section 1102.2.2.1, 1102.2.2.2 or 1102.2.2.3. Where required by the equipmentor appliance owner or the code official, the installer shall furnish a signed declaration that the refrigerant used meets the requirements of Section 1102.2.2.1, 1102.2.2.2 or 1102.2.2.3. Exception: The refrigerant used shall meet the purity specifications set by the manufacturer of the equipment or appliance in which such refrigerant is used where such specifications are different from that specified in Sections 1102.2.2.1, 1102.2.2.2 and 1102.2.2.3. 1102.2.2.1 New refrigerants. Refrigerants shall be of a purity level specified by the equipment or appliance manufacturer. 2012 INTERNATIONAL MECHANICAL CODE® 95 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,iNb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION 1102.2.2.2 Recovered refrigerants. Refrigerants that are recovered from refrigeration and air-conditioning systems shall not be reused in other than the system from which they were recovered and in other systems of the same owner. Recovered refrigerants shall be fil- tered and dried before reuse. Recovered refrigerants that show clear signs of contamination shall not be reused unless reclaimed in accordance with Section 1102.2.2.3. 1102.2.2.3 Reclaimed refrigerants. Used refrigerants shall not be reused in a different owner's equipment or appliances unless tested and found to meet the purity requirements of ARI 700. Contaminated refrigerants shall not be used unless reclaimed and found to meet the purity requirements of ARI 700. SECTION 1103 REFRIGERATION SYSTEM CLASSIFICATION 1103.1 Refrigerant classification. Refrigerants shall be clas- sified in accordance with ASHRAE 34 as listed in Table 1103.1. 1103.2 Occupancy classification. Locations of refrigerating systems are described by occupancy classifications that con- sider the ability of people to respond to potential exposure to refrigerants. Where equipmentor appliances, other than pip- ing, are located outside a building and within 20 feet (6096 mm) of any building opening, such equipment or appliances shall be governed by the occupancy classification of the building. Occupancy classifications shall be defined as fol- lows: 1. Institutional occupancy is that portion of premises from which, because they are disabled, debilitated or con- fined, occupants cannot readily leave without the assis- tance of others. Institutional occupancies include, among others, hospitals, nursing homes, asylums and spaces containing locked cells. 2. Public assembly occupancyis that portion of premises where large numbers of people congregate and from which occupants cannot quickly vacate the space. Pub- lic assembly occupancies include, among others, audi- toriums, ballrooms, classrooms, passenger depots, restaurants and theaters. 3. Residential occupancyis that portion of premises that provides the occupants with complete independent liv- ing facilities, including permanent provisions for liv- ing, sleeping, eating, cooking and sanitation. Residential occupancies include, among others, dormi- tortes, hotels, multiunit apartments and private resi- dences. 4. Commercial occupancy is that portion of premises where people transact business, receive personal ser- vice or purchase food and other goods. Commercial occupancies include, among others, office and profes- sional buildings, markets (but not large mercantile occupancies) and work or storage areas that do not qualify as industrial occupancies. 5. Large mercantile occupancyis that portion of premises where more than 100 persons congregate on levels above or below street level to purchase personal mer- chandise. 6. Industrial occupancy is that portion of premises that is not open to the public, where access by authorized per- sons is controlled, and that is used to manufacture, pro- cess or store goods such as chemicals, food, ice, meat or petroleum. 7. Mixed occupancy occurs when two or more occupan- cies are located within the same building. When each occupancy is isolated from the rest of the building by tight walls, floors and ceilings and by self closing doors, the requirements for each occupancyshall apply to its portion of the building. When the various occu- pancies are not so isolated, the occupancy having the most stringent requirements shall be the governing occupancy. 1103.3 System classification. Refrigeration systems shall be classified according to the degree of probability that refriger- ant leaked from a failed connection, seal or component could enter an occupied area. The distinction is based on the basic design or location of the components. 1103.3.1 Low -probability systems. Double -indirect open -spray systems, indirect closed systems and indirect - vented closed systems shall be classified as low -probabil- ity systems, provided that all refrigerant -containing piping and fittings are isolated when the quantities in Table 1103.1 are exceeded. 1103.3.2 High -probability systems. Direct systems and indirect open -spray systems shall be classified as high - probability systems. Exception: An indirect open -spray system shall not be required to be classified as a high -probability system if the pressure of the secondary coolant is at all times (operating and standby) greater than the pressure of the refrigerant. 96 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I IT odUto.. by POVOtput, I,ANb�to,P,,UoFsd Single—mly So, Pod oNyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRTRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER [F] TABLE 1103.1 REFRIGERANT CLASSIFICATION, AMOUNT AND DEL CHEMICAL REFRIGERANT FORMULA CHEMICAL NAME OF BLEND REFRIGERANT CLASSIFICATION DEGREES OF HAZARDa [MI AMOUNT OF REFRIGERANT PER OCCUPIED SPACE Pounds per 1,000 cubic feet PPm glm' OEL` R-11' CC13E trichlorofluoromethane Al 2-0-06 0.39 1,100 6.2 C1,000 R-12' CCI,F, dichlorodifluoromethane Al 2-0-06 5.6 18,000 90 1,000 R-13' CC1E3 chlorotrifluoromethane Al 2-0-06 1,000 R-13B1° CBrE3 bromotrifluoromethane Al 2-0-06 1,000 R-14 CEq tetrafluoromethane (carbon tetrafluoride) Al 2-0-06 25 110,000 400 1,000 R-22 CHC1Ez chlorodifluoromethane Al 2-0-06 13 59,000 210 1,000 R-23 CHE3 trifluoromethane (fluoroform) Al 2-0-06 7.3 41,000 120 1,000 R-32 CHrEr difluoromethane (methylene fluoride) A2 4.8 36,000 77 1,000 R-113° CC12ECC1E2 1,1,2-tichloro-1,2,2-trifluoroethane Al 2-0-06 1.2 2,600 20 1,000 R-114' CC1E2CC1E2 1,2-dichloro-1,2,2-tetrafluoroethane Al 2-0-06 8.7 20,000 140 1,000 R-115 CC1E2CE3 chloropentafluoroethane Al 47 120,000 760 1,000 R-116 CE3CE3 hexafluoroethane Al 1-0-0 34 97,000 550 1,000 R-123 CHC12CE3 2,2-dichloro-1,1,1-trifluoroethane B1 2-0-06 3.5 9,100 57 50 R-124 CHCIECE3 2-chloro-1,1,1,2-tetrafluoroethane Al 2-0-06 3.5 10,000 56 1,000 R-125 CHE2CE3 pentafluoroethane Al 2-0-06 23 75,000 370 1,000 R-134a CH2ECE3 1,1,1,2-tetrafluoroethane Al 2-0-06 13 50,000 210 1,000 R-141b CH3CC12E 1,1-dichloro-l-fluoroethane 0.78 2,600 12 500 R-142b CH3CC1E2 1-chloro-1,1-difluoroethane A2 5.1 20,000 83 1,000 R-143a CH3CE3 1,1,1-trifluoroethane A2 2-0-06 4.5 21,000 70 1,000 R-152a CH3CHE2 1,1-difluorethane A2 1-4-0 2 12,000 32 1,000 R-170 CH3CH3 ethane A3 2-4-0 0.54 7,000 8.7 1,000 R-E170 CH30CH3 Methoxymethane (dimethyl ether) A3 1 8,500 16 1,000 R-218 CE3CE2CE3 octafluoropropane Al 2-0-06 43 90,000 690 1,000 R-227ea CE3CHECE3 1, 1, 1,2,3,3,3-heptafluoropropane Al 36 84,000 580 1,000 R-236fa CE3CH2CE3 1, 1, 1,3,3,3-hexafluoropropane Al 2-0-06 21 55,000 340 1,000 R-245fa CHE2CH2CE3 11,1,1,3,3-pentafluoropropane B1 2-0-06 12 34,000 190 300 R-290 CH3CH2CH3 propane A3 2-4-0 0.56 5,300 9.5 1 1,000 R-C318 I -(CE)q I octafluorocyclobutane I Al 41 80,000 1 660 1 1,000 (continued) A m m m m A D 0 z m [F] TABLE 1103.1-continued REFRIGERANT CLASSIFICATION, AMOUNT AND DEL CHEMICAL REFRIGERANT FORMULA CHEMICAL NAME OF BLEND REFRIGERANT CLASSIFICATION DEGREES OF HAZARDa [M] AMOUNT OF REFRIGERANT PER OCCUPIED SPACE Pounds per 1,000 cubic feet ppm g/m' OEL` R400° zeotrope R-12/114 (50/50) Al 2-0-06 10 28,000 160 1,000 R-400° zeotrope R-12/114 (60/40) Al 11 30,000 170 1,000 R-401A zeotrope R-22/152a/124 (53/13/34) Al 2-0-06 6.6 27,000 110 1,000 R-401B zeotrope R-22/152a/124 (61/11/28) Al 2-0-06 7.2 30,000 120 1,000 R-401C zeotrope R-22/152a/124 (33/15/52) Al 2-0-06 15.2 20,000 84 1,000 R-402A zeotrope R-125/290/22 (60/2/38) Al 2-0-06 8.5 33,000 140 1,000 R-402B zeotrope R-125/290/22 (38/2/60) Al 2-0-06 15 63,000 240 1,000 R-403A zeotrope R-290/22/218 (5.0/75.0/20.0) A2 2-0-06 7.6 33,000 120 1,000 R-403B zeotrope R-290/22/218 (5/56/39) Al 2-0-06 18 70,000 290 1,000 R-404A zeotrope R-125/143a/134a (44/52/4) Al 2-0-06 31 130,000 500 1,000 R-405A zeotrope R-22/152a/142b/C318 (45.0/7.0/5.5/2.5) 16 57,000 260 1,000 R-406A zeotrope R-22/600a/142b (55/4/41) A2 4.7 21,000 25 1,000 R-407A zeotrope R-32/125/134a (20/40/40) Al 2-0-06 18 78,000 290 1,000 R-407B zeotrope R-32/125/134a (10/70/20) Al 2-0-06 20 77,000 320 1,000 R-407C zeotrope R-32/125/134a (23/25/52) Al 2-0-06 17 76,000 270 1,000 R-407D zeotrope R-32/125/134a (15/15/70) Al 2-0-06 15 65,000 240 1,000 R-407E zeotrope R-32/125/134a (25/15/60) Al 2-0-06 16 75,000 260 1,000 R-408A zeotrope R-125/143a/22 (7/46/47) Al 2-0-06 21 95,000 340 1,000 R-409A zeotrope R-22/124/142b (60/25/15) Al 2-0-06 7.1 29,000 110 1,000 R-409B zeotrope R-22/124/142b (65/25/10) Al 2-0-06 7.3 30,000 120 1,000 R-410A zeotrope R-32/125 (50/50) Al 2-0-06 25 130,000 390 1,000 R-410B zeotrope R-32/125 (45/55) Al 2-0-06 24 130,000 390 1,000 R-411A zeotrope R-127/22/152a (1.5/87.5/11.0) A2 2.9 14,000 46 990 R-411B zeotrope R-1270/22/152a (3/94/3) A2 2.8 13,000 45 980 R-412A zeotrope R-22/318/142b (70/5/25) A2 5.1 22,000 82 1,000 R-413A zeotrope R-218/134a/600a (9/88/3) A2 5.8 22,000 94 1,000 R-414A zeotrope R-22/124/600a/142b (51/28.5/4/16.5) Al 6.4 26,000 100 1,000 R-414B zeotrope R-22/124/600a/142b (50/39/1.5/9.5) Al 6 23,000 95 1,000 (continued) A m A O A D zz REFRIGERATION w V J o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O a 0 0 0 0 O O O O O O O O O O O o 0 0 0 0 0 0 0 0 0 0 w a VO O N 0 0 00 0 0 0 0 0 0 0 0 („ ) O O M ti ,ti \[J ,ti ep O ti O 0 E m So,O .� m W M m LSJ m CES .� O LSJ W 1 N N LSJ W CO N W W pI N M N M N N N N M N N M M W a z o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 c0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o 0 00 0 0 0� O o 0 w o 0 0 0 0 0 0 0 0 0 0 0 0_ o 0 0 0 0 0 or,0 o� o 0 0 0 M m O o[J .� m M CE) N W m M t` D CO M CO W LSJ M C M M W C C ' 6J 6J LSJ LSJ LSJ l� C CO CO CO N CO LSJ LSJ N CO N L` W � LL W � 0 p O F O Z - a m Q a N M M LSJ M mN L` .ti W CO W CO 6J N CO N W M F M M M LSJ O LSJ LSJ 6J 1� 9= ^ 6J M M N W CO _ C � " a u o a OA 0 W K o 0 0 0 0 0 0 0 0 0 0 0 W H O O O O O O O O O O O O = N N N N N N N N N N N N W 0 z ¢KFzo W¢ N N ti ti N N ti ti ti ti ti ti ti ti ti ti ti ti ti M M M M M M M ti M M M ti ti Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi Qi aLL �O wa �U co m o o O N 0 t` M O CO C yZj .ti O S O N C O �cJ \ O \ 0 0 \ CD p] C O O L p O M cO LCJ C 7t LL 7' M M M M S!J O Lp ON O W L5 W�cJ IiJ O LCJ O O L�J �\cJ N O ti N 6J a N ti a N a 6D O p `ti W W 4 Lp O \ ti C �p cO �p O p 'ti p 6D Z O '—' \ O \ O t` \ LCJ O^ \ N M cO O O O O O O O p 0 0 0 W In N LCJ M N (J OO O I J .�� C .� OO W cO I J cO C O N C C O O .� O W O 2 O O N O O O O O l� O m 6D .�_. `,S O N O U Nj W LCJ CO CO N W CO CO CO CO CO N CO M N p �. R �. N Lip N a N N N N A N O N �_ O O O N N N N N C N C C N C C C C C C 4t So, 4t a 4t M O O O SPAOJ OJ OJ M� O O C SPA SPAM SPA M M M M M M So,M C M O O M L[J L[J L[J .ti N .ti .ti .ti .ti .ti .ti .ti .ti M .ti N .ti ti O O O O .ticz) CO CO .ti N N N C M LCJ N O 0' LCJ N C M LCJ N LCJ N LCJ N LCJ N LCJ N LCJ N C M LCJ N N LCJ N N LCJ N l� `� N N Lp O 6J . N . N . N . N LCJ N C` `� O 6J O 6J LCJ N N N N N M M [Z] N [Z] N N M �i �i �i �i �i �i �i �i �i �i g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C C C C C C C C 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 K o 0 0 0 0 0 0 0 0 0 0 0 0 0 o SO SO SO 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N N N N N N N N N N N N N N N N SO SO SON N N N N N N N N SIDSID N N LL Z :: W LSJ LSJ CO W 6J O ti N N N N M C LSJ Cp L` W 6J O N M M M C LSJ Cp Cp L` W .ti ti .ti .ti .ti .ti N N N N N N N N N N N N N N M M M M M M M M M M M M W — C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C U 2012 INTERNATIONAL MECHANICAL CODE® 99 I " ' Co,gbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx1oovco189 oc Sep so.2.o19 o 147 PM(PDT) pwmmtto IL eAg—mt,oUICC No FYUP,,eplodmeoo.00 AYUP, (,eFodmYo¢ebymytl,dputy,o,ANb,to,au o,sd Smglo—mlympymg mdortuodmg F oARItAd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION 0 z z az 0 �O c � c¢ UZ �2 oU � LL JN mg �U �z z 0 W W J o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o 0 0 0� O O O O O O O O O O O O O O O O O N O O O O ¢or, O LYS a N 0 W O O O O O OI SIG LYS SIG a z o 0 0 0 w E o 0 0 c� o 0 0 0 0 0 0 0 0 0 O O O- M 0- O O D O LL 6 0 SIGLSJ C M I � M LYS N- LYS I � � SIG C O O Z m a 0 ME,CO M .� N 6J N N SIG C M C N W •� CO N N ti LP Q N a L� .� .� O 0 0 0 0 yi yi p 9 O u OA 0 W K O O O O O O O O O O O p N ti W 0 z Z¢O SE (� LL w¢ �U z z J m N O � N N OJ W � O ZIn N O O N O W O O SS .^i O J Q N LP .ti LP W 6J L�LJ LP N L[J 0 ti CO LP Ea LP W N G O Ni %� '2 SIGN L� W ti W OJ CO C m O. G m SO O O N LP LP � Cp Cp W CO j� .0 u SO SIG Z N N N N M N N M OrS N M N M N N N .-. E4 m N E 2 N E E' u M SON Qi Qi Qi :4 Qi Qi :4 :4 Q4 Q4 d N N L N E m U N N Q+ � O x x O 5 d d SO SO SO SO d d d d U U x x O O O II II iiN w x O LL N N N N N N N N N N N N N N N U �i U U rTi rTi rTi � x � U ¢z Q Q� Q� W Q� Q� O m O C O O O O O O O O OGE) z t o o d b�0 C 9 9_ S _ W F O q C L_ 9 `o k U d 9 °c 9 O d c „n G' L L C ¢ b0 H? 00 o � O � O 3 c E_ 2 c 0 c � o m � m 0 0 � E w E � 6 r� x 3� ¢ L C 9 L ¢ > ra � p Y 9 G C t V ¢ O a O d W O ti ¢ ME __ M x M V coom _ dc0 O � o T O O o > c c m b» � 0 0 o k CE It C O N O y It "'carzrw°�opr `o 100 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO,2019 o 1 av PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, L I ( riR�ep�od Uto.. bymyUb,dpPLP,o[dlembmo—Uoosd Single—mly mpymg Pod-Pyodmg FokbSted ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION SECTION 1104 SYSTEM APPLICATION REQUIREMENTS 1104.1 General. The refrigerant, occupancyand system clas- sification cited in this section shall be determined in accor- dance with Sections 1103.1, 1103.2 and 1103.3, respectively. For refrigerant blends assigned dual classifications, as formu- lated and for the worst case of fractionation, the classifica- tions for the worst case of fractionation shall be used. 1104.2 Machinery room. Except as provided in Sections 1104.2.1 and 1104.2.2, all components containing the refrig- erant shall be located either outdoors or in a machineryroom where the quantity of refrigerant in an independent circuit of a system exceeds the amounts shown in Table 1103.1. For refrigerant blends not listed in Table 1103.1, the same requirement shall apply when the amount for any blend com- ponent exceeds that indicated in Table 1103.1 for that compo- nent. This requirement shall also apply when the combined amount of the blend components exceeds a limit of 69,100 parts per million (ppm) by volume. Machinery rooms required by this section shall be constructed and maintained in accordance with Section 1105 for Group At and BI refrig- erants and in accordance with Sections 1105 and 1106 for Group A2, B2, A3 and B3 refrigerants. Exceptions: 1. Machinery rooms are not required for listed equip- ment and appliances containing not more than 6.6 pounds (3 kg) of refrigerant, regardless of the refrig- erant's safety classification, where installed in accor- dance with the equipment's or appliance's listing and the equipment or appliance manufacturer's installation instructions. 2. Piping in conformance with Section 1107 is allowed in other locations to connect components installed in a machineryroom with those installed outdoors. 1104.2.1 Institutional occupancies. The amounts shown in Table 1103.1 shall be reduced by 50 percent for all areas of institutional occupancies except kitchens, labora- tories and mortuaries. The total of all Group A2, B2, A3 and B3 refrigerants shall not exceed 550 pounds (250 kg) in occupied areas or machinery rooms. 1104.2.2 Industrial occupancies and refrigerated rooms. This section applies only to industrial occupancies and refrigerated rooms for manufacturing, food and bever- age preparation, meat cutting, other processes and storage. Machinery rooms are not required where all of the follow- ing conditions are met: 1. The space containing the machinery is separated from other occupancies by tight construction with tight -fitting doors. 2. Access is restricted to authorized personnel. 3. The floor area per occupant is not less than 100 square feet (9.3 m') where machinery is located on floor levels with exits more than 6.6 feet (2012 mm) above the ground. Where provided with egress directly to the outdoors or into approved building exits, the minimum floor area shall not apply. 4. Refrigerant detectors are installed as required for machinery rooms in accordance with Section 1105.3. 5. Surfaces having temperatures exceeding 800°F (427°C) and open flames are not present where any Group A2, B2, A3 or B3 refrigerant is used (see Section 1104.3.4). 6. All electrical equipment and appliances conform to Class 1, Division 2, hazardous location classifica- tion requirements of NFPA 70 where the quantity of any Group A2, B2, A3 or B3 refrigerant, other than ammonia, in a single independent circuit would exceed 25 percent of the lower flammability limit (-FL) upon release to the space. 7. All refrigerant -containing parts in systems exceed- ing 100 horsepower (hp) (74.6 kW) drive power, except evaporators used for refrigeration or dehu- midification; condensers used for heating; control and pressure relief valves for either; and connecting piping, shall be located either outdoors or in a machineryroom. 