Loading...
HomeMy WebLinkAboutResolution No. 2008-70RESOLUTION NO. R2008-70 A RESOLUTION ADOPTING A DESIGN CRITERIA MANUAL FOR THE CITY OF FRIENDSWOOD, TEXAS; CONTAINING STANDARDS FOR THE DESIGN, CONSTRUCTION AND INSTALLATION OF PUBLIC INFRASTRUCTURE AND RELATED FACILITIES AND IMPROVEMENTS WITHIN THE CITY; AND REPEALING CITY OF FRIENDSWOOD RESOLUTION NO. R2006-24, PASSED AND RESOLVED ON THE 11TH DAY OF SEPTEMBER 2006, AND ALL OTHER RESOLUTIONS OR PARTS OF RESOLUTIONS INCONSISTENT ON OR CONFLICT HEREWITH. WHEREAS, the City Council has determined a need for the adoption of comprehensive and concise standards covering the design, construction, and installation of public infrastructure and related improvements within the City; and WHEREAS, the City has determined that such improvement standards and requirements should be, to the extent practicable, incorporated into a single document; and WHEREAS, attached hereto is that certain City of Friendswood Community Development Department "Design Criteria Manual", which document contains certain design, construction and installation standards for public infrastructure and related improvements incident to City construction projects and subdivision and other development within the City's jurisdiction; now therefore BE IT RESOLVED BY THE CITY COUNCIL OF THE CITY OF FRIENDSWOOD, TEXAS: Section 1. The facts and matters set forth in the preamble of this Resolution are hereby found to be true and correct. Section 2. That certain City of Friendswood Community Development Department "Design Criteria Manual", dated September 2008, a true and correct copy of which is attached hereto and for all things made a part hereof, is hereby adopted. The standards and related documents contained and referred to therein shall control and are hereby established as minimum design, construction, and installation standards for certain public infrastructure and related improvements within the City of Friendswood, Texas, for City projects and subdivision and other related development. In the event of conflict between any provision of the Design Criteria Manual and any ordinance of the City, or between any condition of plat or development approval imposed by the City, the provisions of any such ordinance or term or condition of approval shall control. Section 3. The Director of Community Development shall maintain copies of such Design Criteria Manual and related documents, which shall be made available, upon payment of the reasonable costs of publication thereof, to any person requesting same. The Director is further directed to periodically evaluate and review such standards and, when deemed necessary and appropriate, recommend changes to City Council. Section 4. City of Friendswood Resolution No. R2006-24, passed and resolved the I lth day of September 2006, is hereby repealed. All other resolutions inconsistent or in conflict herewith, are, to the extent of such inconsistency or conflict, hereby repealed. PASSED, APPROVED AND RESOLVED on this 61h day of October, 2008. 4DaidJ. H. Smith Mayor ATTEST: FR�ENO O* V o D loris McKenzie, TRMC City Secretary i b R2008-70 2 CITY OF FRIENDSWOOD COMMUNITY DEVELOPMENT DEPARTMENT DESIGN CRITERIA MANUAL Interin CITY OF FRIENDSWOOD COMMUNITY DEVELOPMENT DEPARTMENT Design Criteria Manual Table of Contents SECTION I. Graphic Requirements II. Wastewater Collection System Design Requirements III. Water Line Distribution System Design Requirements IV. Street Paving Design Requirements V. Storm Drainage Design Requirements VI. Site Development Requirements VII. Modification Procedures APPENDICES A. Attachments B. Figures C. Parking Group Table D. Qualified Tree List City of Friendswood Community Development Department SECTION I Design Criteria Manual GRAPHIC and Design REQUIREMENTS GRAPHIC and Design REQUIREMENTS 1.0 GENERAL Should any portion of this Section conflict with any provisions of the Subdivision Ordinance or Zoning Ordinance, the latter two (2) will govern. The Director of Community Development shall have the final interpretation of any provisions in this manual. The Director of Community Development has the right to issue administrative orders or design criteria modifications for just cause related to any provisions or conditions in this manual. 1.01 CHAPTER INCLUDES: Graphic and Design requirements for construction drawings. 1.02 REFERENCES City of Friendswood Standard Details, latest version. These can be purchased from Community Development or downloaded from www.ci.friendswood.tx.us 1.03 DEFINITIONS A. CADD (Computer Aided Drafting Design) - the preparation of documents utilizing computer facilities for the production of drawings, plans, prints and other related documents. B. HCFCD — Harris County Flood Control District C. GCCDD — Galveston County Consolidated Drainage District 1.04 DESIGN REQUIREMENTS A. Provide a cover sheet for all projects involving three or more design drawings (excluding standard detail sheets). Plan sheet numbers shall be shown on the cover sheet or area key map. Include a vicinity map to identify project locations. Also provide approval block for the Director of Public Works and the Director of Community Development with a note stating that approval is valid for 1 year only from date of signatures. B. Preliminary drawings shall be prepared on nominal 24 inch x 36 inch or 22 inch x 34 inch overall paper stock. C. Final drawings shall be india WE on mylar or produced by CADD on mylar. The engineer shall also submit, at the time of plan approval, an electronic version of the CADD drawings Revised 9/2008 Section I Page I of 4 City of Friendswood Community Development Department Design Criteria Manual GRAPHIC and Design REQUIREMENTS on diskette or CD-ROM of the development showing all lot lines and associated lot information, rights -of -way, easements, contours -lines, utilities, and all drainage and paving improvements. D. Details of special structures (not covered by approved standard drawings, such as stream or gully crossings, special manholes, or junction boxes, etc.) shall be drawn with vertical and horizontal scales equal to each other, and shown on a separate sheet (s) from the Standard Detail sheets. E. Each set of construction drawings shall contain paving and utility key drawings indexing specific plan and profile sheets. Standard City detail drawings, where applicable, shall be included. All sheets shall have standard title blocks, and be sequentially numbered. Where applicable, show HCFCD or GCCDD key drawings and numbers. F. Draw project overall layouts to a minimum scale of 1 inch = 100 feet and provide an index G. Plan stationing must run from left to right, except for short streets or lines originating from a major intersection. An index sheet shall be shown on the overall cover sheet. H. A north arrow shall be shown on all sheets (except standard or special detail sheets) and shall be oriented either toward the top or to the right. This requirement is waived under the following conditions. 1. A storm sewer, wastewater sewer or primary outfall ditch drainage facility. 2. Short sections of improvements fitted on a sheet that otherwise has the north arrow correctly shown. Stationing is intended to start from the cardinal points of the compass and proceed in the direction of construction. I. Standard scales permitted for plans and profiles of paving and utility construction drawings are as follows: 1. Major thoroughfares, streets with esplanades over 400 feet in length, or special intersections / situation 1 inch = 20 feet horizontal, 1 inch = 2 feet vertical Minor or residential single-family streets. 