1104.3 Refrigerant restrictions. Refrigerant applications, maximum quantities and use shall be restricted in accordance with Sections 1104.3.1 through 1104.3.4. 1104.3.1 Air-conditioning for human comfort. In other than industrial occupancies where the quantity in a single independent circuit does not exceed the amount in Table 1103.1, Group Bl, B2 and B3 refrigerants shall not be used in high -probability systems for air-conditioning for human comfort. 1104.3.2 Nonindustrial occupancies. Group A2 and B2 refrigerants shall not be used in high -probability systems where the quantity of refrigerant in any independent refrigerant circuit exceeds the amount shown in Table 1104.3.2. Group A3 and B3 refrigerants shall not be used except where approved. Exception: This section does not apply to laboratories where the floor area per occupant is not less than 100 square feet (9.3 m'). 1104.3.3 All occupancies. The total of all Group A2, B2, A3 and B3 refrigerants other than R-717, ammonia, shall not exceed 1,100 pounds (499 kg) except where approved. 1104.3.4 Protection from refrigerant decomposition. Where any device having an open flame or surface tem- perature greater than 800°F (427°C) is used in a room con- taining more than 6.6 pounds (3 kg) of refrigerant in a single independent circuit, a hood and exhaust system shall be provided in accordance with Section 510. Such exhaust system shall exhaust combustion products to the outdoors. Exception: A hood and exhaust system shall not be required: 1. Where the refrigerant is R-717, R-718 or R-744; 2. Where the combustion air is ducted from the out- doors in a manner that prevents leaked refrigerant from being combusted; or 2012 INTERNATIONAL MECHANICAL CODE® 101 I II I C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION 3. Where a refrigerant detector is used to stop the combustion in the event of a refrigerant leak (see Sections 1105.3 and 1105.5). 1104.4 Volume calculations. Volume calculations shall be in accordance with Sections 1104.4.1 through 1104.4.3. 1104.4.1 Noncommunicating spaces. Where the refriger- ant -containing parts of a system are located in one or more spaces that do not communicate through permanent open- ings or HVAC ducts, the volume of the smallest, enclosed occupied space shall be used to determine the permissible quantity of refrigerant in the system. 1104.4.2 Communicating spaces. Where an evaporator or condenser is located in an air duct system, the volume of the smallest, enclosed occupied space served by the duct system shall be used to determine the maximum allowable quantity of refrigerant in the system. Exception: If airflow to any enclosed space cannot be reduced below one -quarter of its maximum, the entire space served by the air duct system shall be used to determine the maximum allowable quantity of refriger- ant in the system. 1104.4.3 Plenums. Where the space above a suspended ceiling is continuous and part of the supply or return air plenum system, this space shall be included in calculating the volume of the enclosed space. SECTION 1105 MACHINERY ROOM, GENERAL REQUIREMENTS [B] 1105.1 Design and construction. Machinery rooms shall be designed and constructed in accordance with the Interna- tional Building Code and this section. 1105.2 Openings. Ducts and air handlers in the machinery room that operate at a lower pressure than the room shall be sealed to prevent any refrigerant leakage from entering the airstream. [F] 1105.3 Refrigerant detector. Refrigerant detectors in machinery rooms shall be provided as required by Section 606.8 of the International Fire Code. 1105.4 Tests. Periodic tests of the mechanical ventilating system shall be performed in accordance with manufacturer's specifications and as required by the code official. 1105.5 Fuel -burning appliances. Fuel -burning appliances and equipment having open flames and that use combustion air from the machinery room shall not be installed in a machineryroom. Exceptions: 1. Where the refrigerant is carbon dioxide or water. 2. Fuel -burning appliances shall not be prohibited in the same machinery room with refrigerant-contain- Ing equipment or appliances where combustion air is ducted from outside the machinery room and sealed in such a manner as to prevent any refrigerant leak- age from entering the combustion chamber, or where a refrigerant vapor detector is employed to automati- cally shut off the combustion process in the event of refrigerant leakage. 1105.6 Ventilation. Machinery rooms shall be mechanically ventilated to the outdoors. Exception: Where a refrigerating system is located out- doors more than 20 feet (6096 mm) from any building opening and is enclosed by a penthouse, lean-to or other open structure, natural or mechanical ventilation shall be provided. Location of the openings shall be based on the relative density of the refrigerant to air. The free -aperture cross section for the ventilation of the machinery room shall be not less than: F = FG (Equation 11-1) For SI: F = 0 138 FG where: F = The free opening area in square feet (m'). G = The mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machineryroom. 1105.6.1 Discharge location. The discharge of the air shall be to the outdoors in accordance with Chapter 5. Exhaust from mechanical ventilation systems shall be dis- charged not less than 20 feet (6096 mm) from a property line or openings into buildings. 1105.6.2 Makeup air. Provisions shall be made for makeup air to replace that being exhausted. Openings for makeup air shall be located to avoid intake of exhaust air. Supply and exhaust ducts to the machinery room shall serve no other area, shall be constructed in accordance with Chapter 5 and shall be covered with corrosion -resis- tant screen of not less than '/q inch (6.4 min) mesh. TABLE 1104.3.2 MAXIMUM PERMISSIBLE QUANTITIES OF REFRIGERANTS TYPE OF REFRIGERATION SYSTEM MAXIMUM POUNDS FOR VARIOUS OCCUPANCIES Institutional Assembly Residential All other occupancies Sealed absorption system In exit access 0 0 3.3 3.3 In adjacent outdoor locations 0 0 22 22 In other than exit access 0 6.6 6.6 6.6 Unit systems In other than exit access 0 0 6.6 6.6 For SI 1 pound - 0 454 kg 102 2012 INTERNATIONAL MECHANICAL CODE® Cop IYEIL @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 100760189 oc Sep SO, 2019 o 147 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( lig �,FodUt .. byzoyUbdparty.oPAembmoo UoFPd Single—oPIA mpymg PodortxodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,EDERAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION 1105.6.3 Ventilation rate. For other than ammonia sys- tems, the mechanical ventilation systems shall be capable of exhausting the minimum quantity of air both at normal operating and emergency conditions, as required by Sec- tions 1105.6.3.1 and 1105.6.3.2. The minimum required ventilation rate for ammonia shall be 30 air changes per hour in accordance with IIAR2. Multiple fans or multispeed fans shall be allowed to produce the emergency ventilation rate and to obtain a reduced airflow for normal ventilation. 1105.6.3.1 Quantity —normal ventilation. During occupied conditions, the mechanical ventilation system shall exhaust the larger of the following: 1. Not less than 0.5 cfm per square foot (0.0025 m3/ s . m') of machinery room area or 20 cfm (0.009 m3/s) per person; or 2. A volume required to limit the room temperature rise to MAT (10°C) taking into account the ambi- ent heating effect of all machinery in the room. 1105.6.3.2 Quantityemergencyconditions. Upon actuation of the refrigerant detector required in Section 1105.3, the mechanical ventilation system shall exhaust air from the machinery room in the following quantity: Q = 100 x FG (Equation 11-2) For SI: Q = 0.07 x r where: Q = The airflow in cubic feet per minute (m3/s). G = The design mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room. 1105.7 Termination of relief devices. Pressure relief devices, fusible plugs and purge systems located within the machinery room shall terminate outside of the structure at a location not less than 15 feet (4572 mm) above the adjoining grade level and not less than 20 feet (6096 mm) from any window, ventilation opening or exit. 1105.8 Ammonia discharge. Pressure relief valves for ammonia systems shall discharge in accordance with ASHRAE 15. [F] 1105.9 Emergency pressure control system. Refrigera- tion systems containing more than 6.6 pounds (3 kg) of flam- mable, toxic or highly toxic refrigerant or ammonia shall be provided with an emergency pressure control system in accordance with Section 606.10 of the International Fire Code. SECTION 1106 MACHINERY ROOM, SPECIAL REQUIREMENTS 1106.1 General. Where required by Section 11011.2, the machineryroom shall meet the requirements of this section in addition to the requirements of Section 1105. 1106.2 Elevated temperature. There shall not be an open flame -producing device or continuously operating hot surface over 800°F (427°C) permanently installed in the room. 1106.3 Ammonia room ventilation. Ventilation systems in ammonia machinery rooms shall be operated continuously at the emergency ventilation rate determined in accordance with Section 1105.6.3.2. Exceptions: 1. Machinery rooms equipped with a vapor detector that will automatically start the ventilation system at the emergency rate determined in accordance with Section 1105.6.3.2, and that will actuate an alarm at a detection level not to exceed 1,000 ppm; or 2. Machinery rooms conforming to the Class 1, Divi- sion 2, hazardous location classification require- ments of NFPA 70. 1106.4 Flammable refrigerants. Where refrigerants of Groups A2, A3, B2 and B3 are used, the machinery room shall conform to the Class 1, Division 2, hazardous location classification requirements of NFPA 70. Exception: Ammonia machinery rooms that are provided with ventilation in accordance with Section 1106.3. [F] 1106.5 Remote controls. Remote control of the mechani- cal equipment and appliances located in the machinery room shall comply with Sections 1106.5.1 and 1106.5.2. [F] 1106.5.1 Refrigeration system emergency shutoff. A clearly identified switch of the break -glass type or with an approved tamper -resistant cover shall provide off only control of refrigerant compressors, refrigerant pumps, and normally closed, automatic refrigerant valves located in the machinery room. Additionally, this equipment shall be automatically shut off whenever the refrigerant vapor con- centration in the machinery room exceeds the vapor detec- tor's upper detection limit or 25 percent of the LEL, whichever is lower. [F] 1106.5.2 Ventilation system. A clearly identified switch of the break -glass type shall provide on -only con- trol of the machinery room ventilation fans. [F] 1106.6 Emergency signs and labels. Refrigeration units and systems shall be provided with approved emergency signs, charts, and labels in accordance with the International Fire Code. SECTION 1107 REFRIGERANT PIPING 1107.1 General. All refrigerant piping shall be installed, tested and placed in operation in accordance with this chap- ter. 1107.2 Piping location. Refrigerant piping that crosses an open space that affords passageway in any building shall be not less than 7 feet 3 inches (2210 mm) above the floor unless the piping is located against the ceiling of such space. Refrig- erant piping shall not be placed in any elevator, dumbwaiter or other shaft containing a moving object or in any shaft that has openings to living quarters or to means of egress. Refrig- erant piping shall not be installed in an enclosed public stair- way, stair landing or means of egress. 2012 INTERNATIONAL MECHANICAL CODE® 103 I II I Copy,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION 1107.2.1 Piping in concrete floors. Refrigerant piping installed in concrete floors shall be encased in pipe ducts. The piping shall be isolated and supported to prevent dam- aging vibration, stress and corrosion. 1107.2.2 Refrigerant penetrations. Refrigerant piping shall not penetrate floors, ceilings or roofs. Exceptions: 1. Penetrations connecting the basement and the first floor. 2. Penetrations connecting the top floor and a machinery penthouse or roof installation. 3. Penetrations connecting adjacent floors served by the refrigeration system. 4. Penetrations by piping in a direct system where the refrigerant quantity does not exceed Table 1103.1 for the smallest occupied space through which the piping passes. 5. In other than industrial occupancies and where the refrigerant quantity exceeds Table 1103.1 for the smallest space, penetrations for piping that connects separate pieces of equipment that are either: 5.1. Enclosed by an approved gas -tight, fire - resistive duct or shaft with openings to those floors served by the refrigeration system or 5.2. Located on the exterior of the building where vented to the outdoors or to the space served by the system and not used as an air shaft, closed court or similar space. 1107.3 Pipe enclosures. Rigid or flexible metal enclosures or pipe ducts shall be provided for soft, annealed copper tubing and used for refrigerant piping erected on the premises and containing other than Group Al or B1 refrigerants. Enclo- sures shall not be required for connections between condens- ing units and the nearest riser busies), provided such connections do not exceed 6 feet (1829 mm) in length. 1107.4 Condensation. All refrigerating piping and fittings, brine piping and fittings that, during normal operation, will reach a surface temperature below the dew point of the sur- rounding air, and are located in spaces or areas where con- densation will cause a safety hazard to the building occupants, structure, electrical equipmentor any other equip - mentor appliances, shall be protected in an approved manner to prevent such damage. 1107.5 Materials for refrigerant pipe and tubing. Piping materials shall be as set forth in Sections 1107.5.1 through 1107.5.5. 1107.5.1 Steel pipe. Carbon steel pipe with a wall thick- ness not less than Schedule 80 shall be used for Group A2, A3, B2 or B3 refrigerant liquid lines for sizes 1.5 inches (38 mm) and smaller. Carbon steel pipe with a wall thick- ness not less than Schedule 40 shall be used for Group At or BI refrigerant liquid lines 6 inches (152 mm) and smaller, Group A2, A3, B2 or B3 refrigerant liquid lines sizes 2 inches (51 mm) through 6 inches (152 mm) and all refrigerant suction and discharge lines 6 inches (152 mm) and smaller. Type F steel pipe shall not be used for refrig- erant lines having an operating temperature less than -20°F (-29°C). 1107.5.2 Copper and brass pipe. Standard iron -pipe size, copper and red brass (not less than 80-percent copper) pipe shall conform to ASTM B 42 and ASTM B 43. 1107.5.3 Copper tube. Copper tube used for refrigerant piping erected on the premises shall be seamless copper tube of Type ACR (hard or annealed) complying with ASTM B 280. Where approved, copper tube for refriger- ant piping erected on the premises shall be seamless cop- per tube of Type K, L or M (drawn or annealed) in accordance with ASTM B 88. Annealed temper copper tube shall not be used in sizes larger than a 2-inch (51 mm) nominal size. Mechanical joints shall not be used on annealed temper copper tube in sizes larger than '/e inch (22.2 mm) OD size. 1107.5.4 Copper tubing joints. Copper tubing joints used in refrigerating systems containing Group A2, A3, B2 or B3 refrigerants shall be brazed. Soldered joints shall not be used in such refrigerating systems. 1107.5.5 Aluminum tube. Type 3003-0 aluminum tubing with high-pressure fittings shall not be used with methyl chloride and other refrigerants known to attack aluminum. 1107.6 Joints and refrigerant -containing parts in air ducts. Joints and all refrigerant -containing parts of a refriger- ating system located in an air duct of an air-conditioning sys- tem carrying conditioned air to and from human -occupied space shall be constructed to withstand, without leakage, a pressure of 150 percent of the higher of the design pressure or pressure relief device setting. 1107.7 Exposure of refrigerant pipe joints. Refrigerant pipe joints erected on the premises shall be exposed for visual inspection prior to being covered or enclosed. 1107.8 Stop valves. All systems containing more than 6.6 pounds (3 kg) of a refrigerant in systems using positive -dis- placement compressors shall have stop valves installed as fol- lows: 1. At the inlet of each compressor, compressor unit or condensing unit. 2. At the discharge outlet of each compressor, compressor unit or condensing unit and of each liquid receiver. Exceptions 1. Systems that have a refrigerant pumpout function capable of storing the entire refrigerant charge in a receiver or heat exchanger. 2. Systems that are equipped with provisions for pumpout of the refrigerant using either portable or permanently installed recovery equipment. 3. Self-contained systems. 1107.8.1 Liquid receivers. All systems containing 100 pounds (45 kg) or more of a refrigerant, other than systems utilizing nonpositive displacement compressors, shall 104 2012 INTERNATIONAL MECHANICAL CODE® riRC,gbt@ ON I ICC ALL RIGHTS RESERVED A-P—d by ().(-)O,d,,Nmmbsx/00760/89 oc SIP SO, 20/90/47 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I ( �ep4odUto.. by POVOtput, I,ANbs �to,P,,UoFd Single—mly mpymg Pod oNyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE TRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFRIGERATION have stop valves, in addition to those required by Section 1107.8, on each inlet of each liquid receiver. Stop valves shall not be required on the inlet of a receiver in a con- densing unit, nor on the inlet of a receiver which is an inte- gral part of the condenser. 1107.8.2 Copper tubing. Stop valves used with soft annealed copper tubing or hard -drawn copper tubing °/e inch (22.2 mm) OD standard size or smaller shall be securely mounted, independent of tubing fastenings or supports. 