1 inch = 20 feet horizontal, 1 inch = 2 feet vertical 1 inch = 40 feet horizontal, 1 inch = 4 feet vertical 1 inch = 50 feet horizontal, 1 inch = 5 feet vertical Revised 9/2008 Section I Page 2 of 4 City of Friendswood Design Criteria Manual Community Development Department GRAPHIC and Design REQUIREMENTS Scales in Paragraph No. 2 above are minimum; larger scales may be used to show details of construction. J. Each sheet of the plan and profile shall have a benchmark elevation and description of the benchmark, and a current flood zone determination statement. Also include the temporary benchmark (TBM) with their elevation and coordinates. K. The seal, date, and original signature of the Professional Engineer licensed by the State of Texas and who is responsible for the drawings shall be required on each sheet developed by the engineer. The engineer may use a stamped or embossed imprint for his/her seal; however, the embossed imprint must be shaded such that it will reproduce on prints. L. A copy of the final plat for new developments shall be included with the final drawings when submitted for final approval. M. If a roadway exists where drawings are being prepared to improve or construct new pavement or a utility, label the existing roadway width, surface type, and thickness. Pavement thickness shall be ascertained by coring with the core hole grout filled to protect pavement prior to construction. N. Show all streets and/or road alignment on drawings. O. Develop drawings to accurate scale showing proposed pavement, typical cross sections, details, lines and grade, and all existing topography within street right-of-way, and any easement contiguous with the right-of-way. At the intersection, the cross street details shall be shown at sufficient distance (20-foot minimum distance outside the primary roadway right-of-way) in each direction along cross street for designing adequate street crossings or transitions. P. Match lines between plan and profile sheets shall not be placed or shown within cross street intersections including cross street rights -of -way. Q. Natural ground profiles shall be shown as follows: For privately -funded projects, center line profiles are satisfactory except where a difference of 0.50 feet or more exists from one right-of-way or easement line to the other, in which case, dual profiles are required. For City of Friendswood projects, provide natural ground profiles at each right- of-way line. Easement profiles shall conform to R.1 below. R. Basic plan and profile sheets shall contain the following information: Identify all lot lines, property lines, easements, rights -of -way, and HCFCD or GCCDD outfalls. Revised 9/2008 Section 1 Page 3 of 4 City of Friendswood Design Criteria Manual Community Development Department GRAPHIC and Design REQUIREMENTS 2. Label each plan sheet as to street/easement widths, pavement widths, pavement thickness where applicable, type of roadway materials, curbs, intersection radii, curve data, stationing, existing utilities (type and location), and any other pertinent feature affecting design. 3. Show all utility lines 4 inches in diameter or larger within the right-of-way or construction easement in profile view. Show all utility lines, regardless of size, in the plan view including fiber optic cables. 4. Graphically, show flow line elevations and direction of flow for all existing ditches. 5. Label proposed top of curb elevations and grades, except at railroad crossings. Center line elevation and grades are acceptable only for paving without curb -and - gutters. 6. Curb return elevations and grades for turnouts shall be shown in profile. 7. The center line elevation at the property line of all existing driveways shall be shown in profile. 8. Station all esplanade noses or the center line of all esplanade openings with esplanade width shown - both existing and proposed. 9. The design of both roadways is required on all paving sections with an esplanade. 10. Station all PCs, PTs, radius returns, and grade change PIs in plan view. Station all radius returns and grade change PIs in profile with their respective elevations. S. Provide a pollution prevention plan with legend. See Site Development (Section VI) under Design Requirements. T. The Drainage Plan shall have a current FEMA flood zone determination statement. Revised 9/2008 Section I Page 4 of 4 City of Friendswood Community Development Department SECTION II Design Criteria Manual WASTEWATER COLLECTION SYSTEM WASTEWATER COLLECTION SYSTEM DESIGN REQUIREMENTS 1.0 GENERAL Should any portion of this Section conflict with the Subdivision Ordinance (Appendix B) or the Zoning Ordinance (Appendix C), the latter two (2) shall govern. The Director of Community Development shall have the final interpretation of any provisions in this manual. The Director of Community Development has the right to issue administrative orders or design criteria modifications for just cause related to any provisions or conditions in this manual. Sanitary sewers located on private property that are not in a dedicated easement, are under the jurisdiction of the Plumbing Code, and will be addressed/reviewed by the Building Official. 1.01 CHAPTER INCLUDES: Criteria for the design of wastewater collection systems. 1.02 REFERENCES A. Texas Commission on Environmental Quality (TCEQ)- "Design Criteria for Sewerage Systems" - Texas Administration Code - Chapter 317 (current revision). B. City of Friendswood Standard Details, latest version. These can be purchased from Community Development or downloaded from www.ci.friendswood.tx.us 1.03 DEFINITIONS Where used in these regulations, the following terms shall be construed to carry the meanings given below: A. Public Sanitary Sewer - A closed conduit which conveys wastewater flow and which is located within the public right-of-way or dedicated public easement. A public sanitary sewer (or public sewer system) is intended to serve more than one (1) "owner". B. Private Sanitary Sewer - A closed conduit which conveys wastewater flow and is constructed and maintained by a private entity (ies) (i.e., homeowner's association). Private sanitary sewers may be located in areas such as a private street or common area, and are subject to the design and construction requirements of the Plumbing Code and must discharge to a public sanitary sewer. Revised 9/2008 Section 1I Page 1 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM C. Sanitary Sewer Main - A sanitary sewer which receives the now from one or more lateral sanitary sewers. D. Lateral Sanitary Sewer - A sanitary sewer running laterally down a street, alley, or easement, which receives only the flow from the abutting property. E. Service Lead - A sanitary sewer which branches off a public sanitary sewer and extends to the limits of the public right-of-way. It shall be construed as having reference to a public sanitary sewer branching off from a main or lateral sanitary sewer to serve one or more houses, single-family lots, or other types of small land tracts situated in the same block with the said main or lateral sanitary sewer, but not directly adjacent thereto. Such a line shall never exceed 150 feet in length. If the sanitary sewer is designed to serve more than two houses, or the equivalent of two single-family residences along a street, a lateral sanitary sewer as defined above shall be constructed. F. Service Connection - A private sanitary sewer from a single source to the main or lateral sanitary sewer in the street, alley, or easement adjacent thereto. Service connections are covered by the Building code. It will be owned and maintained by the owner of the property being served by said sanitary sewer. G. Project Area - The area within the immediate vicinity of the public sanitary sewer to be constructed. If, as an example, a public sanitary sewer were to be constructed within the public right-of-way, the project area would extend 10 feet to either side of the public right- of-way. If as an example, a public sanitary sewer is to be constructed within a dedicated easement adjacent to the public right-of-way, the project area would extend 10 feet to either side of the dedicated easement, depending upon the existing topographical elements, unless impacted by a permanent structure (i.e.. telephone pole, trees, drainage ditches, etc.) If, as an example, a public sanitary sewer is to be constructed within a side lot easement (if approved by the City), the same criteria would apply as for a dedicated easement adjacent to public right-of-way. H. Stack - A riser pipe constructed on main or lateral sanitary sewers which are deeper than 6 feet, measured from finished grade at manhole to facilitate construction of service leads or service connections. I. Force Main - A pressure -rated conduit (i.e. ductile iron pipe, pressure -rated PVC, etc.) that conveys wastewater from a pump station to a discharge point. All references hereafter to sewer, public sewer, private sewer, sewer main, lateral sewer, service lead, service connections, stack and force mains shall mean elements of a sanitary sewer system. 