1107.8.3 Identification. Stop valves shall be identified where their intended purpose is not obvious. Numbers shall not be used to label the valves, unless a key to the numbers is located near the valves. SECTION 1108 FIELD TEST 1108.1 General. Every refrigerant -containing part of every system that is erected on the premises, except compressors, condensers, vessels, evaporators, safety devices, pressure gauges and control mechanisms that are listed and factory tested, shall be tested and proved tight after complete installa- tion, and before operation. Tests shall include both the high - and low-pressure sides of each system at not less than the lower of the design pressures or the setting of the pressure relief device(s). The design pressures for testing shall be those listed on the condensing unit, compressor or compres- sor unit nameplate, as required by ASHRAE 15. Exceptions: 1. Gas bulk storage tanks that are not permanently con- nected to a refrigeration system. 2. Systems erected on the premises with copper tubing not exceeding % inch (15.8 mm) OD, with wall thickness as required by ASHRAE 15, shall be tested in accordance with Section 1108.1, or by means of refrigerant charged into the system at the saturated vapor pressure of the refrigerant at MAT (21 A or higher. 3. Limited -charge systems equipped with a pressure relief device, erected on the premises, shall be tested at a pressure not less than one and one-half times the pressure setting of the relief device. If the equipment or appliance has been tested by the manufacturer at one and one-half times the design pressure, the test after erection on the premises shall be conducted at the design pressure. 1108.1.1 Booster compressor. Where a compressor is used as a booster to obtain an intermediate pressure and discharges into the suction side of another compressor, the booster compressor shall be considered a part of the low side, provided that it is protected by a pressure relief device. 1108.1.2 Centrifugal/nonpositive displacement com- pressors. In field-testing systems using centrifugal or other nonpositive displacement compressors, the entire system shall be considered as the low -side pressure for field test purposes. 1108.2 Test gases. Tests shall be performed with an inert dried gas including, but not limited to, nitrogen and carbon dioxide. Oxygen, air, combustible gases and mixtures con- taining such gases shall not be used. Exception: The use of air is allowed to test R-717, ammo- nia, systems provided that they are subsequently evacu- ated before charging with refrigerant. 1108.3 Test apparatus. The means used to build up the test pressure shall have either a pressure -limiting device or a pres- sure -reducing device and a gauge on the outlet side. 1108.4 Declaration. A certificate of test shall be provided for all systems containing 55 pounds (25 kg) or more of refriger- ant. The certificate shall give the name of the refrigerant and the field test pressure applied to the high side and the low side of the system. The certification of test shall be signed by the installer and shall be made part of the public record. [F] SECTION 1109 PERIODIC TESTING 1109.1 Testing required. The following emergency devices and systems shall be periodically tested in accordance with the manufacturer's instructions and as required by the code official. 1. Treatment and flaring systems. 2. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes. 3. Fans and associated equipment intended to operate emergency ventilation systems. 4. Detection and alarm systems. 2012 INTERNATIONAL MECHANICAL CODE® 105 I II I Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,iNb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 106 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc SIP SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( riR�ep�odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER 12 HYDRONIC PIPING SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern the construction, installation, alteration and repair of hydronic piping systems. This chapter shall apply to hydronic piping systems that are part of heating, ventilation and air-condition- ing systems. Such piping systems shall include steam, hot water, chilled water, steam condensate and ground source heat pump loop systems. Potable cold and hot water distribu- tion systems shall be installed in accordance with the Interna- tional Plumbing Code. 1201.2 Sizing. Piping and piping system components for hydronic systems shall be sized for the demand of the system. 1201.3 Standards. As an alternative to the provisions of Sec- tions 1202 and 1203, piping shall be designed, installed, inspected and tested in accordance with ASME 1331.9. SECTION 1202 MATERIAL 1202.1 Piping. Piping material shall conform to the standards cited in this section. Exception: Embedded piping regulated by Section 1209 1202.2 Used materials. Reused pipe, fittings, valves or other materials shall be clean and free of foreign materials and shall be approved by the code official for reuse. 1202.3 Material rating. Materials shall be rated for the oper- ating temperature and pressure of the hydronic system. Mate- rials shall be suitable for the type of fluid in the hydronic system. 1202.4 Piping materials standards. Hydronic pipe shall conform to the standards listed in Table 1202.4. The exterior of the pipe shall be protected from corrosion and degradation. TABLE 1202.4 HYDRONIC PIPE MATERIAL STANDARD (see Chapter 15) Acrylonitrile butadiene styrene ASTM D 1527; ASTM D 2282 (ABS) plastic pipe Brass pipe ASTM B 43 Brass tubing ASTM B 135 Copper or copper -alloy pipe ASTM B 42; ASTM B 302 Copper or copper -alloy tube ASTM B 75; ASTM B 88; (Type K, L or M) ASTM B 251 Chlorinated polyvinyl chloride ASTM D 2846; ASTM F 441; (CPVC) plastic pipe JASTM F 442 Cross -linked polyethylene/ aluminum/cross-linked ASTM F 1281; polyethylene (PEX-AL-PEX) CSA CAN/CSA-B-137.10 pressure pipe (continued) TABLE 1202.4—continued HYDRONIC PIPE MATERIAL STANDARD (see Chapter 15) Cross -linked polyethylene ASTM F 876; ASTM F 877 (PEX) tubing Ductile iron pipe AWWA C151/A21.51; AWWA C115/A21.15 Lead pipe FS WW-P-325B Polybutylene (PB) plastic pipe ASTM D 3309 and tubing Polyethylene/aluminum/polyeth- ylene ASTM F 1282; CSA B137.9 (PE -AL -PE) pressure pipe ASTM D 2513; Polyethylene (PE) pipe, tubing ASTM D 3035; ASTM D and fittings (for ground source ASTM D 2683; heat pump loop systems) AST ASTM F 1055; ASTM D 2837; ASTM D 3350; ASTM D 1693 Polypropylene (PP) plastic pipe ASTM F 2389 Polyvinyl chloride (PVC) ASTM D 1785; ASTM D 2241 plastic pipe Raised temperature polyethylene ASTM F 2623; ASTM F 2769 (PE-RT) Steel pipe ASTM A 53; ASTM A 106 Steel tubing ASTM A 254 1202.5 Pipe fittings. Hydronic pipe fittings shall be approved for installation with the piping materials to be installed, and shall conform to the respective pipe standards or to the standards listed in Table 1202.5. TABLE 1202.5 HYDRONIC PIPE FITTINGS MATERIAL STANDARD (see Chapter 15) Brass ASTM F 1974 Bronze ASME B16.24 ASME B 16.15; ASME B 16.18; Copper and copper alloys ASME B 16.22; ASME B 16.23; ASME B 16.26; ASME B 16.29 Ductile iron and gray iron ANSI/AWWA C110/A21.10 Ductile iron ANSI/AWWAC153/A21.53 Gray iron ASTM A 126 Malleable iron ASME B 16.3 PEX fittings ASTM F 877; ASTM F 1807; ASTM F 2159 ASTM D 2466; ASTM D 2467; ASTM D 2468; ASTM F 438; Plastic ASTM F 439; ASTM F 877; ASTM F 2389; ASTM F 2735 ASME B 16.5; ASME B 16.9; Steel ASME B 16.11; ASME B 16.28; ASTM A 420 2012 INTERNATIONAL MECHANICAL CODE® 107 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o19o147 To (PDT) p—Pot to IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER HYDRONIC PIPING 1202.6 Valves. Valves shall be constructed of materials that are compatible with the type of piping material and fluids in the system. Valves shall be rated for the temperatures and pressures of the systems in which the valves are installed. 1202.7 Flexible connectors, expansion and vibration com-pensators. Flexible connectors, expansion and vibration con-trol devices and fittings shall be of an approved type. SECTION 1203 JOINTS AND CONNECTIONS 1203.1 Approval. Joints and connections shall be of an approved type. Joints and connections shall be tight for the pressure of the hydronic system. 1203.1.1 Joints between different piping materials. Joints between different piping materials shall be made with approved adapter fittings. 1203.2 Preparation of pipe ends. Pipe shall be cut square, reamed and chamfered, and shall be free of burrs and obstruc- tions. Pipe ends shall have full -bore openings and shall not be undercut. 1203.3 Joint preparation and installation. When required by Sections 1203.4 through 1203.14, the preparation and installation of brazed, mechanical, soldered, solvent - cemented, threaded and welded joints shall comply with Sec- tions 1203.3.1 through 1203.3.8. 1203.3.1 Brazed joints. Joint surfaces shall be cleaned. An approved flux shall be applied where required. The joint shall be brazed with a filler metal conforming to AWS A5.8. 1203.3.2 Mechanical joints. Mechanical joints shall be installed in accordance with the manufacturer's instruc- tions. 1203.3.3 Soldered joints. Joint surfaces shall be cleaned. A flux conforming to ASTM B 813 shall be applied. The joint shall be soldered with a solder conforming to ASTM B 32. 1203.3.4 Solvent -cemented joints. Joint surfaces shall be clean and free of moisture. An approved primer shall be applied to CPVC and PVC pipe joint surfaces. Joints shall be made while the cement is wet. Solvent cement con- forming to the following standards shall be applied to all joint surfaces: 1. ASTM D 2235 for ABS joints. 2. ASTM F 493 for CPVC joints. 3. ASTM D 2564 for PVC joints. CPVC joints shall be made in accordance with ASTM D 2846. Exception: For CPVC pipe joint connections, a primer is not required where all of the following conditions apply: 1. The solvent cement used is third -party certified as conforming to ASTM F 493. 2. The solvent cement is yellow in color. 3. The solvent cement is used only for joining V, inch (12.7 mm) through 2-inch (51 mm) diameter CPVC pipe and fittings. 4. The CPVC pipe and fittings are manufactured in accordance with ASTM D 2846. 1203.3.5 Threaded joints. Threads shall conform to ASME B1.20.1. Schedule 80 or heavier plastic pipe shall be threaded with dies specifically designed for plastic pipe. Thread lubricant, pipe joint compound or tape shall be applied on the male threads only and shall be approved for application on the piping material. 1203.3.6 Welded joints. Joint surfaces shall be cleaned by an approved procedure. Joints shall be welded with an approved filler metal. 1203.3.7 Grooved and shouldered mechanical joints. Grooved and shouldered mechanical joints shall conform to the requirements of ASTM F 1476 and shall be installed in accordance with the manufacturer's installation instruc- tions. 1203.3.8 Mechanically formed tee fittings. Mechanically extracted outlets shall have a height not less than three times the thickness of the branch tube wall. 1203.3.8.1 Full flow assurance. Branch tubes shall not restrict the flow in the run tube. A dimple/depth stop shall be formed in the branch tube to ensure that pene- tration into the outlet is of the correct depth. For inspec- tion purposes, a second dimple shall be placed '/q inch (6.4 mm) above the first dimple. Dimples shall be aligned with the tube run. 1203.3.8.2 Brazed joints. Mechanically formed tee fit-tings shall be brazed in accordance with 1203.3.1. Section 1203.4 ABS plastic pipe. Joints between ABS plastic pipe or fittings shall be solvent -cemented or threaded joints conform- ing to Section 1203.3. 1203.5 Brass pipe. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints conforming to Section 1203.3. 1203.6 Brass tubing. Joints between brass tubing or fittings shall be brazed, mechanical or soldered joints conforming to Section 1203.3. 1203.7 Copper or copper -alloy pipe. Joints between copper or copper -alloy pipe or fittings shall be brazed, mechanical, soldered, threaded or welded joints conforming to Section 1203.3. 1203.8 Copper or copper -alloy tubing. Joints between cop- per or copper -alloy tubing or fittings shall be brazed, mechan- ical or soldered joints conforming to Section 1203.3, flared joints conforming to Section 1203.8.1, push -fit joints con- forming to Section 1203.8.2 or press -type joints conforming I to Section 1203.8.3. 1203.8.1 Flared joints. Flared joints shall be made by a tool designed for that operation. 1203.8.2 Push -fit joints. Push -fit joints shall be installed in accordance with the manufacturer's instructions. 108 2012 INTERNATIONAL MECHANICAL CODE® CoTy,ght @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nmmbsx 100760189 oc Sep SO, 2019 o 1 av PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, IS ( FN ,Fod,Yo,,bymytl,dputy,o,ibau�to,o,sd Single —oPIA PTymg anodmgp� kliRdortuokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE PEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER HYDRONIC PIPING 1203.8.3 Press joints. Press joints shall be installed in accordance with the manufacturer's instructions. 1203.9 CPVC plastic pipe. Joints between CPVC plastic pipe or fittings shall be solvent -cemented or threaded joints conforming to Section 1203.3. 1203.10 Polybutylene plastic pipe and tubing. Joints between polybutylene plastic pipe and tubing or fittings shall be mechanical joints conforming to Section 1203.3 or heat - fusion joints conforming to Section 1203.10.1. 1203.10.1 Heat -fusion joints. Joints shall be of the socket -fusion or butt -fusion type. Joint surfaces shall be clean and free of moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall be undis- turbed until cool. Joints shall be made in accordance with ASTM D 3309. 1203.11 Cross -linked polyethylene (PEX) plastic tubing. Joints between cross -linked polyethylene plastic tubing and fittings shall conform to Sections 1203.11.1 and 1203.11.2. Mechanical joints shall conform to Section 1203.3. 1203.11.1 Compression -type fittings. When compres- sion -type fittings include inserts and ferrules or 0-rings, the fittings shall be installed without omitting the inserts and ferrules or 0-rings. 1203.11.2 Plastic -to -metal connections. Soldering on the metal portion of the system shall be performed at least 18 inches (457 mm) from a plastic -to -metal adapter in the same water line. 1203.12 PVC plastic pipe. Joints between PVC plastic pipe and fittings shall be solvent -cemented or threaded joints con- forming to Section 1203.3. 1203.13 Steel pipe. Joints between steel pipe or fittings shall be mechanical joints that are made with an approved elasto- meric seal, or shall be threaded or welded joints conforming to Section 1203.3. 1203.14 Steel tubing. Joints between steel tubing or fittings shall be mechanical or welded joints conforming to Section 1203.3. 1203.15 Polyethylene plastic pipe and tubing for ground source heat pump loop systems. Joints between polyethyl- ene plastic pipe and tubing or fittings for ground source heat pump loop systems shall be heat fusion joints conforming to Section 1203.15.1, electrofusion joints conforming to Section 1203.15.2, or stab -type insertion joints conforming to Section 1203.15.3. 1203.15.1 Heat -fusion joints. Joints shall be of the socket -fusion, saddle -fusion or butt -fusion type, joined in accordance with ASTM D 2657. Joint surfaces shall be clean and free of moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall be undis- turbed until cool. Fittings shall be manufactured in accor- dance with ASTM D 2683 or ASTM D 3261. 1203.15.2 Electrofusion joints. Joints shall be of the elec- trofusion type. Joint surfaces shall be clean and free of moisture, and scoured to expose virgin resin. Joint sur- faces shall be heated to melt temperatures for the period of time specified by the manufacturer. The joint shall be undisturbed until cool. Fittings shall be manufactured in accordance with ASTM F 1055. 1203.15.3 Stab -type insert fittings. Joint surfaces shall be clean and free of moisture. Pipe ends shall be cham- fered and inserted into the fittings to full depth. Fittings shall be manufactured in accordance with ASTM F 1924. 1203.16 Polypropylene (PP) plastic. Joints between PP plastic pipe and fittings shall comply with Sections 1203.16.1 and 1203.16.2. 1203.16.1 Heat -fusion joints. Heat -fusion joints for poly- propylene (PP) pipe and tubing joints shall be installed with socket -type heat -fused polypropylene fittings, elec- tro-fusion polypropylene fittings or by butt fusion. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 2389. 1203.16.2 Mechanical and compression sleeve joints. Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instruc- tions. 1203.17 Raised temperature polyethylene (PE-RT) plastic tubing. Joints between raised temperature polyethylene tub- ing and fittings shall conform to Sections 1203.17.1 and 1203.17.2. Mechanical joints shall conform to Section 1203.3. 1203.17.1 Compression -type fittings. Where compres- sion -type fittings include inserts and ferrules or 0-rings, the fittings shall be installed without omitting the inserts and ferrules or 0-rings. 1203.17.2 PE-RT-to-metal connections. Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PE-RT pipe. 1203.18 Polyethylene/aluminum/polyethylene (PE -AL - PE) pressure pipe. Joints between polyethylene/aluminum/ polyethylene pressure pipe and fittings shall conform to Sec- tions 1203.18.1 and 1203.18.2. Mechanical joints shall com- ply with Section 1203.3. 1203.18.1 Compression -type fittings. Where compres- sion -type fittings include inserts and ferrules or 0-rings, the fittings shall be installed without omitting the inserts and ferrules or 0-rings. 1203.18.2 PE -AL -PE -to -metal connections. Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PE -AL -PE pipe. 1203.19 Cross -linked polyethylene/aluminum/cross- linked polyethylene (PEX-AL-PEX) pressure pipe. Joints between cross -linked polyethylene/aluminum/cross-linked polyethylene pressure pipe and fittings shall conform to Sec- tions 1203.19.1 and 1203.19.2. Mechanical joints shall com- ply with Section 1203.3. 1203.19.1 Compression -type fittings. Where compres- sion -type fittings include inserts and ferrules or 0-rings, the fittings shall be installed without omitting the inserts and ferrules or 0-rings. 2012 INTERNATIONAL MECHANICAL CODE® 109 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nmmbsx1oovco189 oc SIP so.2.o19o1av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER HYDRONIC PIPING 1203.19.2 PEX-AL-PEX-to-metal connections. Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PEX-AL-PEX pipe. SECTION 1204 PIPE INSULATION 1204.1 Insulation characteristics. Pipe insulation installed in buildings shall conform to the requirements of the Interna- tional Energy Conservation Code; shall be tested in accor- dance with ASTM E 84 or UL 723, using the specimen preparation and mounting procedures of ASTM E 2231; and shall have a maximum flame spread index of 25 and a smoke - developed index not exceeding 450. Insulation installed in an air plenum shall comply with Section 602.2.1. Exception: The maximum flame spread index and smoke - developed index shall not apply to one- and two-family dwellings. 1204.2 Required thickness. Hydronic piping shall be insu- lated to the thickness required by the International Energy Conservation Code. SECTION 1205 VALVES 1205.1 Where required. Shutoff valves shall be installed in hydronic piping systems in the locations indicated in Sections 1205.1.1 through 1205.1.6. 1205.1.1 Heat exchangers. Shutoff valves shall be installed on the supply and return side of a heat exchanger. Exception: Shutoff valves shall not be required when heat exchangers are integral with a boiler; or are a com- ponent of a manufacturer's boiler and heat exchanger packaged unit and are capable of being isolated from the hydronic system by the supply and return valves required by Section 1005.1. 1205.1.2 Central systems. Shutoff valves shall be installed on the building supply and return of a central util- ity system. 1205.1.3 Pressure vessels. Shutoff valves shall be installed on the connection to any pressure vessel. 1205.1.4 Pressure -reducing valves. Shutoff valves shall be installed on both sides of a pressure -reducing valve. 1205.1.5 Equipment and appliances. Shutoff valves shall be installed on connections to mechanical equipment and appliances. This requirement does not apply to com- ponents of a hydronic system such as pumps, air separa- tors, metering devices and similar equipment. 1205.1.6 Expansion tanks. Shutoff valves shall be installed at connections to nondiaphragm-type expansion tanks. 1205.2 Reduced pressure. A pressure relief valve shall be installed on the low-pressure side of a hydronic piping system that has been reduced in pressure. The relief valve shall be set at the maximum pressure of the system design. The valve shall be installed in accordance with Section 1006. SECTION 1206 PIPING INSTALLATION 1206.1 General. Piping, valves, fittings and connections shall be installed in accordance with the conditions of approval. 1206.2 System drain down. Hydronic piping systems shall be designed and installed to permit the system to be drained. Where the system drains to the plumbing drainage system, the installation shall conform to the requirements of the Inter- national Plumbing Code. Exception: The buried portions of systems embedded underground or under floors. 1206.3 Protection of potable water. The potable water sys- tem shall be protected from backflow in accordance with the International Plumbing Code. 1206.4 Pipe penetrations. Openings for pipe penetrations in walls, floors or ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building ele- ments shall be sleeved. The annular space surrounding pipe penetrations shall be protected in accordance with the Inter- national Building Code. 1206.5 Clearance to combustibles. A pipe in a hydronic pip- ing system in which the exterior temperature exceeds 250°F (121°O) shall have a minimum clearance of 1 inch (25 mm) to combustible materials. 1206.6 Contact with building material. A hydronic piping system shall not be in direct contact with building materials that cause the piping material to degrade or corrode, or that interfere with the operation of the system. 1206.7 Water hammer. The flow velocity of the hydronic piping system shall be controlled to reduce the possibility of water hammer. Where a quick -closing valve creates water hammer, an approved water -hammer arrestor shall be installed. The arrestor shall be located within a range as spec- ified by the manufacturer of the quick -closing valve. 1206.8 Steam piping pitch. Steam piping shall be installed to drain to the boiler or the steam trap. Steam systems shall not have drip pockets that reduce the capacity of the steam piping. 1206.9 Strains and stresses. Piping shall be installed so as to prevent detrimental strains and stresses in the pipe. Provi- sions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement. Piping shall be installed so as to avoid structural stresses or strains within building components. 1206.9.1 Flood hazard. Piping located in a flood hazard area shall be capable of resisting hydrostatic and hydrody- namic loads and stresses, including the effects of buoy- ancy, during the occurrence of flooding to the design flood elevation. 1206.10 Pipe support. Pipe shall be supported in accordance with Section 305. 110 2012 INTERNATIONAL MECHANICAL CODE® C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 01 av PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,odw.noa oAYUP, S I kliF ( od Uto.. by POVO d party. o,±RYb�toc P,,Uoosd Single—mly So, Pod o Nyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER HYDRONIC PIPING 1206.11 Condensation. Provisions shall be made to prevent the formation of condensation on the exterior of piping. SECTION 1207 TRANSFER FLUID 1207.1 Flash point. The flash point of transfer fluid in a hydronic piping system shall be a minimum of 50oF (28°C) above the maximum system operating temperature. 1207.2 Makeup water. The transfer fluid shall be compatible with the makeup water supplied to the system. SECTION 1208 TESTS 1208.1 General. Hydronic piping systems other than ground - source heat pump loop systems shall be tested hydrostatically at one and one half times the maximum system design pres- sure, but not less than 100 psi (689 kPa). The duration of each test shall be not less than 15 minutes. Ground -source heat pump loop systems shall be tested in accordance with Section 1208.1.1. 1208.1.1 Ground source heat pump loop systems. Before connection (header) trenches are backfilled, the assembled loop system shall be pressure tested with water at 100 psi (689 kPa) for 30 minutes with no observed leaks. Flow and pressure loss testing shall be performed and the actual flow rates and pressure drops shall be com- pared to the calculated design values. If actual flow rate or pressure drop values differ from calculated design values by more than 10 percent, the problem shall be identified and corrected. SECTION 1209 EMBEDDED PIPING 1209.1 Materials. Piping for heating panels shall be stan- dard -weight steel pipe, Type L copper tubing, polybutylene or other approved plastic pipe or tubing rated at 100 psi (689 kPa) at 180°F (82°C). 1209.2 Pressurizing during installation. Piping to be embedded in concrete shall be pressure tested prior to pour- ing concrete. During pouring, the pipe shall be maintained at the proposed operating pressure. 1209.3 Embedded joints. Joints of pipe or tubing that are embedded in a portion of the building, such as concrete or plaster, shall be in accordance with the requirements of Sec- tions 1209.3.1 through 1209.3.3. 1209.3.1 Steel pipe joints. Steel pipe shall be welded by electrical arc or oxygen/acetylene method. 1209.3.2 Copper tubing joints. Copper tubing shall be joined by brazing with filler metals having a melting point of not less than 1,000°F (538°C). 1209.3.3 Polybutylene joints. Polybutylene pipe and tub- ing shall be installed in continuous lengths or shall be joined by heat fusion in accordance with Section 1203.10.1. 1209.4 Not embedded related piping. Joints of other piping in cavities or running exposed shall be joined by approved methods in accordance with manufacturer's installation instructions and related sections of this code. 1209.5 Thermal barrier required. Radiant floor heating systems shall be provided with a thermal barrier in accor- dance with Sections 1209.5.1 through 1209.5.4. Exception: Insulation shall not be required in engineered systems where it can be demonstrated that the insulation will decrease the efficiency or have a negative effect on the installation. 1209.5.1 Slab -on -grade installation. Radiant piping uti- lized in slab -on -grade applications shall be provided with insulating materials installed beneath the piping having a minimum R-value of 5. 1209.5.2 Suspended floor installation. In suspended floor applications, insulation shall be installed in the joist bay cavity serving the heating space above and shall con- sist of materials having a minimum R-value of 11. 1209.5.3 Thermal break required. A thermal break shall be provided consisting of asphalt expansion joint materials or similar insulating materials at a point where a heated slab meets a foundation wall or other conductive slab. 1209.5.4 Thermal barrier material marking. Insulating materials utilized in thermal barriers shall be installed such that the manufacturer's R-value mark is readily observable upon inspection. 2012 INTERNATIONAL MECHANICAL CODE® ill I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 112 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( lig odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,EDORD, COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER13 FUEL OIL PIPING AND STORAGE SECTION 1301 GENERAL 1301.1 Scope. This chapter shall govern the design, installa- tion, construction and repair of fuel -oil storage and piping systems. The storage of fuel oil and flammable and combusti- ble liquids shall be in accordance with Chapters 6 and 57 of the International Fire Code. 1301.2 Storage and piping systems. Fuel -oil storage sys- tems shall comply with Section 603.3 of the International Fire Code. Fuel -oil piping systems shall comply with the requirements of this code. 1301.3 Fuel type. An appliance shall be designed for use with the type of fuel to which it will be connected. Such appliance shall not be converted from the fuel specified on the rating plate for use with a different fuel without securing reapproval from the code official. 1301.4 Fuel tanks, piping and valves. The tank, piping and valves for appliances burning oil shall be installed in accor- dance with the requirements of this chapter. When an oil burner is served by a tank, any part of which is above the level of the burner inlet connection and where the fuel supply line is taken from the top of the tank, an approved antisiphon valve or other siphon -breaking device shall be installed in lieu of the shutoff valve. 1301.5 Tanks abandoned or removed. All exterior above - grade fill piping shall be removed when tanks are abandoned or removed. Tank abandonment and removal shall be in accordance with Section 5704.2.13 of the International Fire Code. SECTION 1302 MATERIAL 1302.1 General. Piping materials shall conform to the stan- dards cited in this section. 1302.2 Rated for system. All materials shall be rated for the operating temperatures and pressures of the system, and shall be compatible with the type of liquid. 1302.3 Pipe standards. Fuel oil pipe shall comply with one of the standards listed in Table 1302.3. 1302.4 Nonmetallic pipe. All nonmetallic pipe shall be listed and labeled as being acceptable for the intended application for flammable and combustible liquids. Nonmetallic pipe shall be installed only outside, underground. 1302.5 Fittings and valves. Fittings and valves shall be approved for the piping systems, and shall be compatible with, or shall be of the same material as, the pipe or tubing. 1302.6 Bending of pipe. Pipe shall be approved for bending. Pipe bends shall be made with approved equipment The bend shall not exceed the structural limitations of the pipe. TABLE 1302.3 FUEL OIL PIPING MATERIAL STANDARD (see Chapter 15) Brass pipe ASTM B 43 Brass tubing ASTM B 135 Copper or copper -alloy pipe ASTM B 42; ASTM B 302 Copper or copper -alloy tubing (Type K, L or M) ASTM B 75; ASTM B 88; ASTM B 280 Labeled pipe (See Section 1302.4) Nonmetallic pipe ASTM D 2996 Steel pipe ASTM A 53; ASTM A 106 Steel tubing ASTM A 254; ASTM A 539 1302.7 Pumps. Pumps that are not part of an appliance shall be of a positive -displacement type. The pump shall automati- cally shut off the supply when not in operation. Pumps shall be listed and labeled in accordance with UL 343. 1302.8 Flexible connectors and hoses. Flexible connectors and hoses shall be listed and labeled in accordance with UL 536. SECTION 1303 JOINTS AND CONNECTIONS 1303.1 Approval. Joints and connections shall be approved and of a type approved for fuel -oil piping systems. All threaded joints and connections shall be made tight with suit- able lubricant or pipe compound. Unions requiring gaskets or packings, right or left couplings, and sweat fittings employ- ing solder having a melting point of less than 1,000°F (538°C) shall not be used in oil lines. Cast-iron fittings shall not be used. Joints and connections shall be tight for the pres- sure required by test. 1303.1.1 Joints between different piping materials. Joints between different piping materials shall be made with approved adapter fittings. Joints between different metallic piping materials shall be made with approved dielectric fittings or brass converter fittings. 1303.2 Preparation of pipe ends. All pipe shall be cut square, reamed and chamfered and be free of all burrs and obstructions. Pipe ends shall have full -bore openings and shall not be undercut. 1303.3 Joint preparation and installation. Where required by Sections 1303.4 through 1303.10, the preparation and installation of brazed, mechanical, threaded and welded joints shall comply with Sections 1303.3.1 through 1303.3.4. 1303.3.1 Brazed joints. All joint surfaces shall be cleaned. An approved flux shall be applied where required. The joints shall be brazed with a filler metal con- forming to AWS A5.8. 2012 INTERNATIONAL MECHANICAL CODE® 113 I II I C,Ty,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsx/00760/89 oc SIP V,20190147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —oPIA opymg andortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER FUEL OIL PIPING AND STORAGE 1303.3.2 Mechanical joints. Mechanical joints shall be installed in accordance with the manufacturer's instruc- tions. 1303.3.3 Threaded joints. Threads shall conform to ASME B1.20.1. Pipe joint compound or tape shall be applied on the male threads only. 1303.3.4 Welded joints. All joint surfaces shall be cleaned by an approved procedure. The joint shall be welded with an approved filler metal. 1303.4 Brass pipe. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Section 1303.3. 1303.5 Brass tubing. Joints between brass tubing or fittings shall be brazed or mechanical joints complying with Section 1303.3. 1303.6 Copper or copper -alloy pipe. Joints between copper or copper -alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Section 1303.3. 1303.7 Copper or copper -alloy tubing. Joints between cop- per or copper -alloy tubing or fittings shall be brazed or mechanical joints complying with Section 1303.3 or flared joints. Flared joints shall be made by a tool designed for that operation. 1303.8 Nonmetallic pipe. Joints between nonmetallic pipe or fittings shall be installed in accordance with the manufac- turer's instructions for the labeled pipe and fittings. 1303.9 Steel pipe. Joints between steel pipe or fittings shall be threaded or welded joints complying with Section 1303.3 or mechanical joints complying with Section 1303.9.1. 1303.9.1 Mechanical joints. Joints shall be made with an approved elastomeric seal. Mechanical joints shall be installed in accordance with the manufacturer's instruc- tions. Mechanical joints shall be installed outside, under- ground, unless otherwise approved. 1303.10 Steel tubing. Joints between steel tubing or fittings shall be mechanical or welded joints complying with Section 1303.3. 1303.11 Piping protection. Proper allowance shall be made for expansion, contraction, jarring and vibration. Piping other than tubing, connected to underground tanks, except straight fill lines and test wells, shall be provided with flexible con- nectors, or otherwise arranged to permit the tanks to settle without impairing the tightness of the piping connections. SECTION 1304 PIPING SUPPORT 1304.1 General. Pipe supports shall be in accordance with Section 305. SECTION 1305 FUEL OIL SYSTEM INSTALLATION 1305.1 Size. The fuel oil system shall be sized for the maxi- mum capacity of fuel oil required. The minimum size of a supply line shall be % inch (9.5 mm) inside diameter nominal pipe or % inch (9.5 mm) od tubing. The minimum size of a return line shall be '/q inch (6.4 mm) inside diameter nominal pipe or e/,s inch (7.9 mm) outside diameter tubing. Copper tubing shall have 0.035-inch (0.9 mm) nominal and 0.032- inch (0.8 mm) minimum wall thickness. 1305.2 Protection of pipe, equipment and appliances. All fuel oil pipe, equipment and appliances shall be protected from physical damage. 