1.04 DESIGN REQUIREMENTS A. Drawings to be furnished: Revised 9/2008 Section II Page 2 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM Before any main or lateral sewer is constructed and before a permit shall be issued for the construction of same, plans and profiles of the proposed sewer shall be prepared and submitted to the City for approval. On projects within the City limits, the tfffeing reproducible drawings and CADD file shall become the property of the City and shall remain on file in the City for the use of any person who may be interested in such information. B. Details to be shown on drawings: The detailed plan view will show the exact location of public sewer lines in the street, alley or easement with respect to the edge of the particular right-of-way, the survey base line, and any nearby utilities, major landscaping, and other structures affecting construction. C. Main and Lateral Sewers 1. Sewers in curved easements, easements defined by property lines and combined easements containing other public utilities shall be shown both in detailed plan and profile views. 2. The profile shall show other underground and surface utilities and facilities, both in parallel and at crossings; the size, grade of the proposed line, the elevation of same to hundreds of a foot at all manholes, changes of grade and dead -ends, and the proposed finished grade over the sewer. It shall show the actual ground line as it exists prior to construction of the sewer. Where proposed fill or cut is contemplated, the proposed new ground line shall be shown as a separate line from the actual ground line. Type of pipe and bedding shall comply with City of Friendswood Standard Specifications and Standard Details. Where public sewers are to be placed between existing pavement and the street right- of-way (or interior easement line) or under existing pavement or shoulders of pavement, show the existing ground line at both sides (or the closest side for sewers near the edge) of the right-of-way or adjacent sewer easement. D. Sewer mains -plan and profile required Sanitary sewer layouts for single-family residential subdivisions should use a scale of 100 feet or less per inch. A scale of 200 feet per inch may be used provided the following information is shown on the layout: a. All easements containing or buffering sanitary sewers shall have points of size change shown, and all manhole locations shall be shown. b. The sewer alignment shall accurately reflect the relative location of the sewer as shown on the detailed plan view. c. All service leads that cross street pavement or serve adjacent property shall be shown on the layout. The detail plans and profiles shall show the flow lines of all service leads at the street or easement right-of-way. Revised 9/2008 Section II Page 3 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM d. The number and size of the lots depicted on both the overall sewer layout sheet and the individual plan and profile sheets shall match the number and size of the lots depicted on the final plat after recordation. e. On the overall sanitary sewer layout sheet the size and direction of flow for all existing and proposed sewers shall be shown. f. The location of the proposed sewer within either the public right-of-way, a dedicated easement adjacent to the public right-of-way, or side lot easement (if allowed by the City). g. The overall sanitary sewer layout sheet shall show the area, in acres, which the proposed sewer(s) is (are) designed to serve. A location map shall be included that references the average proximity to nearby major thoroughfare and boulevard streets. The scale of the location map shall be 1 inch = 2,000 feet or less. 2. Commercial subdivision sanitary sewer layouts for large areas and with a scale of 400 feet or more per inch shall have an additional set of layouts at not more than 200 feet per inch, with match lines and a small index map showing which portion of the overall layout that each sheet's layout represents. 3. Acceptable horizontal scales for the detailed plan and profile views shall be 10 feet, 20 feet, 40 feet and not more than 50 feet maximum per inch. Horizontal scale for major thoroughfares and boulevards shall be 1 inch = 20 feet or less. 4. Acceptable vertical scales for detailed profile views shall be 2 feet, 4 feet, and not more than 5 feet maximum per inch unless otherwise approved. Vertical scale for major thoroughfares and boulevards shall be 1 inch = 2 feet or less. 5.The plan view shall show, at a minimum, the following information for the project area: 6. a. All topographical features; b. Stationing for the proposed sewers; c. All existing underground and overhead utilities (i.e. telephone, gas, power, etc.) d. Any significant landscaping and/or other structures which might impact construction and/or construction related activities; e. The width and type of all existing and proposed easements; f. All proposed service leads; g. The limits of bore and/or tunnel; h. Locations where pressure rated pipe is to be installed at water line crossings; i. Drawings for single-family residential subdivisions shall show the proposed location, by stations, of all service leads, service connections, and stacks. The distance from the sewer or survey base line station to the nearest existing manhole shall be shown in the plan view or on an additional sewer layout sheet with a scale no more than 1 inch = 100 feet; 6. The profile view shall show, at a minimum, the following information for the project area: Revised 9/2008 Section II Page 4 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM a. Underground and/or surface utilities/facilities which are either parallel to the proposed sewer or cross the proposed sewers; b. The proposed sewer's diameter and grade for each manhole section; c. The flow line elevation for all sanitary sewers at each manhole; d. The rim elevation of all existing and proposed manholes; e. The flow line elevation at each sheet "break" (i.e., from one sheet to another); f. Type of pipe bedding/backfill shall be noted on each plan/profile sheet; g. The finished grade for proposed and existing pavement where "fill" and/or "cut" is proposed, the proposed new ground elevation line shall be shown as a separate line from the existing ground elevation line; h. The existing ground elevation line for the "near side" of the public right-of-way where a sewer is to be placed between the edge of existing pavement and the edge of the public right-of-way; i. The existing ground elevation line at the centerline of the proposed sanitary sewer where a sanitary sewer is to be placed within an existing easement. Show any proposed and/or existing pavement. j. The flow line elevation of all service leads where they cross the edge of the public right-of-way or the dedicated easement adjacent to the public right-of- way; k. The limits of bore and/or tunnel; 1. Locations where pressure rated pipe is to be installed at water line crossings; m. The location of special backfill and/or proposed stacks shall be identified by "stations" indicated on the design plans. n. The location of stacks shall be labeled with stations. E. Service leads 1. Service leads shall be at the property line between two (2) adjoining lots, or as directed by the City. A single 6 inch service lead located at the property line between two (2) adjoining lots would serve two (2) single-family residences with a wye placed at the end of the service lead. Do not extend the wye clean -outs beyond the edge of either the public right-of-way or dedicated easement. 2. Any service lead extension of more than 50 feet parallel to the street right-of-way shall be treated as a lateral sewer. Service leads from developments with more than 17,500 gallons -per -day flow shall discharge into a proposed or existing manhole. Where the flow line of the service is 30 inches or greater above the flow line of the manhole, provide a standard drop to manhole. a. Service leads shall be provided to serve each lot within a proposed development inside the City limits. b. Service leads shall be 6 inches in diameter (minimum). If the length of a service lead exceeds 100 feet or the width of the public right-of-way by more than 20 Revised 9/2008 Section II Page 5 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM feet, the minimum diameter shall be 8 inches and a manhole shall be utilized for connection to the public sewer. c. Service leads with a diameter of 6 inches shall utilize "full body" fitting (extruded or factory -fabricated) for connection to the proposed public sewer or an approved saddle -type connector for connection to an existing public sewer. d. Saddle -type connectors shall be installed with the "stub" oriented between the "spring line" (3 o'clock and 9 o'clock positions) and 45 degrees from the "spring line" ("1:30" and "10:30" positions). Tees (aka, "full body fittings") shall be oriented in the same manner. e. The service lead shall be designated to minimize the use of bends as site conditions will permit. f. Service leads exceeding the limits defined in 1.04.E.2. shall have a manhole at each end; as well as, a plan/profile drawing for each right-of-way crossing. All, or part, of these service leads which are located in a public right-of-way, alley or dedicated sanitary sewer or public utility easement may be treated as a public sewer, depending upon the location of the terminal manhole and any intermediate manholes. g. For all existing lots (which are not served in accordance with these guidelines) that need a service lead, if the distance to the nearest existing sewer is less than 50 feet, the service lead falls under the jurisdiction of the Plumbing Code and the Building Official. F. General Requirements. 1. Sanitary sewers within the City of Friendswood's jurisdiction shall allow for orderly expansion of the system and shall conform with the comprehensive water and sewer plan for the City of Friendswood. 2. Sewers shall be sized based on the minimum requirements set out in this standard and the standard wastewater flow rates as established by the City of Friendswood. 3. All sewers shall conform to the minimum requirements of the Texas Department of Health, "Design Criteria for Sewerage Systems". 4. Sewers shall be separated from water lines by a minimum of 9 feet. Where the minimum separation is not maintained, refer to Section 7 for allowable clearances. Sewers crossing utilities other than water, a minimum of 6 inches of clearance must be maintained. The public sanitary sewer, as maintained by the City of Friendswood, shall be defined as all sewers, including stacks and service leads, that serve more than one sewer connection, that are located in public easements or street right-of-ways, and that are installed in accordance with these Standards. 6. Sanitary lines greater than 6 feet deep shall require stacks to facilitate construction of service leads or service connections. Stacks shall be shown on plans with station Revised 9/2008 Section II Page 6 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM numbers. Place stacks and wyes or tees as shown. Where no stacks are shown, it is the responsibility of the licensed plumber to place a City approved saddle for connection to the line and the responsibility of the City Inspector to determine that such saddle is water tight and properly installed. 7. Materials and construction shall conform to latest City of Friendswood specifications with all amendments thereto, including standard leak test. 8. Unless noted otherwise, all public sewers and service leads shall be completely embedded in cement -stabilized sand to 6 inches below the pipe, 12 inches above the pipe and to 6 inches on each side. All such bedding shall be compacted to 95% standard proctor density. The cross-section so described herein shall be termed the "embedment zone." 9. Backfill all excavation areas/trenches under or within 12 inches of existing or proposed pavement or shoulder of pavement with cement -stabilized sand from the top of the pipe "embedment zone" to the bottom of the subgrade. Cement -stabilized sand must develop 100-psi compression at 48 hours. Backfill shall be compacted to 95% standard proctor density. 10. The location of all special backfill and of proposed stacks shall be shown by stations in the drawings. 11. Construction notes shall designate the kind and class of pipe with exceptions to the construction notes to be shown on the plan and profile sheets. 12. Non -sanitary sewer easements or fee strips such as pipeline, power company, drainage district, railroad, etc., are in and of themselves insufficient and unacceptable to permit laying of sanitary sewers and/or force mains across or along the underlying private property or restricted non -sanitary use type of public property. 13. The final determination as to that portion of a street, alley, or easement to be occupied by a proposed sewer rests with the Director of Community Development and the Director of Public Works who will take into consideration existing, planned and proposed facilities such as manholes, pavement, pipe/conduits, along with existing trees, shrubs, or other unique surface conditions when arriving at a decision. 14. Where an easement for a public sewer ends at a public right-of-way, the last manhole shall be extended into the public right-of-way at a minimum of 2 feet beyond the property line; or as close to the public right-of-way as possible due to acceptable clearances required for other utilities (i.e., water line and storm sewers). 15. The drawings for the sewer shall show the location of any existing known pipe, duct or other obstacles that might interfere with the construction of the sewer and call Revised 9/2008 Section 11 Page 7 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM such to the attention of the City any known obstacles that might be encountered in constructing the sewer in any location under consideration. The Professional Engineer for the project, who shall be licensed by the State of Texas, shall determine the existence of pipes, ducts and/or obstacles from a visual survey on the ground plus research of all public records and private records when available. 16. All sanitary sewer mains shall be constructed utilizing pressure rate pipe, SDR 26, unless specifically approved by Director of Community Development and the Director of Public Works. 17. In new developments, sanitary sewer lines shall be centered in sanitary sewer line easements. G. Line Size 1. The minimum pipe diameter for a public sanitary sewer shall be 8 inches. 2. 4-inch service leads shall be confined to the limits of the lot which they serve and shall serve only the equivalent of one single-family lot. No four (4) inch sewer shall be laid in any street, alley, or right-of-way. 3. 6-inch service leads shall not serve more than the equivalent of two (2) single- family lots or other types of small land tracts. 4. 4-inch and 6-inch service leads for single-family residential lots shall have a minimum grade of 1.0 percent and 0.50 percent, respectively. 