1305.2.1 Flood hazard. All fuel oil pipe, equipment and appliances located in flood hazard areas shall be located above the elevation required by Section 1612 of the Inter- national Building Code for utilities and attendant equip- ment or shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to such elevation. 1305.3 Supply piping. Supply piping shall connect to the top of the fuel oil tank. Fuel oil shall be supplied by a transfer pump or automatic pump or by other approved means. Exception: This section shall not apply to inside or above- ground fuel oil tanks. 1305.4 Return piping. Return piping shall connect to the top of the fuel oil tank. Valves shall not be installed on return piping. 1305.5 System pressure. The system shall be designed for the maximum pressure required by the fuel -oil -burning appli- ance. Air or other gases shall not be used to pressurize tanks. 1305.6 Fill piping. A fill pipe shall terminate outside of a building at a point at least 2 feet (610 mm) from any building opening at the same or lower level. A fill pipe shall terminate in a manner designed to minimize spilling when the filling hose is disconnected. Fill opening shall be equipped with a tight metal cover designed to discourage tampering. 1305.7 Vent piping. Liquid fuel vent pipes shall terminate outside of buildings at a point not less than 2 feet (610 mm) measured vertically or horizontally from any building open- ing. Outer ends of vent pipes shall terminate in a weather- proof vent cap or fitting or be provided with a weatherproof hood. All vent caps shall have a minimum free open area equal to the cross -sectional area of the vent pipe and shall not employ screens finer than No. 4 mesh. Vent pipes shall termi- nate sufficiently above the ground to avoid being obstructed with snow or ice. Vent pipes from tanks containing heaters shall be extended to a location where oil vapors discharging from the vent will be readily diffused. If the static head with a vent pipe filled with oil exceeds 10 pounds per square inch (psi) (69 kPa), the tank shall be designed for the maximum static head that will be imposed. 114 2012 INTERNATIONAL MECHANICAL CODE® C,Ty,ght @ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT) p—Potto l»eAge mt,oUICC No FYUP ep,odw.noa oAYUP, 4 I kliF ( [IFod Ut.. by POVO d party. o,±RYb�toc P,,Uoosd Single —oPIA PTymg Pod o Nyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE riRPEDREAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER FUEL OIL PIPING AND STORAGE Liquid fuel vent pipes shall not be cross connected with fill pipes, lines from burners or overflow lines from auxiliary tanks. SECTION 1306 OIL GAUGING 1306.1 Level indication. All tanks in which a constant oil level is not maintained by an automatic pump shall be equipped with a method of determining the oil level. 1306.2 Test wells. Test wells shall not be installed inside buildings. For outside service, test wells shall be equipped with a tight metal cover designed to discourage tampering. 1306.3 Inside tanks. The gauging of inside tanks by means of measuring sticks shall not be permitted. An inside tank provided with fill and vent pipes shall be provided with a device to indicate either visually or audibly at the fill point when the oil in the tank has reached a predetermined safe level. 1306.4 Gauging devices. Gauging devices such as liquid level indicators or signals shall be designed and installed so that oil vapor will not be discharged into a building from the liquid fuel supply system. Liquid -level indicating gauges shall comply with UL 180. 1306.5 Gauge glass. A tank used in connection with any oil burner shall not be equipped with a glass gauge or any gauge which, when broken, will permit the escape of oil from the tank. SECTION 1307 FUEL OIL VALVES 1307.1 Building shutoff. A shutoff valve shall be installed on the fuel -oil supply line at the entrance to the building. Inside or above -ground tanks are permitted to have valves installed at the tank. The valve shall be capable of stopping the flow of fuel oil to the building or to the appliance served where the valve is installed at a tank inside the building. Valves shall comply with UL 842. 1307.2 Appliance shutoff. A shutoff valve shall be installed at the connection to each appliance where more than one fuel -oil -burning appliance is installed. 1307.3 Pump relief valve. A relief valve shall be installed on the pump discharge line where a valve is located downstream of the pump and the pump is capable of exceeding the pres- sure limitations of the fuel oil system. 1307.4 Fuel -oil heater relief valve. A relief valve shall be installed on the discharge line of fuel -oil -heating appliances. 1307.5 Relief valve operation. The relief valve shall dis- charge fuel oil when the pressure exceeds the limitations of the system. The discharge line shall connect to the fuel oil tank. SECTION 1308 TESTING 1308.1 Testing required. Fuel oil piping shall be tested in accordance with NITA 31. 2012 INTERNATIONAL MECHANICAL CODE® 115 I II I C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 116 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc SIP SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( riR�ep�odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER14 SECTION 1401 GENERAL 1401.1 Scope. This chapter shall govern the design, construc- tion, installation, alteration and repair of systems, equipment and appliances intended to utilize solar energy for space heat- ing or cooling, domestic hot water heating, swimming pool heating or process heating. 1401.2 Potable water supply. Potable water supplies to solar systems shall be protected against contamination in accor- dance with the International Plumbing Code. Exception: Where all solar system piping is a part of the potable water distribution system, in accordance with the requirements of the International Plumbing Code, and all components of the piping system are listed for potable water use, cross -connection protection measures shall not be required. 1401.3 Heat exchangers. Heat exchangers used in domestic water -heating systems shall be approved for the intended use. The system shall have adequate protection to ensure that the potability of the water supply and distribution system is prop- erly safeguarded. 1401.4 Solar energy equipment and appliances. Solar energy equipment and appliances shall conform to the requirements of this chapter and shall be installed in accor- dance with the manufacturer's installation instructions. 1401.5 Ducts. Ducts utilized in solar heating and cooling sys- tems shall be constructed and installed in accordance with Chapter 6 of this code. SECTION 1402 INSTALLATION 1402.1 Access. Access shall be provided to solar energy equipmentand appliances for maintenance. Solar systems and appurtenances shall not obstruct or interfere with the opera- tion of any doors, windows or other building components requiring operation or access. 1402.2 Protection of equipment Solar equipment exposed to vehicular traffic shall be installed not less than 6 feet (1829 mm) above the finished floor. Exception: This section shall not apply where the equip- ment is protected from motor vehicle impact. 1402.3 Controlling condensation. Where attics or structural spaces are part of a passive solar system, ventilation of such spaces, as required by Section 406, is not required where other approved means of controlling condensation are pro- vided. 1402.4 Roof -mounted collectors. Roof -mounted solar col- lectors that also serve as a roof covering shall conform to the requirements for roof coverings in accordance with the Inter- national Building Code. Exception: The use of plastic solar collector covers shall be limited to those approved plastics meeting the require- ments for plastic roof panels in the International Building Code. 1402.4.1 Collectors mounted above the roof. When mounted on or above the roof covering, the collector array and supporting construction shall be constructed of non- combustible materials or fire -retardant -heated wood con- forming to the International Building Code to the extent required for the type of roof construction of the building to which the collectors are accessory. Exception: The use of plastic solar collector covers shall be limited to those approved plastics meeting the requirements for plastic roof panels in the International Building Code. 1402.5 Equipment. The solar energy system shall be equipped in accordance with the requirements of Sections 1402.5.1 through 1402.5.4. 1402.5.1 Pressure and temperature. Solar energy system components containing pressurized fluids shall be pro- tected against pressures and temperatures exceeding design limitations with a pressure and temperature relief valve. Each section of the system in which excessive pres- sures are capable of developing shall have a relief device located so that a section cannot be valved off or otherwise isolated from a relief device. Relief valves shall comply with the requirements of Section 1006.4 and discharge in accordance with Section 1006.6. 1402.5.2 Vacuum. The solar energy system components that are subjected to a vacuum while in operation or during shutdown shall be designed to withstand such vacuum or shall be protected with vacuum relief valves. 1402.5.3 Protection from freezing. System components shall be protected from damage by freezing of heat trans- fer liquids at the lowest ambient temperatures that will be encountered during the operation of the system. 1402.5.4 Expansion tanks. Liquid single-phase solar energy systems shall be equipped with expansion tanks sized in accordance with Section 1009. 1402.6 Penetrations. Roof and wall penetrations shall be flashed and sealed to prevent entry of water, rodents and insects. 1402.7 Filtering. Air transported to occupied spaces through rock or dust -producing materials by means other than natural convection shall be filtered at the outlet from the heat storage system. 2012 INTERNATIONAL MECHANICAL CODE® 117 I II I C,gbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nmmbsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,iNb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,Fokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER SOLAR SYSTEMS SECTION 1403 HEAT TRANSFER FLUIDS 1403.1 Flash point The flash point of the actual heat transfer fluid utilized in a solar system shall be not less than 50oF (28oQ above the design maximum nonoperating (no -flow) temperature of the fluid attained in the collector. 1403.2 Flammable gases and liquids. A flammable liquid or gas shall not be utilized as a heat transfer fluid. The flash point of liquids used in occupancies classified in Group H or F shall not be lower unless approved. SECTION 1404 MATERIALS 1404.1 Collectors. Factory -built collectors shall be listed and labeled, and bear a label showing the manufacturer's name and address, model number, collector dry weight, collector maximum allowable operating and nonoperating tempera- tures and pressures, minimum allowable temperatures and the types of heat transfer fluids that are compatible with the col- lector. The label shall clarify that these specifications apply only to the collector. 1404.2 Thermal storage units. Pressurized thermal storage units shall be listed and labeled, and bear a label showing the manufacturer's name and address, model number, serial num- ber, storage unit maximum and minimum allowable operating temperatures, storage unit maximum and minimum allowable operating pressures and the types of heat transfer fluids com- patible with the storage unit. The label shall clarify that these specifications apply only to the thermal storage unit. 118 2012 INTERNATIONAL MECHANICAL CODE® riRC,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx 100760189 oc Sep SO, 2019 o 147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP ep,od U:oa oAYUP, od Uto.. by POVOt part, o,±RYbs �toc P,,Uood Single—mly mpymg Pod o Nyo,k,Fokb,Ad ANY VNAVTHORIVED REPRODUCTION OR DISTRIBUTED N IS A VIOLATION OF THE FOR REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER CHAPTER15 REFERENCED STANDARDS This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section 102.8. AC CA Air Conditioning Contractors of America 2800 Shirhngton Road, Suite 300 Arlington, VA 22206 reference number Title in code section number Manual D-09 Residential Duct Systems................................................................. 603.2 1832007 Peak Cooling and Heating Load Calculations in Buildings Except Low-rise Residential Buildings .......312.1 AH RI Air- Conditioning, Heating and Refrigeration Institute 4100 North Fairfax Drive, Suite 200 Arlington, VA 22203 Standard Referenced reference in code number Title section number 700-2006 Purity Specifications for Fluorocarbon and Other Refrigerants...............................1102.2.2.3 AMCAAir Movement and Control Association International AMCA West University Drive Arlington Heights, IL 60004 reference in code number Title section number 550-08 Test Method for High Velocity Wind Driven Rain Resistant Louvers ...................... 401.5, 501.3.2 ANSI American National Standards Institute 11 West42nd Street New York, NY 10036 reference in code number Title section number Z21.8-1994 (R2002) Installation of Domestic Gas Conversion Burners..............................................919.1 AS RAE American Society of Heating, Refrigerating and Air -Conditioning Engineers, Inc 1791 Tulne Circle, NE Atlanta, CA 30329 reference number Title in code section number ASHRAE-2009 ASHRAE Fundamentals Handbook.........................................................603.2 15-2010 Safety Standard for Refrigeration Systems.....................................1101.6, 1105.8, 1108.1 34-2010 Designation and Safety Classification of Refrigerants.............................202, 1102.2.1, 1103.1 2012 INTERNATIONAL MECHANICAL CODE 119 I " ' Copyright OO?.ot I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 1007601e9 oc Sep so.2.o19 o 147 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,oddtoa oAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Pod-Pyo,k,FokbUd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS ASHRAE-continued 62.1-2010 Ventilation for Acceptable Indoor Air Quality............................................403.3.2.3.2 1802008 Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems.............................................................. 102.3 AS� l� American Society of Mechanical Engineers ��I� Three Park Avenue New York, NY 10016-5990 Standard Referenced reference in code number Title section number 131.20.1 1983 (R2006) Pipe Threads, General Purpose (Inch) ............................................ 1203.3.5, 1303.3.3 B16.3-2006 Malleable Iron Threaded Fittings, Classes 150 & 300.................................... Table 1202.5 B16.5-2003 Pipe Flanges and Flanged Fittings NPS l/z through NPS 24 ............................... Table 1202.5 B16.9-2007 Factory Made Wrought Steel Buttwelding Fittings ...................................... Table 1202.5 B16.11-2005 Forged Fittings, Socket -welding and Threaded ......................................... Table 1202.5 B16.15-2006 Cast Bronze Threaded Fittings...................................................... Table 1202.5 B16.18-2001 (Reaffirmed 2005) Cast Copper Alloy Solder Joint Pressure Fittings ............................... 513.13.1, Table 1202.5 B16.22-2001 (Reaffirmed 2005) Wrought Copper and Copper Alloy Solder Joint Pressure Fittings .................. 513.13.1, Table 1202.5 B16.23-2002 (Reaffirmed 2006) Cast Copper Alloy Solder Joint Drainage Fittings DW V.................................. Table 1202.5 B16.242006 Cast Copper Alloy Pipe Flanges and Flanged Fittings: Class 150, 300, 400, 600, 900, 1500 and 2500................................................................ Table 1202.5 B16.26-2006 Cast Copper Alloy Fittings for Flared Copper Tubes ..................................... Table 1202.5 B16.28-1994 Wrought Steel Buttwelding Short Radius Elbows and Returns ............................. Table 1202.5 B16.29-2007 Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings-DWV ............ Table 1202.5 B31.9-08 Building Services Piping............................................................... 1201.3 BPVC-2007 ASME Boiler & Pressure Vessel Code-07 Edition ..................................... 1004.1, 1011.1 CSD-1-2009 Controls and Safety Devices for Automatically Fired Boilers ................................... 1004.1 ASSE American Society of Sanitary Engineering 901 Canterbury, Suite A Westlake, OH 44145 reference in code number Title section number 10172010 Performance Requirements for Temperature Actuated Mixing Values for Hot Water Distribution Systems ...................................................... 1002.2.2 ASTM ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428 reference in code number Title section number A 53/A 53M07 Specification for Pipe, Steel, Black and Hot -dipped, Zinc -coated Welded and Seamless ......................................................Table 1202.4, Table 1302.3 A 106/A106M08 Specification for Seamless Carbon Steel Pipe for High -Temperature Service ...... Table 1202.4, Table 1302.3 A 126-04 Specification for Gray Iron Castings for Valves, Flanges and Pipe Fittings ................... Table 1202.5 A 25497 (2007) Specification for Copper Brazed Steel Tubing ............................... Table 1202.4, Table 1302.3 A 420/A 420M07 Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Low -Temperature Service .................................................... Table 1202.5 A 53999 Specification for Electric -resistance -welded Coiled Steel Tubing for Gas and Fuel Off Lines ..... Table 1302.3 B 32-08 Specification for Solder Metal.......................................................... 1203.3.3 B 4202e01 Specification for Seamless Copper Pipe, Standard Sizes ....... 