5. For commercial service leads such as street bores, submit a copy of the approved plumbing drawings to establish the required size of the line. The minimum size lead shall be 6 inches. 6. All main and lateral sewers shall end in manholes, except for special and/or unusual situations and subject to specific approval by the Director of Community Development and the Director of Public Works. All sewer lines shall be laid at a size and depth to conform to designs permitting an orderly expansion of the sewer system of the City and so as to avoid a duplication of lines in the future. 8. The City shall be the final judge as to sizes and depths required and exceptions to "lateral service leads" as previously defined. H. Line Depth The sewer should be laid with the top of the pipe a minimum of 3 feet below finished grade or top of curb, whichever is lower. Revised 9/2008 Section II Page 8 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM 2. Sewer laid in street rights -of -way with curb -and -gutter paved streets shall have a minimum cover of 4 feet from the top of the pipe to the top of the curb to anticipate future sewer extension. 3. Sewers laid in street right-of-way with crowned roads and side ditches shall have a minimum cover of 5 feet from the average ground elevation line at the adjacent street right-of-way to the top of pipe. 4. Where the minimum cover as specified in paragraphs H, 1,2, and 3 above is not possible, the sewer shall be laid in Class 150 (150 psi) pressure pipe or rigid factory made pipe with cement -stabilized sand as shown on the City's Standard Details. Ductile iron pipe shall be lined with either a polyethylene or polyurethane coating as approved by the pipe manufacturer and applied by either the pipe manufacturer or an approved application. The minimum liner thickness shall be 40 mils. 5. Maximum depth for 8 inch, 10 inch, and 12 inch collection lines shall be 20 feet from average ground surface to pipe invert. Depths greater than 20 feet are subject to approval by the City Engineer if justified for site -specific reasons during the preliminary engineering phase of the project design. Line Grades The following table lists the minimum grades for 6 inch through 27 inch public sewers. The minimum grade is based on a minimum full pipe velocity of 2.0 feet per second. The maximum grade is based on a maximum full pipe velocity of 10.0 feet per second. In both cases, the Manning Formula has been used with an "n" of 0.013. The use of different pipe materials will not alter the use of 0.013 for the purpose of the Design Manual. Inside Dimension (I.D.) of Pipe in Inches 6 8 10 12 15 18 21 24 27 Minimum Slope (in Percent) to Develop V=2.3 ft./sec. 0.65 0.44 0.33 0.26 0.19 0.15 0.13 0.11 0.087 For sewers larger than 27 inches in diameter, the Professional Engineer of record, who shall be licensed by the State of Texas, shall determine the appropriate grade utilizing the Manning Formula, n = 0.013 and a full pipe velocity of 2.3 fps. Revised 9/2008 Section II Page 9 of 15 City of Friendswood Community Development Department J. Manholes Design Criteria Manual WASTEWATER COLLECTION SYSTEM All manholes shall be precast concrete, unless the Professional Engineer of record submits a "cast in place" manhole design for review and approval by the Director of Community Development and the Director of Public Works. All precast manholes to incorporate a "boot" type connector for sewer diameters up to 24 inches. For sewer diameters greater than 24 inches, utilize either the "boot" type connector (if available) or an integral gasket. All precast manholes shall conform to the latest ASTM requirements. No manholes may be placed in the paved portion of the City right-of-way. For all public sewers, manholes shall be placed at all changes in alignment, changes in grade, junction points, and either at street, alley, or easement intersections as designs may require. a. Sewers laid in easements shall have a manhole in each street crossed by the sewer. b. The maximum distance between manholes shall be 350 feet for 8 inch to 48 inch pipes diameters. Spacing for lines of a diameter larger than 48 inches shall be determined on an individual project basis. c. Sewers with the same, or approximate flow line elevation shall intersect each other at a 90-degree angle. However, where a true perpendicular intersection cannot be obtained, and where the "entering" sewer intersects the receiving sewer at, or about, the same flow line, one or more manholes shall be utilized to maintain a minimum 80-degree angle at the point of intersection. When the "entering" sewer is on the upstream side of the manhole, the minimum angle between the sewers may be reduced to a 45-degree angle; provided: (1) A distinct flow channel can be maintained within the manhole when the flowline elevations of the sewers are at, or within, one (1) pipe diameter of the smaller pipe; or (2) When the flow line elevation of the "entering" pipe is above the crown of the "primary" sewer and clearance can be provided between the sewers. d. Manholes shall be placed at all dead-end mains and laterals. e. Criteria for connections to, and utilization of, manholes. (1) Where manholes are utilized to facilitate connections between public sewers, when possible the sewers shall either match the manhole's flow line, match the elevation of each other's crown or utilize an "outside" manhole drop. (2) Connections between public sewers at the manhole shall adhere to the following criteria when possible: (a) The elevation of the crown of the discharging sewer shall either match the elevation of the crown of the receiving sewer or be approved as special cases by the Director of Community Development and the Director of Public Works. Revised 9/2008 Section II Page 10 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM (b) A standard drop connection is required when the difference in elevation between discharging sewer flowline and receiving flowline is greater than 30 inches. (3) The routing of service connection directly to manholes will be allowed only where the flowline elevation of the existing sanitary sewer is more than 10 feet below grade and there is no available stack, and either: (a) The lot to be so connected is a single-family, owner -occupied, single lot residence connection to an existing manhole; or (b) The lot to be so connected is a single-family, owner- occupied, single lot residence connecting to a proposed manhole at the end o a cul-de-sac. (4) When routing an approved service connection to a manhole (see Item "3 "), the wall penetration shall not be greater than 10 inches in diameter and shall be cored and sealed using grout as approved by the Standard Wastewater Products Committee. (5) When routing an approved service connection to a manhole (see Item "3"), the connections shall utilize a "drop (either inside or outside) and shall adhere to the following criteria: (a) The manhole wall penetration shall be a minimum of 10 feet below the manhole rim elevation and shall not be greater than 10 inches in diameter; (b) The drop shall be 6 inches in diameter and shall be constructed of SDR 26 PVC pipe (ATSM D 3034-94); (c) The drop shall be located 45 degrees from the upstream side of the main sewer; (d) An internal drop shall be affixed to the manhole wall utilizing stainless steel bands and anchor bolts. (e) An internal drop shall terminate with a 45-degree bend. Said 45- degree bend shall not extend below the "top of pipe" elevation of receiving sanitary sewer and; (f) The wall penetration (core) shall be sealed using a "grout" as approved by the Director of Community Development and the Director of Public Works. (6) All public sewers shall terminate in a manhole. Clean -outs will not be utilized except at the end of each service lead. (a) The manhole cover shall have a minimum diameter of 32 inches. (b) All sanitary sewer manholes shall have inflow protectors. K. Lift Stations Lift station design shall comply with the City of Friendswood specifications, with a storage volume in the wet well equal to one and one-half (1.5) times the peak design flow to the lift station. Add 10 percent to account for volume displaced by pumps. Revised 9/2008 Section II Page 11 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM 2. A startup package for the pumps shall be submitted to the Director of Public Works before final acceptance. This package should also include a completed start up log sheet with field and product data. See Attachment 1. 3. Minimum site size shall be 40 feet by 40 feet. Smaller sites, that are adjacent to public rights -of -way are contiguous to green space or similar land use areas, may be approved when adequate odor control provisions are provided. 4. Pumps shall be sized to operate at optimum efficiency. Minimum acceptable efficiency at the operating point will be 60 percent unless specifically approved by the Director of Community Development and the Director of Public Works.. 5. Operation and maintenance shall be considered in the design of the station and the location of the station. 6. Wet well working volume shall be sized to allow for the recommended pump cycle of 6 minutes for each pump. 7. Prior to installation, controls and equipment shall be approved by the Director of Public Works. 8. Emergency operations shall be considered. Provide fittings and a blind flange that will be readily accessible for emergency bypass pumping. 9. The inlet structure shall be designed to minimize turbulence. 10. The velocity in the force main and riser pipes shall be less than 8 feet per second and greater than 3 feet per second. 11. The wet well shall be sized to provide adequate clearance between the pumps (refer to manufacturers recommended clearances). 12. A peak factor of four (4) shall be used for lift station design. 13. A minimum of 2 feet of clearance shall be provided between pumps and between pump and wall. 14. Low water levels shall be at least 6 inches above impeller, or higher if required by manufacturer. 15. Complete immersion of submersible pump motor at low water level is preferred, if possible. 16. Tie reinforcing steel in lift station bottom to wall reinforcing steel (includes caisson construction situation) to provide watertight wetwell. Revised 9/2008 Section 11 Page 12 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM 17. Nuts, bolts, chains and all other metal components within wetwell shall be stainless steel, not carbon steel. 18. Vent pipe shall be 8 inches minimum diameter equipped with odor control system. 19. The following Hazen -Williams Coefficient shall be used for various pipe types: PVC New C = 160 10-year C = 140 DIP New C = 140 10-year C = 100 20. Provide board fence (either cedar or heart redwood) with steel posts set in concrete. Fence shall be at least 8 feet high. 21. Entrance drive to be at least 14 feet wide concrete pavement. Provide enough room to park vehicles inside lift station site. 22. Indicate method of drainage of site on site plan. Internal drainage, sheet flow and valley gutter driveways are acceptable. Drain to street or storm sewer, never onto adjacent private property. 23. Locate control panel and wetwell hatch above 100-year flood plain. Call out the 100-year flood plain elevation on the plans. 24. Stainless steel guide rails (or other pump removal method that avoids entering wetwell) are required for submersible pumps. 25. A tee, plug valve (or gate valve), and blind flange assembly is required on the force main on the downstream side of the discharge valves and header. This is required so truck -mounted pumps can bypass the lift station pumps and piping while maintenance work is being done on lift station. 26. Bedding for PVC force main shall be cement -stabilized sand. 27. PVC force mains shall be AW WA C-900. 28. DIP force mains shall be bedded in bank sand and polyethylene wrapped. 29. When calculating headloss in force main and piping, use of K factors on fittings, with the Hazen -Williams formula, is preferred. 30. Backfill structural excavations (wetwell, etc.) with cement -stabilized sand. 31. Lift station site plans shall be submitted in scales of 1-inch = 5-feet or 1-inch = 10- feet. Revised 9/2008 Section II Page 13 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM 32. Provide a protective coating or concrete additive to interior walls of wetwell. The Director of Public Works shall approve coating or additive used. 33. Lift station shall be equipped with a telemetry system, approved by the Director of Public Works and shall be compatible with existing systems in the City. A bubbler system shall be installed and connected to telemetry system to monitor status of lift station. 34. Power supply to lift station shall be 3-phase (and 480 volts where possible). 35. A system of floats shall be provided to control pumps. 36. A pressure gauge suitable for application shall be installed on each discharge pipe. 37. A 1-inch minimum water service equipped with backflow prevention shall be provided at the lift station site. 1.05 APPURTENANCES - Reserved 1.06 SUBMITTALS A. Preliminary design - submit the following for review and comment: 1. Copies of any documents which grant approval of exceptions to the City's design criteria. 2. Design calculations for line sizes and grades 3. Contour map for overall area. 4. Plan and profile sheets showing proposed improvements (City projects only). 5. Geotechnical soils report for the project (City projects only). B. Final design - submit the following for approval: 1. Final documents of the above plus plan and profile sheets and Geotechnical soils reports for non -City projects. 2. Review prints. 3. Original drawings. 1.07 QUALITY ASSURANCE Revised 9/2008 Section 11 Page 14 of 15 City of Friendswood Community Development Department Design Criteria Manual WASTEWATER COLLECTION SYSTEM A. Prepare calculations and construction drawings under the supervision of a Professional Engineer licensed by the State of Texas and trained in the disciplines required by the drawings. The final construction drawings must be sealed, signed, and dated by the Professional Engineer responsible for the development of the drawings. 2.0 EXECUTION 2.01 RESEARCH REQUIREMENTS A. Research existing utility and right-of-way information. B. Verify that no restrictions exist that will deny approval of the project concept. 2.02 DESIGN ANALYSIS A. Calculations of design flows for overall development project. 2.03 DRAWINGS A. Drawings shall include layout sheets with contours, plan and profile sheets, and detail sheets for special items and treatment plants. Revised 9/2008 Section II Page 15 of 15 City of Friendswood Community Development Department SECTION III Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM WATER LINE DISTRIBUTION SYSTEM DESIGN REQUIREMENTS 1.0 GENERAL Should any portion of this Section conflict with the Subdivision Ordinance (Appendix B) or the Zoning Ordinance (Appendix C), the latter two (2) shall govern. The Director of Community Development shall have the final interpretation of any provisions in this manual. The Director of Community Development has the right to issue administrative orders or design criteria modifications for just cause related to any provisions or conditions in this manual. 1.01 CHAPTER INCLUDES: Criteria for the design of water lines 1.02 REFERENCES A. Texas Commission on Environmental Quality (TCEQ), Water Utilities Division "Rules and Regulations for Public Water Systems," latest revision. B. American Water Works Association (AWWA). C. National Sanitation Foundation (NSF). D. Texas Department of Health. E. Texas State Board of Insurance. F. City of Friendswood Standard Details, latest version. These can be purchased from Community Development or downloaded from www.ci.friendswood.tx.us 1.03 DEFINITIONS A. Water Line - Closed conduits designed to distribute potable water for human consumption to various areas and provide fire protection. Line size and fire protection accessory locations are dependent on distance from primary source and quantity of demand. 