513.13.1, 1107.5.2, Table 1202.4, Table 1302.3 120 2012 INTERNATIONAL MECHANICAL CODE C,gbt@ ON I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 100760189 oc Sep SO, 20190147 To (PDT) p-Potto l»eAge mt,oUICC No FYUP epoodw.noa oAYUP, S I ( olUto.. byzoyUbdparty.oPAembmoo UoFPd Single-mly mpymg PodoehxodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE TRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS ASTM-continued B 4398(2004) Specification for Seamless Red Brass Pipe, Standard Sizes .... 513.13.1, 1107.5.2, Table 1202.4, Table 1302.3 B 6802 Specification for Seamless Copper Tube, Bright Annealed .................................... 513.13.1 B 7502 Specification for Seamless Copper Tube ................................... Table 1202.4, Table 1302.3 B 8803 Specification for Seamless Copper Water Tube .............. 513.13.1, 1107.5.3, Table 1202.4, Table 1302.3 B 135-08a Specification for Seamless Brass Tube .................................... Table 1202.4, Table 1302.3 B 25102e01 Specification for General Requirements for Wrought Seamless Copper and Copper -alloy Tube ................................................. 513.13.1, Table 1202.4 B 28008 Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service ...................................... 513.13.1, 1107.4.3, Table 1302.3 B 30207 Specification for Threadless Copper Pipe, Standard Sizes ..................... Table 1202.4, Table 1302.3 B 81300(2009) Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube................................................................1203.3.3 C 31507 Specification for Clay Flue Liners and Chimney Pots ........................... 801.16.1, Table 803.10.4 C 41105 Test Method for Hot -surface Performance of High -temperature Thermal Insulation .................. 604.3 D 56-05 Test Method for Flash Point by Tag Closed Tester .............................................. 202 D 9308 Test Method for Flash Point of Pensky-Martens Closed Cup Tester ................................. 202 D 152799(2005) Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe, Schedules 40 and 80 ..... Table 1202.4 D 169308 Test Method for Environmental Stress -Cracking of Ethylene Plastics ....................... Table 1202.4 D 178506 Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80 and 120 .......... Table 1202.4 D 223504 Specifications for Solvent Cement for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe and Fittings............................................................ 1203.3.4 D 224105 Specification for Poly (Vinyl Chloride) (PVC) Pressure -rated Pipe (SDR-Series) .............. Table 1202.4 D 228299(2005) Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR) .............. Table 1202.4 D 241202(2008) Test Method for Determination of External Loading Characteristics of Plastic Pipe by Parallel -plate Loading............................................................603.8.3 D 244703 Specification for Polyethylene (PE) Plastic Pipe, Schedules 40 and 80, Based on Outside Diameter Table 1202.4 D 246606 Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40 .............. Table 1202.5 D 246706 Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80 .............. Table 1202.5 D 246896a Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe Fittings, Schedule 40 ..... Table 1202.5 D 2513-08b Specification for Thermoplastic Gas Pressure Pipe, Tubing, and Fittings ..................... Table 1202.4 D 256404e01 Specification for Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Piping Systems ......... 1203.3.4 D 2657-07 Standard Practice for Heat Fusion Joining of Polyolefin Pipe and Fittings ....................... 1203.15.1 D 268304 Specification for Socket -type Polyethylene Fittings for Outside Diameter -controlled Polyethylene Pipe and Tubing ........................................... Table 1202.4, 1203.15.1 D 283708 Test Method for Obtaining Hydrostatic Design Basis for Thermoplastic Pipe Materials or Pressure Design Basis for Thermoplastic Pipe Products ................................ Table 1202.4 D 2846/D 2846M09 Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Hot and Cold Water Distribution Systems ......................................... Table 1202.4, 1203.3.4 D 299601(2007) e01 Specification for Filament -wound Fiberglass (Glass Fiber Reinforced Thermosetting Resin) Pipe. Table 1302.3 D 303508 Specification for Polyethylene (PE) Plastic Pipe (DR -PR) Based on Controlled Outside Diameter. Table 1202.4 D 327896(2004) Test Methods for Flash Point of Liquids by Small Scale Closed -cup Apparatus ....................... 202 D 326103 Specification for Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing ............................................. 1203.15.1 D 330996a(2002) Specification for Polybutylene (PH) Plastic Hot and Cold Water Distribution Systems. Table 1202.4, 1203.10.1 D 335008 Specification for Polyethylene Plastics Pipe and Fittings Materials ......................... Table 1202.4 E 8409 Test Method for Surface Burning Characteristics of Building Materials ................ 202, 510.8, 602.2.1, 602.2.1.5, 604.3, 1204.1 E 11908a Test Method for Fire Tests of Building Construction and Materials......... 607.5.2, 607.5.5, 607.6.1, 607.2.1 E 13609 Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C ................... 202 E 814-08b Test Method for Fire Tests of Through -penetration Fire Stops ...................... 506.3.10.2, 506.3.10.3 E 1509-04 Specification for Room Heaters, Pellet Fuel -burning Type ...................................... 904.1 E 223104 Standard Practice For Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics .......................................... 604.3, 1204.1 E 233604 Standard Test Methods for Fire Resistive Grease Duct Enclosure Systems .............. 506.3.6, 506.3.10.2 F 438-- 04 Specification for Socket Type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40.................................................................. Table 1202.5 F 439-- 06 Specification for Socket Type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80.................................................................. Table 1202.5 F 441/F 441M02(2008) Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe, Schedules 40 and 80 .. Table 1202.4 F 442/F 442M99(2005)el Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe (SDR-PR) ........... Table 1202.4 F 493-- 04 Specification for Solvent Cements for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe andFittings......................................................................1203.3.4 F 876 08b Specification for CrossHnked Polyethylene (PE}) Tubing ................................ Table 1202.4 F 87707 Specification for Crosslinked Polyethylene (PE}) Plastic Hot and Cold Water Distribution Systems ................................................ Table 1202.4, Table 1202.5 F 105598 (2006) Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene Pipe and Tubing .......................... Table 1202.4, 1203.15.2 2012 INTERNATIONAL MECHANICAL CODE 121 I " ' C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6Nombsx1oovco189 oc SIP so.2.o190147 To (PDT) p-Pot to IL eAgemt,oUICC No FYUPepooddtoaoAYUP, (,eFod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single -ooly, mpymg Pod-PyodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS ASTM—continued F 128107 Specification for Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene (PEX-AL-PEX) Pressure Pipe .................................................... Table 1202.4 F 128206 Standard Specification for Polyethylene/Aluminum/Polyethylene (PE -AL -PE) Composite Pressure Pipe................................................................. Table 1202.4 F 147607 Specification for Performance of Gasketed Mechanical Couplings for Use in Piping Applications..... 1203.3.7 F 180708 Standard Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR 9 Cross -linked Polyethylene (PEX) Tubing ........................................... Table 1202.5 F 192405 Standard Specification for Plastic Mechanical Fittings for Use on Outside Diameter Controlled Polyethylene Gas Distribution Pipe and Tubing ......................................... 1203.15.3 F 197408 Standard Specification for Metal Insert Fittings for Polyethylene/Aluminum/Polyethylene and Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene Composite Pressure Pipe ............... Table 1202.5 F 215905 Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring for SDR 9 Cross -linked Polyethylene (PEX) Tubing ........................................... Table 1202.5 F 2389 07el Specification for Pressure -rated Polypropylene Piping Systems .................Table 1202.4, Table 1202.5 F 262308 Standard Specification for Polyethylene of Raised Temperature (PE-RT) SDR 9 Tubingl ....... Table 1202.4 F 273508a Standard Specification for Plastic Insert Fittings for SDR 9 Cross -linked Polyethylene (PEX) and Raised Temperature (PE-RT) Tubing ........................................... Table 1202.5 F 276909 Polyethylene of Raised Temperature (PE-RT) Plastic Hot and Cold -water Tubing and Distribution Systems........................................................... Table 1202.4 A� %� American Welding Society W/ 550 N W LeJeune Road P O Box 351040 Miami, FL 33135 Standard Referenced reference in code number Title section number A5.8-2004 Specifications for Filler Metals for Brazing and Braze Welding........................1203.3.1, 1303.3.1 A� %� %� American Water Work Association �/ �/ 6666 West Quincy Avenue Denver, CO 80235 reference in code number Title section number C110/A21.1003 Standard for Ductile Iron & Gray Iron Fittings, 2 inches Through 48 inches for Water .......... Table 1202.5 C115/A21.1599 Standard for Flanged Ductile -iron Pipe with Ductile Iron or Grey -iron Threaded Flanges........ Table 1202.4 C151/A21.5102 Standard for Ductile -iron Pipe, Centrifugally Cast for Water .............................. Table 1202.4 C153/A21.5300 Standard for Ductile -iron Comoact Fittings for Water Service ............................. Table 1202.5 CSA Canadian Standards Association 5060 Spectrum Way Mississauga, Ontario, Canada L4W 5N6 reference number Title in code section number B137.905 Polyethylene/Aluminum/Polyethylene (PE -AL -PE) Composite Pressure -Pipe Systems ......... Table 1202.4 B137.1005 Crosslinked Polyethylene/Aluminum/Cross-linked Polyethylene (PEX-AL-PEX) Composite Pressure -pipe Systems ................................................... Table 1202.4 ANSI CSA America FC1-03 Stationary Fuel Cell Power Systems........................................................ 924.1 122 2012 INTERNATIONAL MECHANICAL CODE C,gbt@ON I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 20190147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPepood A:oaoAYUP, S I ( olUto.. byzoyUbdparty.oPAembmoo UoFPd Single—mly mpymg PodoetodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS D O L Department of Labor Occupational Safety and Health Administration do Superintendent of Documents US GovemmentPrinting Office Washington, DC 20402-9325 Standard Referenced reference in code number Title section number (2009) Air Contaminants...................................................................... 502.6 29 CFR Part 1910.1025 (2009) Toxic and Hazardous Substances......................................................... 502.19 FS Federal Specifications* General Services Administration 7th & D Streets Specification Section, Room 6039 Washington, DC 20407 reference in code number Title section number W W-P-325B (1976) Pipe, Bends, Traps, Caps and Plugs; Lead (for Industrial Pressure and Soil and Waste Applications............................................................ Table1202.4 *Standards are available from the Supt of Documents, U S Government Printing Office, Washington, DC 20402-9325 1CC International Code Council, Inc 500 New Jersey Ave, NW 6th Floor Washington, DC 20001 reference in code number Title section number IBC-12 International Building Code ............................... 201.3, 202, 301.12, 301.12, 301.14, 301.15, 302.1, 302.2, 304.7, 304.10, 308.8, 308.10, 401.4, 401.6, 406.1, 502.10, 502.10.1, 504.2, 506.3.3, 506.3.10, 506.3.12.2, 506.4.1, 509.1, 510.6, 510.6.3, 510.6.2, 510.7, 511.1.5, 513.1, 513.2, 513.3, 513.4.3, 513.5, 513.5.2, 513.5.2.1, 513.6.2, 513.10.5, 513.12, 513.12.2, 513.20, 602.2.1.5.1, 602.2.1.5.2, 602.3, 603.1, 603.10, 604.5.4, 607.1.1, 607.3.2.1, 607.5.1, 607.5.2, 607.5.3, 607.5.4, 607.5.4.1, 607.5.5, 607.5.5.1, 607.6, 607.6.2, 701.4.1, 701.4.2, 801.3, 801.16.1, 801.18.4, 902.1, 908.3, 908.4, 910.3, 925.1, 1004.6, 1105.1, 1206.4, 1402.4, 1402.4.1 IEBC-12 International Existing Building Code ....................................................... 101.2 IECC12 International Energy Conservation Code ............. 202, 301.2, 303.3, 312.1, 603.9, 604.1, 1204.1, 1204.2 IFC-12 International Fire Code ............................................ 201.3, 310.1, 311.1, 502.4, 502.5, 502.7.2, 502.8.1, 502.9.5, 502.9.5.2, 502.9.5.3, 502.9.8.2, 502.9.8.3, 502.9.8.5, 502.9.8.6, 502.10, 502.10.3, 502.16.2, 509.1, 510.2.1, 510.2.2, 510.4, 511.1.1 513.12.3, 513.15, 513.16, 513.17, 513.18, 513.19, 513.20.2, 513.20.3, 606.2.1, 908.7, 1101.9, 1105.3, 1105.9, 1106.5, 1106.6, 1301.1, 1301.2 IFGC12 International Fuel Gas Code ...................... 101.2, 201.3, 301.3, 701.1, 801.1, 901.1, 906.1, 1101.5 IPC-12 International Plumbing Code ............................... 201.3, 301.8, 512.2, 908.5, 1002.1, 1002.2, 1002.3, 1005.2, 1006.6, 1008.2, 1009.3, 1101.4, 1201.1, 1206.2, 1206.3, 1401.2 IRC-12 International Residential Code ............................................................ 101.2 2012 INTERNATIONAL MECHANICAL CODE 123 I " ' C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6N—bsx1oovco189 oc SIP so.2.o190147 To (PDT) p—Pot to IL eAg—mt,oUICC No FYUP epooddto—oAYUP, (,eFodmYo¢ebymytl,dputy,o,ANb,to,au o,sd Smglo poly, mpymg Pod-PyodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS IIAR International Institute of Ammonia Refrigeration 1110 North Glebe Road Arlington, VA 22201 Standard Referenced reference in code number Title section number (with Addendum A2005) Addendum A to Equipment, Design, and Installation of Ammonia Mechanical Refrigerating Systems .. 1101.6 MSS Manufacturers Standardization Society of the Valve & Fittings Industry, Inc 127 Park Street, N E Vienna, VA 22180 reference in code number Title section number SP-69-2002 Pipe Hangers and Supports -Selection and Application ......................................... 305.4 NAI� l�� North American Insulation Manufacturers Association ��I� 44 Canal Center Plaza, Suite 310 Alexandria, VA 22314 reference in code number Title section number AH116-09 Fibrous Glass Duct Construction Standards ............................................. 603.5, 603.9 NFPA National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 Standard Referenced reference in code number Title section number 30A-12 Code for Motor Fuel -dispensing Facilities and Repair Garages .................................. 304.6 31-11 Installation of Oil -burning Equipment ................... 801.2.1, 801.18.1, 801.18.2, 920.2, 922.1, 1308.1 37-10 Stationary Combustion Engines and Gas Turbines.......................................915.1, 915.2 58-11 Liquefied Petroleum Gas Code.......................................................... 502.9.10 69-08 Explosion Prevention Systems........................................................... 510.8.3 70-11 National Electrical Code............................................301.7, 306.3.1, 306.4.1, 511.1.1, 513.11, 513.12.1, 602.2.1.1, 1106.3, 1106.4 72-10 National Fire Alarm Code............................................................... 606.3 82-09 Incinerators and Waste and Linen Handling Systems and Equipment .............................. 601.1 9110 Exhaust Systems for Air Conveying of Vapors, Gases, and Noncombustible Particulate Solids........................................................... 502.9.5.1,502.17 9213-09 Smoke Management Systems in Malls, Atria and Large Spaces .................................. 513.8 96-08 Standard for Ventilation Control and Fire Protection Cooking Operations .......................... 507.2 211-10 Chimneys, Fireplaces, Vents and Solid Fuel -burning Appliances ................................ 806.1 26211 Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air -handling Spaces......................................................... 602.2.1.1 70412 Identification of the Hazards of Materials for Emergency Response ............. 502.8.4, Table 1103.1, 510.1 853-10 Installation of Stationary Fuel Power Plants ................................................. 924.1 850 1-97 Single Burner Boiler Operation.......................................................... 1004.1 8502-99 Prevention of Furnace Explosions/Implosions in Multiple Burner Boiler -furnaces .................. 1004.1 8504-96 Atmospheric Fluidized -bed Boiler Operation ............................................... 1004.1 124 2012 INTERNATIONAL MECHANICAL CODE C,gbt@ON I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPepood A:oaoAYUP, 4 I ( �ep4olUto.. byzoyUbdparty.oPAembmoo UoFPd Single—mly mpymg PodoehxodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE TRY REAL COPYRIGHT 11 INC THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS NSF NSF International 789 Dixboro Road Ann Arbor, MI 48105 reference in code number Title section number 14-2011 Plastic Piping System Components and Related Materials ...................................... 301.4 Sl� N� Sheet Metal & Air Conditioning Contractors National Assoc , Inc ��I� 4201 Lafayette Center Drive Chantilly, VA 20151-1209 reference in code number Title section number SMACN ANSI-2005 HVAC Duct Construction Standards -Metal and Flexible 2005 ............................ 603.4, 603.9 SMACNA-10 Fibrous Glass Duct Construction Standards ............................................. 