1.04 DESIGN REQUIREMENTS A. Easements for water lines. Lines shall be located within street rights -of -way, permanent access easements with overlapping public utility easements, easements adjacent to street rights -of way or recorded water line easements. Revised 9/2008 Section III Page 1 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM 2. When outside of a public street right-of-way or permanent access easement with an overlapping public utility easement, easements must be dedicated and restricted for water lines only. 3. When possible, easements shall be contiguous with public rights -of -way. 4. Except for side lot easements, water line easements shall be contiguous to a paved access. 5. For water lines 12 inches or smaller located outside of street rights -of -way, minimum width of easement shall be 10 feet. 6. For water lines 14 inches or larger located outside of street rights -of -way, the minimum width of easement shall be 15 feet. 7. For water mains located less than 5 feet from the right-of-way line, the outside edge of a water line easement shall be located from the right-of-way line as follows: 12 inch and smaller pipe - 5 feet 14 inch and larger pipe - 10 feet 8. Water lines along State rights -of -way shall be installed outside of the right-of-way whenever possible and in a separate 10-foot minimum contiguous easement. 9. No back lot easements shall be allowed for the installation of water lines, unless specifically approved by the City. 10. Commercial developments inside the City requiring on -site fire hydrants must provide a minimum 15-foot water line easement for the water line and fire hydrant. 11. In new developments, water lines shall be centered in water line easements. 12. When using side lot easements, such easements shall be a minimum of 10 feet in width, located on one lot or centered between lots. If centered between lots, the water line may be centered within the 5-foot easement on one lot, or centered in the full 10-foot easement. 13. Location of water lines in an easement not adjoining a public right-of-way shall be prohibited, except as specifically approved by the Director of Community Development and the Director of Public Works. When approved, these water mains will be centered in a 15-foot wide exclusive easement restricted to water only. B. Location of water lines Locate within a street right-of-way. Revised 9/2008 Section III Page 2 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM 2. Location of water lines within an easement - locate water lines in the center of a 10- foot minimum width dedicated waterline easement. Within a commercial development inside the City, center water lines within a 15-foot easement. Obtain approval for lines to be located in wider or multi -use easements. When a water line is placed parallel to another utility line, other than a sanitary sewer, the water line shall have a minimum horizontal clearance of 9 feet from the outside wall of the water line to the outside wall of the existing utility. a). Where the nine foot separation distance cannot be achieved, the following criteria shall apply: The new potable waterline shall be located at least two feet above the new wastewater line, measured vertically and at least four feet away, measured horizontally, from the replaced wastewater line. 4. When a water line crosses a sanitary sewer line, the vertical clearance shall be 9 feet and the horizontal clearance shall be 4 feet. C. Water line size 1. 6 inch lines may be used on dead-end lines within cul-de-sacs or if the line is less than 1,000 feet in length and interconnected between two lines which are 8 inches in size or larger. The maximum number of fire hydrants on any length of 6 inch line is one (1). 2. 8 inch lines may be used for lines over 1,000 feet long or when two (2) or more fire hydrants are required. 12 inch and larger lines — line length, usage, etc., to be determined by the Professional Engineer of record, licensed by the State of Texas, and the Director of Community Development and the Director of Public Works. D. Dead-end lines Dead-end lines within a public right-of-way. a. On permanent dead-end lines, other than on cul-de-sacs, the line shall be 6 inches and shall not exceed more than 500 feet in length from the closest interconnection main line and shall terminate with a fire hydrant. b. On permanent dead-end lines on cul-de-sacs, reduce pipe size successively. Carry 8 inch pipe to the next to last hydrant, then use 6 inch pipe to the line's end. Place the last service as near as possible to the end and install a fire hydrant at the end of the 6 inch line. The maximum length of this reduced line size configuration shall not exceed 800 feet. 2. Dead-end lines with one on -site fire hydrant. a. 6 inch lines may be used for lengths less than 200 feet provided domestic service is taken from the end of the line. Revised 9/2008 Section III Page 3 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM b. 8 inch lines may be used for lengths greater than 200 feet but less than 500 feet, provided domestic service is taken from the end of the line. E. Depth of cover 14 inch and smaller mains shall have a minimum cover of 4 feet from top of curb. For open ditch roadway sections, lines 14 inches and smaller shall be installed at least 3 feet below the ultimate flowline of the ditch or 6 feet below natural ground at the right-of-way line, whichever is deeper and maintain the elevation throughout the project. 2. 16 inch and larger mains shall have minimum cover of 5 feet from top of curb. For open ditch roadway sections, lines 16 inches and larger mains shall be installed at least 3 feet below the flow line of the ditch or 7 feet below natural ground at the right-of-way line, whichever is deeper and maintain the elevation throughout the proj ect. Changes in grade to clear other utilities or underground features may be made by deflecting pipe joints. The maximum designed deflection shall be one-half ('/z) of the manufactures allowable deflection. If a depth greater than 8 feet to the top of the pipes is required, a welded steel section will be used. The standard depth of cover maintained on the water main and the grade change shall be made using the welded steel section. The installation of fittings for vertical deflections or changes in elevation shall not be allowed except with specific approval by The Director of Community Development and the Director of Public Works. F. Water line crossings Public and private utility crossings other than sanitary sewer. a. Where a water line crosses another utility other than a sanitary sewer, a minimum of 6 inches of clearance must be maintained between the outside wall of the water line and the outside wall of the utility being crossed. Stream and Ditch Crossings a. Elevated Crossings (1) All water lines shall be steel or restrained joint metallic pipe and shall extend a minimum of 15 feet beyond the last bend or to the right-of-way line, whichever is greater. (2) Elevated crossings are preferred rather than underground crossings. (3) Use a separate elevated supporting structure for 16 inch and larger water lines unless otherwise approved by the Director of Community Development and the Director of Public Works. Locate the structure a minimum of 10 feet from any existing or proposed structure. (4) Support water lines on existing or proposed bridges. The following criteria may be used for 14 inch and smaller lines when approved in advance by the Director of Community Development and the Director of Public Works. Revised 9/2008 Section III Page 4 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM (a) Have adequate structural capacity. (b) Have sufficient clearance above the bent cap elevation for installation under the bridge. (5) Design elevated crossings with the elevation of the bottom of the water line above the low chord of the nearest adjacent bridge or a minimum of 1 '/2 feet above the 100-year flood plain elevation, whichever is higher. (6) Extend pipe from right-of-way to right-of-way for crossings. (7) Provide sufficient span length to accommodate the cross section of future widening of the stream or ditch, if available. (8) Support the line on columns spaced to accommodate the structural capacity of the pipe, considering deflection and loading. (9) Base column support design on soil capacity, spacing, loading, and structural requirements. G. Underground crossings Provide a minimum 3-foot clearance above the top of the pipe to the ultimate flow line of the ditch. 