603.5, 603.9 UL Underwriters Laboratories, Inc 333 Pfingsten Road Northbrook, IL 60062-2096 Standard Referenced reference in code number Title section number 172008 Vent or Chimney Connector Dampers for Off -fired Appliances .................................. 803.6 10301 Factory -built Chimneys, Residential Type and Building Heating Appliance with Revisions through March 2010..................................................... 805.2 127-08 Factory -built Fireplaces —with Revisions through January 2010 ...................... 805.3, 903.1, 903.3 17404 Household Electric Storage Tank Water Heaters —with Revisions through May 2006 ............... 1002.1 180-03 Liquid -level Indicating Gauges for Oil Burner Fuels —with Revisions through March 2007........... 1306.4 18105 Factory -made Air Ducts and Air Connectors —with Revisions through October 2008.... 512.2, 603.5, 603.6.1, 603.6.2, 604.13 181A05 Closure Systems for Use with Rigid Air Ducts and Air Connectors with Revisions through February 2008................................................... 603.9 18113 05 Closure Systems for Use with Flexible Air Ducts and Air Connectors with Revisions through February 2008................................................... 603.9 2072009 Refrigerant -containing Components and Accessories, Nonelectrical ............................. 1101.2 2632003 Standard for Fire Test of Building Construction and Materials with Revisions through October 2007..................................... 607.5.2, 607.5.5, 607.6.1 268-2009 Smoke Detectors for Fire Prevention Signaling ............................................... 606.1 268A2008 Smoke Detectors for Duct Application —with Revisions through September 2009 ................... 606.1 343-2008 Pumps for Oil -Burning Appliances....................................................... 1302.7 378-06 Draft Equipment................................................................ 804.3,804.3.8 3912006 Solid -fuel and Combination -fuel Central and Supplementary Furnaces with Revisions through March 2010..................................................... 918.1 412-04 Refrigeration Unit Coolers —with Revisions through January 2009 .............................. 1101.2 47106 Commercial Refrigerators and Freezers —with Revisions through October 2008.................... 1101.2 499-05 Electric Heating Appliances —with Revisions through August 2008 ......................... 912.1, 923.1 508-99 Industrial Control Equipment —with Revisions through September 2008 ......................... 307.2.3 536-97 Flexible Metallic Hose —with Revisions through June 2003.................................... 1302.8 555-06 Fire Dampers —with Revisions through May 2010............................................ 607.3 555C-06 Ceiling Dampers —with Revisions through May 2010........................................ 607.3.1 555S-99 Smoke Dampers —with Revisions through May 2010......................................... 607.3.1 586-2009 High -Efficiency, Particulate, Air Filter Units ................................................ 605.2 641-95 Type L Low -temperature Venting Systems —with Revisions through July 2009 ..................... 802.1 71095 Exhaust Hoods for Commercial Cooking Equipment —with Revisions through December 2009 ........ 507.1 71 OB-04 Recirculating Systems —with Revisions through April 2006.................................... 507.1 7232008 Standard for Test for Surface Burning Characteristics of Building Materials ................. 510.8, 602.2.1, 602.2.1.5, 604.3, 1204.1 726-95 Oil -fired Boiler Assemblies —with Revisions through April 2010 .......................... 916.1, 1004.1 727-06 Oil -fired Central Furnaces............................................................... 918.1 2012 INTERNATIONAL MECHANICAL CODE' 125 I " ' Co,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco1es oc SIP so.2.o19o147 To (PDT) p—Pot to IL eAgemt,oUICC No FYUPepooddtoaoAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly, mpymg Podoehuodmgp4okbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER REFERENCED STANDARDS LIL-continued 729-03 Oil -fired Floor Furnaces -with Revisions through April 2010................................... 910.1 730-03 Oil -fired Wall Furnaces -with Revisions through April 2010................................... 909.1 731-95 Oil -fired Unit HeaterswithRevisions through April 2010..................................... 920.1 732-95 Oil -fired Storage Tank Water Heaters -with Revisions through April 2010 ....................... 1002.1 737-2007 Fireplace Stoves -with Revisions through January 2010....................................... 905.1 762-2010 Outline of Investigation for Power Ventilators for Restaurant Exhaust Appliances .................. 506.5.1 791-06 Residential Incinerators -with Revisions through April 2010................................... 907.1 83404 Heating, Water Supply and Power Boilers Electric -with Revisions through December 2009 ......... 1004.1 842-07 Valves for Flammable Fluids............................................................ 1307.1 858-05 Household Electric RangeswithRevisions through May 2010................................. 917.1 867-00 Electrostatic Air Cleaners -with Revisions through February 2010 ............................... 605.2 87509 Electric Dry Bath Heater -with Revisions through October 2009................................ 914.2 896-93 Oil -burning Stoves -with Revisions through May 2010................................... 917.1, 922.1 900-04 Air Filter Units -with Revisions through November 2009...................................... 605.2 923-2008 Microwave Cooking Appliances -with Revisions through June 2010 ............................. 914.2 907-94 Fireplace Accessories -with Revisions through July 2006...................................... 901.4 95901 Medium Heat Appliance Factory -built Chimneys -with Revisions through June 2010................ 805.5 1046-00 Grease Filters for Exhaust Ducts......................................................... 507.11 124005 Electric Commercial Clothes -Drying Equipment -with Revisions through October 2009 ............ 913.1 1261-01 Electric Water Heaters for Pools and Tubs -with Revisions through May 2008 ..................... 916.1 145304 Electric Booster and Commercial Storage Tank Water Heaters with Revisions through December 2009................................................. 1002.1 1479-03 Fire Tests of Through -penetration Firestops-with Revisions through April 2007....... 506.3.10.2, 506.3.10.3 1482-2010 Solid -fuel Type Room Heaters............................................................ 905.1 1618-09 Wall Protectors, Floor Protectors and Hearth Extensions ............................ 308.5, 903.2, 905.3 1777-2007 Chimney Liners -with Revisions through July 2009................................ 801.16.1, 801.18.4 18122009 Standard for Ducted Heat Recovery Ventilators -with Revisions through June 2010 ................. 927.1 1815-2009 Standard for Nonducted Heat Recovery ..................................................... 927.2 182004 Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics with Revisions through February 2009................................................ 602.2.1.3 188704 Fire Tests of Plastic Sprinkler Pipe for Visible Flame and Smoke Characteristics with Revisions through February 2009................................................ 602.2.1.2 1978-05 Grease DuctswithRevisions through June 2009........................................... 506.3.2 1995-05 Heating and Cooling Equipment -with Revisions through July 2009 ............ 911.1, 918.1, 918.3, 1101.2 199604 Electric Duct Heaters -with Revisions through December 2006................................. 911.1 20242008 Standard for Safety Optical -Fiber and Communications Cable Raceway ........................ 602.2.1.1 20432008 Fire Test for Heat and Visible Smoke Release for Discrete Products and their Accessories Installed in Air -handling Spaces....................................................602.2.1.4.2 215897 Electric Clothes Dryers -with Revisions through March 2009 ............................ 504.6.3, 913.1 2158A-2006 Outline of Investigation for Clothes Dryer Transition Duct .................................... 504.6.3 216201 Outline of Investigation for Commercial Wood -fired Baking Ovens -Refractory Type ................. 917.1 220098 Stationery Engine Generator Assemblies -with Revisions through December 2009 .................. 915.1 222101 Tests of Fire Resistive Grease Duct Enclosure Assemblies .................................. 506.3.10.3 2518-02 Air Dispersion System Materials......................................................... 603.17 2523-09 Solid Fuel -fired Hydronic Heating Appliances ........................................ 1002.1, 1004.1 126 2012 INTERNATIONAL MECHANICAL CODE' Co,gbt@ON I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6Nombsx 100760189 oc Sep SO, 20190147 To (PDT) p-Pot to IL eAgemt,oUICC No FYUPepood A:oaoAYUP, S I (ep�od,Yo,,bymytl,dputy,o,ANb�to,au o�sd Single-mlym,ymg and-Pyodmgp�okbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE TRY REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 100760189 APPENDIX A CHIMNEY CONNECTOR PASS-THROUGHS 1� m�i�. v vvmuv ai WATER —INSOLUBLE REFRACTORY CEMENT\ W WW zD I S u- U CHIMNEY SECTION — FLUSH WITH INSIDE OF FLUE For SI: 1 inch = 25.4 ram. (This appendix is informative and is not part of the code.) SYSTEM A SYSTEM 8 ---�--jjj 2" MIN. CHIMNEY CLEARANCE I �TO BRICK AND COMBUSTIBLE MATERIALS. MIN. CLEARANCE: 12" OF BRICK W D CHIMNEY CONNECTOR J W } W Z = FIRE —CLAY LINER U 1 /2" THICK BRICK MASONRY CHIMNEY 2" MIN. CHIMNEY CLEARANCE FROM MASONRY TO SHEET METAL SUPPORTS AND COMBUSTIBLE MATERIALS. 9" MIN. CLEARANCE _ CHIMNEY CONNECTOR CHIMNEY SECTION MANUFACTURER'S PARTS SHALL BE UTILIZED TO ATTACH CONNECTOR TO CHIMNEY SECTION. LABELED, SOUD—INSULATED, FACTORY — BUILT CHIMNEY SECTION SHEET STEEL SUPPORTS MASONRY CHIMNEY FIGURE A-1 CHIMNEY CONNECTOR SYSTEMS (continued) FACTORY —BUILT CHIMNEY SECTION 9" MIN. AIR SPACE 2012 INTERNATIONAL MECHANICAL CODE° 127 Copyright @ 2011 ICC ALL RIGHTS RESERVED Accessed by (), (-) Order Number #100760189 on Sep 30, 2019 of 47 PM (PDT) pursuant to License Agreement with ICC No further reproduction, no further reproductions by myth ird party, or distribution authorized Single user only, copying andnetworlangprohibrted ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER APPENDIX A 100760189 SYSTEM C SHEET METAL THIMBLE (24 GAGE MIN.) TWO VENTILATED AIR CHANNELS EACH OF1" SYSTEM D 2" MIN. CHIMNEY CLEARANCE TO SHEET STEEL SUPPORTS AND COMBUSTIBLE MATERIALS GLASS -FIBER INSULATION zr—TWO 1" AIR CHANNELS CHIMNEY CONNECTOR (24 GAGE MIN.) MIN. '* SHEET STEEL SUPPORTS (24 GAGE MIN.) MASONRY CHIMNEY 2" MIN. CHIMNEY CLEARANCE I [-TO SHEET STEEL SUPPORTS AND FACTORY -BUILT COMBUSTIBLE MATERIALS. CHIMNEY SECTION 2" MIN. CLEARANCE I" ANNULAR AIRSPACE CHI CHIMNEY CONNECTOR W BETWEEN CHIMNEY CONNECTOR GAGE MIN.) AND CHIMNEY SECTION tj CHIMNEY CONNECTOR 2" AIRSPACE L) FACTORY -BUILT CHIMNEY SECTION -SHEET STEEL SUPPORTS SHEET STEEL SUPPORTS MASONRY CHIMNEY For SI: 1 inch = 25.4 mm. FIGURE A-1—continued CHIMNEY CONNECTOR SYSTEMS 128 2012 INTERNATIONAL MECHANICAL CODE° Copyright() -II CC ALL RIGHTS RESERVED AaY dby (),(-)Ordu Numbu...........0 Sep ....... o...Nofurth,r pIDdb,L,T ofunh,r reprodumo0sbye0y Nerd peRy, or d�.sn�buho0 euthorizeA S�Ogle us.r o0ly, copy�0ge0d 0etworki0gproh�b�teA ANYUNAUPHORIRE,DREPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUB]- TO CIVIL AND CRIMINAL PENALTIES THEREUNDER APPENDIX B RECOMMENDED PERMIT FEE SCHEDULE (This appendix is informative and is not part of the code.) B101 MECHANICAL WORK, OTHER THAN GAS PIPING SYSTEMS B101.1 Initial Fee For issuing each permit $ B101.2 Additional Fees B101.2.1 Fee for inspecting heating, ventilating, ductwork, air-conditioning, exhaust, venting, combustion air, pressure ves- sel, solar, fuel oil and refrigeration systems and appliance installations shall be $ for the first $1,000.00, or fraction thereof, of valuation of the installation plus $ for each additional $1,000.00 or fraction thereof. B101.2.2 Fee for inspecting repairs, alterations and additions to an existing system shall be $ plus $ for each $1,000.00 or fraction thereof. B101.2.3 Fee for inspecting boilers (based upon Btu input): 33,000 Btu (1 bhp) to 165,000 (5 bhp) $ 165,001 Btu (5 bhp) to 330,000 (10 bhp) $ 330,001 Btu (10 bhp) to 1,165,000 (52 bhp) $ 1,165,001 Btu (52 bhp) to 3,300,000 (98 bhp) $ Over 3,300,000 Btu (98 bhp) $ For SI 1 British thermal unit — 0 2931 W, 1 bhp — 33,475 Btu/hr B102 FEE FOR REINSPECTION If it becomes necessary to make a reinspection of a heating, ventilation, air-conditioning or refrigeration system, or boiler instal- lation, the installer of such equipment shall pay a reinspection fee of $ B103 TEMPORARY OPERATION INSPECTION FEE When preliminary inspection is requested for purposes of permitting temporary operation of a heating, ventilating, refrigeration, or air-conditioning system, or portion thereof, a fee of $ shall be paid by the contractor requesting such preliminary inspec- tion. If the system is not approved for temporary operation on the first preliminary inspection, the usual reinspection fee shall be charged for each subsequent preliminary inspection for such purpose. B104 SELF-CONTAINED UNITS LESS THAN 2 TONS In all buildings, except one- and two-family dwellings, where self-contained air-conditioning units of less than 2 tons are to be installed, the fee charged shall be that for the total cost of all units combined (see 13101.2.1 for rate). 2012 INTERNATIONAL MECHANICAL CODE® 129 I I I I Copyngbt OO?.ot I ICC ALL RIGHTS RESERVED Awsed by ().(-)O[d6 Nombsx 100760189 oc Sep so.2.o19 o 147 To (PDT) p—Potto l»eAge mt,oUICC No FYUP ep,oddtoa oAYUP, (,ep4od,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg Podortuodmgp4okbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 130 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx1oovco189 oc Sep SO, 2019o1 av PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( lig odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,EDORD, COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER INDEX n ADMINISTRATION AND ENFORCEMENT Chapter 1 AIR Combustion Chapter 7 Dispersion systems 60317 Distribution systems Chapter 6 Filters 605 Recirculation 40321 Supply Chapter 4 Transfer 40322 Ventilation Chapter 4 ALTERNATIVE MATERIALS AND METHODS 1052 AMMONIA 1105 8, 1106 3, 1106 4 APPEAL 109 APPLIANCES Access 306 Cooking 917 Hazardous location 3032 Installation Chapters 3, 9 Outdoors 3036 Prohibited locations 3033 APPLICABILITY OF CODE 102 APPROVAL 105 ATTIC VENTILATION 406 AUTOMATIC FIRE SUPPRESSION, KITCHEN EXHAUST 509 AUTOMATIC VENT DAMPERS 8036 BALANCING, VENTILATION SYSTEM 4037 BARBECUE APPLIANCES 906 BATHROOM VENTILATION 402, 403 BLOWOFF VALVE, STEAM 1008 BOILERS Approval 10041 Controls 1006 Gauges 1010 General 1001 Low-water cutoff 1007 Rooms 3047, 10046 Tests 1011 BURNER, CONVERSION 919 c CANOPY HOODS 507 12, 507 13 CEILING DAMPERS 607 CHILLED WATER PIPING Chapter 12 CHIMNEYS AND VENTS Connectors 803 Dampers 803 5, 803 6 Direct vents 8041 Exhausters 8043 Existing 801 18 Factory built 802,805 General 801 Liners 801 16, 801 17, 801 18 Masonry, general 801 Offsets 8053 Vents 802 CLEANOUTS Clothes dryer exhaust 5043 Kitchen exhaust 506 3 8, 506 3 9, 506 3 12 Masonry chimneys 801 13 CLEARANCES Appliance in garages 304 3, 304 6, 304 7 Chimney and vent 801 184 Connectors 803 10 6 Kitchen exhaust 50636, 5079 Reduction 308 Specific appliances Chapter 9 CLOTHES DRYER Appliance 913 Exhaust 504 COAL -BURNING APPLIANCES Chapter 9 CODE OFFICIAL 103, 104, 202 COLLECTORS, SOLAR 1402 4, 1404 1 COMBUSTIBLE LIQUID STORAGE TANK 1301 COMBUSTIBLES, REDUCED CLEARANCE 308 COMBUSTION AIR Chapter 7 COMMERCIAL KITCHEN EXHAUST 506 Hoods 507 CONDENSATE DISPOSAL 307 CONDENSATION Ducts 60312 Piping 11074 CONFLICTS 102 8 1, 102 8 2 CONNECTORS, CHIMNEY OR VENT 803 CONTAMINANTS, VENTILATION AIR 401 4,401 6 2012 INTERNATIONAL MECHANICAL CODE® 131 I II I Copy,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d,,Nombsx1oovco189 oc Sep V,20190147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER INDEX CONVERSION BURNERS ................... 919 CONVEYOR SYSTEMS ..................... 511 COOKING APPLIANCES .................... 917 COOLING TOWERS ........................ 908 COOLING WATER PIPING ............ Chapter 12 COVERING, DUCT ........................ 604.3 CRAWL SPACE PLENUMS .................. 602 CRAWL SPACE, VENTILATION .............. 406 CREMATORIES ........................... 907 CUTTING, NOTCHING, BORING .............. 302 DAMPERS Chimney or vent ................... 803.5, 803.6 Fire.................................... 607 Smoke ................................. 607 DEFINITIONS ........................ Chapter 2 DETECTORS, DUCT SMOKE ................ 606 DOCUMENTS .......................... 106.3.1 DRYER,CLOTHES Exhaust ................................ 504 General ................................ 913 DUCT Clothes dryer exhaust ..................... 504 Construction ............................. 603 Covering..............................604.3 Detectors, smoke ......................... 606 Diffusers..............................603.18 Enclosure ......................506.3.11, 510.4 Exhaust...............................501.5 Fire damper ............................. 607 Flexible...............................603.6 Furnace...............................918.2 Hangers and supports ...................603.10 Hazardous exhaust ....................... 510 Installation .............................. 603 Insulation ............................... 604 Joints, seams and connections ............. 603.9 Kitchen exhaust .......................... 506 Lining.................................604.3 Penetrations ............................. 607 Plastic .............................. 603.8.3 Private garage ..........................603.7 Sizing.................................603.2 Smoke damper .......................... 607 Systems ........................... Chapter Underground...........................603.8 Underground grease .................. 506.3.10 DUST, STOCK AND REFUSE CONVEYOR SYSTEMS ................... 511 E ELECTRIC INSTALLATION ................301.10 ENERGY EFFICIENCY .....................301.2 ENERGY RECOVERY SYSTEMS.............514 ENGINE/TURBINE EQUIPMENT .............. 915 EQUIPMENT ACCESS ...................... 306 EQUIPMENT IDENTIFICATION ......304.12, 504.6.5 EVAPORATIVE COOLING ................... 928 EXHAUST, DOMESTIC ..................... 505 EXHAUST, DOWNDRAFT ..................507.2 EXHAUST, REQUIRED SYSTEMS ............ 502 Clothes dryer ............................ 504 Discharge..............................501.3 Ducts.................................501.4 Independence ..........................501.2 Outlets .........................501.3, 501.3.1 Kitchen ............................. 506,507 Machinery room .................... 1105, 1106 Mechanical ..................... 403, Chapter 5 Ventilator openings ................ 401.4, 401.5 System, hazardous ....................... 510 EXHAUSTER, MECHANICAL FLUE ........... 804 EXISTING SYSTEMS ......................102.2 EXPLOSION VENTING ..................... 310 F 7:110Ill d111JI01 Barbecue appliance ....................... 906 Chimneys ............................... 805 Commercial exhaust hoods ................507.1 Ducts (kitchen exhaust) ........ 506.3.1.1, 506.3.2, 506.3.2.5, 506.3.6, 506.3.11.3 Fireplaces ............................... 903 FANS, EXHAUST ................... 503, 506.5.1 FILTERS, AIR ............................. 605 FILTERS, GREASE ......................507.11 FIRE DAMPERS ........................... 607 FIRE SUPPRESSION Hazardous exhaust ......................510.7 Kitchen exhaust .......................... 509 FIREPLACES Accessories............................901.4 Factory built ............................. 903 Masonry...............................902.1 FIREPLACE STOVE ........................ 905 FLEXIBLE CONNECTORS (DUCT) ..... 603.6, 607.7 FLEXIBLE CONNECTORS, HYDRONIC...... 1202.7 FLEXIBLE DUCTS .................. 603.6, 607.7 FLOOD HAZARD ...........301.16, 401.4, 501.3.2, 602.4, 603.13 132 2012 INTERNATIONAL MECHANICAL CODE® I I CopyngbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsx/00760/89 oc SIP SO, 20190147 PM(PDT)p—Potto l»eAg—mt,oUICC No FYUP ep,odU:o—oAYUP, Fk S I ( [IFod Ut.. byzoyUb,dparty.oPAxmbmo—Uoosd Single —oPIA mpymg and-tyodmgplokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER INDEX FLOOR FURNACE ......................... 910 FLUE LINERS .................. 801.16, 801.18.2 FUEL CELLS..............................924 FUEL, CONVERSION .................... 301.12 FUEL OIL Piping ............................ Chapter 13 Piping installation ........................ 1305 Piping material .......................... 1302 FURNACE, FORCED -AIR .................... 918 FURNACE ROOM ........................ 304.8 w GAUGES, BOILERS ....................... 1010 GREASE ............................. 506, 507 GREASE FILTERS ...................... 507.11 GREASE RESERVOIRS ................ 506.3.7.1 GRILLES .............................. 603.18 GUARDS ....................... 304.11, 306.5.1 H HANGERS, DUCT ....................... 603.10 HANGERS, PIPE ........................... 305 HAZARDOUS EXHAUST SYSTEM ............ 510 HAZARDOUS LOCATION, EQUIPMENT ..................... 304.3, 901.3 HAZARDOUS LOCATION, INSTALLATION ... 304.3 HEARTH EXTENSIONS ................... 905.3 HEATER ............................ Chapter 9 HEAT RECOVERY VENTILATORS ............ 927 HEAT PUMP ............................ 918.3 HOOD DESIGN (KITCHEN) .................. 507 HOOD, EXHAUST........... 505, 506, 507, 510.5.3 HOOD LABEL ........................ 507.2.1.2 HOT WATER BOILERS ............... Chapter 10 HOT WATER PIPING ................. Chapter 12 HYDROGEN GENERATION AND REFUELING .................. 304.5, 926 HYDRONIC PIPING ................... Chapter 12 IGNITION SOURCE ................... 202, 304.3 INCINERATORS ........................... 907 INFRARED HEATERS ...................... 912 INSPECTION..............................107 INSULATION Duct...................................604 Pipe..................................1204 INTAKE OPENINGS ...................... 401.4 J JOINTS Connectors..........................803.10.1 Duct .................... 506.3.2, 510.8.1, 603.9 Piping ........ 1003.2, 1107.6, 1107.7, 1203, 1303 K KEROSENE STOVE ........................ 922 KILNS...................................923 KITCHEN EXHAUST EQUIPMENT........ Chapter 5 L Ill 111111k1Le Criteria for .................. 301.4, 301.5, 301.6 LINER, FLUE ........................... 801.16 LINING, DUCT ........................... 604.3 LISTING ................................ 301.7 LOAD CALCULATIONS, HEATING AND COOLING .................. 312 LOCATION, EQUIPMENT AND APPLIANCE .... 303 LOW-WATER CUTOFF, BOILER ............. 1007 M MACHINERY ROOMS.......... 1104.2, 1105, 1106 MAINTENANCE .......................... 102.3 MAKEUP AIR, EXHAUST.............508, 510.5.5 MAKEUP WATER ................. 908.5, 1005.2, 1206.3, 1207.2, 1401.2 MASONRY CHIMNEYS ................. Chapter 8 MASONRY FIREPLACE ..................... 902 MECHANICAL EXHAUST/DRAFT ............. 804 MECHANICAL OFFICIAL (see CODE OFFICIAL) MECHANICAL REFRIGERATION ....... Chapter 11 MECHANICAL VENTILATION ......... 304.5.2, 403 MOTORS, FAN ................... 503, 506.5.1.1 MOVED STRUCTURE ..................... 102.7 N NATURAL VENTILATION .............304.4.1, 402 NONCANOPY HOODS ................... 507.14 Eel OIL, FUEL PIPING .................... Chapter 13 OPENINGS Outside ...................401.4, 401.5, 501.3.2 Transfer.................................607 OUTDOOR APPLIANCE INSTALLATION ..... 303.6 2012 INTERNATIONAL MECHANICAL CODE® 133 I II I CopyngbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER INDEX OUTSIDE AIR, MINIMUM .................... 403 i PELLET FUEL -BURNING APPLIANCES ....... 904 PENETRATIONS .....................302.2, 607 PERMITS ................................ 106 PIPE Insulation ........................ 1107.3, 1204 Support ................................ 305 PIPING Fuel oil ........................... Chapter 13 Material, fuel oil ......................... 1302 Material, hydronic ....................... 1202 Refrigerant ............................. 1107 Support ................................ 305 PLENUMS ........................... 601.4, 602 PLUMBING CONNECTIONS ................ 301.8 POOL/SPA HEATER ....................... 916 POWER EXHAUSTER ...................... 804 PRESSURE GAUGE ...................... 1010 PRESSURE VESSEL ......................1003 7 RADIANT HEATER ........................ 912 RADIANT HEATING SYSTEMS ............... 927 RANGE HOODS ...................... Chapter 5 REDUCED, CLEARANCE ................... 308 REFRIGERANT ..................... Chapter 11 Locking access caps...................1101.10 Piping ................................. 1107 Quantity ............................... 1104 REFRIGERANT PIPING .................... 1107 REGISTERS ............................ 603.18 RELIEF VALVES, FUEL OIL ................ 1307 RELIEF VALVES, PRESSURE VESSELS...... 1006 RELIEF VALVES, SOLAR ............... 1402.5.1 REPAIRS...............................102.4 ROOM HEATERS, SOLID FUEL ...... 904, 905, 921 S SAFETY VALVE ..........................1006 SAUNA HEATER .......................... 914 SCOPE OF CODE ........................ 101.2 SEISMIC...............................301.15 SIGHT GLASS ........................... 1010 SMOKE AND HEAT VENTS ................. 311 SMOKE CONTROL ........................ 513 SMOKE DAMPERS ........................ 607 SMOKE DETECTORS ...................... 606 SOLAR ............................ Chapter 14 SOLID FUEL -BURNING APPLIANCES.... Chapter 9 STANDARDS, REFERENCED..... 102.8, Chapter 15 STEAM Blowoff................................1008 Boilers ........................... Chapter 10 Gauge................................1010 Piping ........................ Chapters 10, 12 SUBSLAB SOIL EXHAUST SYSTEM .......... 512 SUPPORTS, DUCT .......................603.10 SUPPORTS, PIPING ....................... 305 SUPPRESSION Hazardous exhaust ......................510.7 Kitchen exhaust .......................... 509 T TANKS, EXPANSION .............. 1009, 1402.5.4 TANKS, FLAMMABLE AND COMBUSTIBLE LIQUIDS ............ Chapter 13 TEMPERATURE CONTROL ................309.1 TEMPERATURE GAUGE ................... 1010 TEMPERATURE RELIEF, SOLAR ........... 1402.4 TESTS Boiler/pressure vessel .................... 1011 Fuel oil piping ........................... 1308 Hydronic piping ...................1208, 1209.2 Kitchen exhaust ........................507.16 Refrigeration ....................... 1108, 1109 THERMAL STORAGE, SOLAR .............1404.2 THIRD -PARTY CERTIFICATION ....... 301.4, 301.5 TOILET ROOM VENTILATION ... 402.1, Table 403.3 TRANSFER FLUID Hydronic piping ......................... 1207 Solar..................................1403 L11 UNDERGROUND STORAGE TANKS .... Chapter 13 UNIT HEATER ............................ 920 UNSAFE CONDITIONS ....................108.7 UNVENTED GAS LOG HEATERS ............ 903.3 1T1 Boilers ........................... 1005, 1008 Fuel oil................................1307 Hydronic...............................1205 Safety and relief ......................... 1006 Stop.................................1107.7 VAPOR RETARDER ......................604.11 134 2012 INTERNATIONAL MECHANICAL CODE® I I ER CopyngbtOO?.o„ ICC ALL RIGHTS RESERVED Awsed by ().(-)O,d,,Nombsx/00760/89 oc Sep SO, 20190147 PM(PDT)p—Potto l»eAg,,mmt,oUICC No FYUP ep,odw.noa oAYUP, S I ( [eplodw.no.. bymyUb,dparty.oPAembmoo Uoosd Single—mly mpymgmdortxodmgFokb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER INDEX VENTILATION Air ................................ Chapter Enclosed parking garages .................. 404 Energy recovery systems ................... 514 Machinery room .................... 1105, 1106 Mechanical ....................... 304.5.2, 403 Natural .......................... 304.4.1,402 Openings ........................ 401.4, 401.5 Rate ................................. 403.3 Recirculation..........................403.2.1 Transfer.............................403.2.2 Uninhabited spaces .......................406 VENTILATORS, HEAT RECOVERY............ 514 VENTS Connectors..............................803 Direct..................................804 Explosion...............................310 General ........................ 802, Chapter 8 Height ................................ 802.6 Smoke and Heat ..........................311 Termination..............................802 VIBRATION CONTROL DEVICES .......... 301.13 VIOLATIONS..............................108 WALL FURNACE .......................... 909 WATER HEATERS ........................1002 WATER PIPING ...................... Chapter 12 WIND RESISTANCE ..................... 301.15 WOOD -BURNING APPLIANCES ......... Chapter 9 2012 INTERNATIONAL MECHANICAL CODE® 135 I II I CopyngbtOO?.o„ ICC ALL RIGHTS RESERVED A-P—dby().(-)O,d,,Nombsxlow6ole9 oc SIP V,2019o147 PM(PDT)p—Potto IL eAgemt,oUICC No FYUPep,oddtoaoAYUP, (,,Fod,Yo¢tbymytl,dputy,o,ANb,to,au o,sd Single —oPIA mpymg PodortuodmgFokbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 136 2012 INTERNATIONAL MECHANICAL CODE® '' ' C,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc SIP SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I ( riR�ep�odUt..lymyUb,dparty.oPAembmo—Uoosd Single—mly mpymg Pod-Pyodmgp,okb,Ad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,ED REAL COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER EDITORIAL CHANGES - SEVENTH PRINTING Page 99, [F] TABLE 1103.1 continued: column 5, row 15 now reads ... 2-0-0' For the complete errata history of this code, please visit: https://www.iccsafe.org/errata-central/ 2012 INTERNATIONAL MECHANICAL CODE® 137 I " ' C,gbtOO?.ot I ICC ALL RIGHTS RESERVED Awsedby().(-)O,d6 Nombsx1oovco189 oc SIP so.2.o190147 PM(PDT)p—Potto IL eAg—mt,oUICC No FYUP,,eploddtoo.00 AYUP, (,,Fod,Yo¢ebymytl,dputy,o,ANb,to,au o,sd Single —ooly mpymg P,dortuodmg F oARItAd ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER 138 2012 INTERNATIONAL MECHANICAL CODE® '' ' Co,gbtOO zoo I ICC ALL RIGHTS RESERVED Awsedby().(-)O[d6 Nombsx 100760189 oc Sep SO, 2019o147 PM(PDT) pwmmtto l»eAg—mt,oUICC No FYUP ep,odmno—oAYUP, S I (ligep�odmYo,,bymytl,dputy,o,ANbau�to,o,sd Smglo mlympymg and-Pyodmgp�okbad ANY VNAVTHORIVED REPRODUCTION REDISTRIBUTION IS A VIOLATION OF THE ,EDORD, COPYRIGHT 11 AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER Imagine... enjoying membership benefits that help you stay competitive in today's tight job market Imagine... increasingyourcode knowledgeand sharpeningyou riob skills with special member discounts on • World -class training and educational programs to help you keep your competitive edge while earning CE Us and LUs • The latest code -related news to enhance your career potential • Member Discounts on code books, CDs, specialized publications, and training materials to help you stay on top of the latest code changes and become more valuable to your organ ization PLUS —having exclusive access to code opinions from experts to answer your code -related questions Imagine... extra benefits such as Member -Only privileged access to peers in online discussion groups as well as access to the industry's leading periodical, the Budding Safety Journal Online' Imagine... receiving these valuable discounts, benefits, and more by simply becoming a member of the nation's leading developer of building safety codes, the International Code Council' _ Free code book(s) — New members receive a free book or set of books (depending on membership category) from the latest, edition of the International Codes JOIN TODAY! 888-ICC-SAFE, x3380 memberf.a iccsafe.org www.iccsafe.org 11-04304 Cop I@mudu, aoo011SI,�=1 A..,TM aw I——A®,.1,..w��« .gym.. eT,.,�.�aNro emaa.�a., e.�omnm Aa, m��mma .re�M oa��na000moNosou-re�eunoNMAVI0=0NOEnff MnmA,.we.re�o�rrANrwAnffM Ao rr ArmATreJr CIVILArm� wewu'�us' xeuemm Most Widely Accepted and Trusted V� ICC EVALUATION SERVICE PM ICC-ES PLUMBING, MECHANICAL, AND FUEL GAS (PMG) LISTING PROGRAM ICC-ES PMG listings determine whether plumbing, mechanical or fuelgas product complies with applicable codes and standards. Accepted nationwide. Conducted under astringent quality assurance program. Peerless speed and customer service. Customers save when transferri ng to an ICC-ES PMG Listing. Accredited byAmerican National Standards Institute (ANSI). Lookforthe markof conformity. For more information, contact us at es(Mcc-es.org or call 1.800.423.6587(0643). www.icc-es.org 8" so io-oaeia NTERNATIONAL CODE COUNCIL' I 2012 INTERNATIONAL GREEN CONSTRUCTION CODE" (IGCC") Release date: Spring 2012 In 2009, the International Code Council launched the development of a new model code focused on new and existing commercial buildings addressing affordable green building design and performance The IGCC provides the building industry with language that both broadens and strengthens build ing codes in a way that will accelerate the construction of high-performance, green buildings It provides a vehicle for jurisdictions to regulate green for the design and performance of new and renovated buildings in a manner that is integrated with existing codes, allowing buildings to reap the rewards of improved - design and construction practices LEARN MORE! www.iccsafe.orgAGCC COMMITTED TO BUILDING A GREEN AND SUSTAINABLE WORLD INTERNATIONAL ENERGY CONSERVATION CODE' Fintpublished:1998 Encourages efficiency in envelope design, mechanical systems, lighting systems, and the use of new materials and techniques ICC PERFORMANCE CODE' Firstpublished: 2001 Presents regulations based on outcome ratherthan prescription to allowfor new design methods and broader interpretation of the I -Codes INTERNATIONAL EXISTING BUILDING CODE' Fintpublished:2003 Promotes the safe use of existing and historical structures to help restore neighborhoods and reducewaste Orderyour2012I-Codestoday! 1-800-786-4452 I www.iccsafe.org/2012icodes Expert Training Available! Visit www.iccsafe.org/training 11-04334 Cop 1@m11 -du, aoO111.=1 o..,eM aw p—�sAM.�,..w��« .gym.. aNro emaa.�a., e.�omnm aM, m��mma .re�M oa��na000moNosou-re�e ISA�� 0NOEnff MnmA,.we�.re�O�rrAOrwO=M ArmA.re,r<r.O cmaam ca�Mwuewu'�us'xeuemm Valuable Guides to Changes in the 2012 I -Codes° NEW! SIGNIFICANT CHANGES TO THE 2012 INTERNATIONAL CODES° Valuable, praclicalresourcesforanyoneussngthe Internationalrodesi Each book offers a comprehensive analysis of the critical changes made between the 2009 and 2012 editions of the codes Changes are identified then followed by in-depth discussion of how the change affects real -world application Coverage reflects provisions with special significance, including new and innovative design ideas and technologies, modern materials and methods of construction, and current approaches to safety and stability Authored by ICC code experts, these useful tools are "must -have" guides to the many important changes in the2012 International Codes EALSO ,ii SIGNIFICANT CHANGES TO THE SIGNIFICANT CHANGES TO THE INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE, 2012 EDITION 2012 EDITION AuthorScott Stookey Authors Doug Thornburg, Jay Woodward and #7404512 John Henry #7024512 SIGNIFICANT CHANGES TO THE INTERNATIONAL PLUMBING CODE/ SIGNIFICANT CHANGES TO THE INTERNATIONAL MECHANICAL CODE/ INTERNATIONAL RESIDENTIAL CODE, INTERNATIONAL FUEL GAS CODE, 2012 EDITION 2012 EDITION AuthorStephenA Van Note Authors Robert Guenther and Lee Clifton =7101512 =7202512 ORDER YOUR HELPFUL GUIDES TODAY! 1-800-786-4452 1 www.iccsafe.org/store ��e �a., �o xm � oso�,e ISA�,oa 0NOF