2. Provide sufficient length to exceed the ultimate future development of the stream or ditch. 3. All water lines shall be steel or restrained joint pipe and shall extend a minimum of 15 feet beyond the last bend or to the right-of-way, whichever is greater and have valves located on both sides of the crossing. H. TxDOT highway and county road crossings Extend carrier pipe from right-of-way to right-of-way. Use welded steel pipe or restrained joint pipe in steel casing under existing and future roadways from a point 15 feet outside of the service road or outside of pavement toward the right-of-way, to a similar point on the other side of the highway across the right-of-way. For highway or roadway crossings with open ditch sections, extend the casing from right-of-way to right-of-way. 3. Highway and county road crossings shall be constructed in conformance with the requirements of the Texas Department of Transportation, Galveston County or Harris County as applicable. 4. When additional right-of-way has been acquired or will be required for future widening, the casing, where required, should be carried to within 10 feet of each future right-of-way line. Street crossings Revised 9/2008 Section III Page 5 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM 1. All water mains and sprinkler line crossings under major thoroughfare boulevards shall be encased using a minimum of PVC pipe, SDR, as shown on the construction detail for "Water Main Encasement." Welded steel pipe may be substituted on street crossings, when specifically approved by the Director of Community Development and the Director of Public Works. 2. Crossings under existing concrete streets, other than major thoroughfares, shall be constructed by boring and jacking. PVC and SDR rated pipe shall be jacked into place with equipment designed for that purpose. Water may be used to facilitate boring and jacking operations. Jetting the pipe main into place shall not be permitted. When conditions exist that warrant an open cut across of the existing street, the Director of Community Development and the Director of Public Works shall specifically approve the open cut crossing. All open cut installations under existing or proposed streets shall be backfilled as shown in the construction details. All street crossings shall be constructed in accordance with construction plans approved by the City. All street crossings shall be inspected by the Project Manager and shall meet the requirements of these standards. Oil and gas pipeline crossings Do not use metallic pipe when crossing oil or gas transmission lines unless a properly designed cathodic system is approved by the Director of Community Development and the Director of Public Works, and is properly installed. Other pipe may be used, regardless of depth, subject to approval by the Director of Community Development and the Director of Public Works. Maintain a minimum 2-foot separation between the pipeline and waterline. K. On -site fire loops within commercial and multi -family developments. For commercial and multi -family developments inside the City requiring on -site fire hydrants, comply with the following requirements to allow maintenance and future repair operations: a. Do not allow placement of structures or equipment pads over the easement. b. Provide 10 foot wide longitudinal pavement joint along easement lines where the water line is located under a driveway, paved parking or street pavement. L. Additional requirements The carrier pipeline shall extend a minimum of 1 foot beyond the end of the casing to allow flanged joints to be connected. 2. For welded steel bends, extend steel pipe a minimum of 5 feet beyond the bend. M. Auger (bore) construction Revised 9/2008 Section III Page 6 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM 1. Use the following general criteria for establishing auger or bore sections: a. Auger or bore sections shall be clearly shown on drawings. b. Improved streets - use auger construction to cross the street regardless of surface. Auger length shall be computed as roadway width at proposed bore location plus 5 feet to either side of the roadway, where applicable. C. Sidewalks - when the water line crosses under a sidewalk 4 feet or more in width and in good condition, the sidewalk shall either be bored and jacked or the sidewalk shall be removed and replaced to the City of Friendswood Standard Details, whichever is most cost effective. Bore and jack length shall be at least the width of the sidewalk. The proposed type of construction shall be noted on the plans. d. Bore Pits - Bore pits shall be at least 3 feet from back of curb and shall be at least 5-feet from the back of curb on a boulevard or major thoroughfare. All bore pits shall be shored in accordance with OSHA requirements. Bore pits and/or receiving pits to be located in street or driveway paving shall be shown on plans. N. Water quality - overall system layout. Circulation and flushing - The layout of the overall water distribution system shall provide the maximum circulation of water to prevent future problems of odor, taste, or color due to stagnant water. a. Provide a source of fresh water at each end or at multiple points of a subdivision. Provide ways to create circulation and place valves and fire hydrants to allow simple flushing of all lines. b. Avoid dead -ends whenever possible; when necessary, isolate dead -ends with a line valve, keep as short as possible, and equip with a fire hydrant near the line's end. C. Where stubs are provided for future extensions, isolate the stubs with a valve and do not allow service connections to stubs until extended. Place one full pipe joint beyond the valve for stuff and plug end of pipes. d. Water mains shall be looped unless physically impossible. e. All materials which come in contact with public drinking water in any stage shall conform with ANSI/NSF Standard 60. See Attachment 2. f. Layout and size of all water mains shall be consistent with the overall layout and phasing plan of the City's water system. The overall water system shall be designed to maintain adequate pressure throughout the system. g. In an unavoidable permanent dead-end situation, reduce the sizes of pipe successively. Carry an 8-inch pipe to the next to last fire hydrant; use a 6 inch PVC to the end of the line. Provide a fire hydrant at the end of the main. O. Clearance of water line from other utilities. (New water lines constructed near sanitary sewers and force mains). 1. New water lines parallel to sanitary sewers and force mains. Revised 9/2008 Section III Page 7 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM a. Locate water lines a minimum of 9 feet horizontally, outside wall to outside wall, when parallel to sanitary sewers or force mains. Use the following procedure when 9 feet of separation cannot be achieved: (1) When a new water line is to parallel an existing sanitary sewer force main or gravity sanitary sewer and the 9 foot minimum separation distance cannot be maintained, the existing sanitary sewer shall be replaced with lined ductile iron or PVC pipe meeting ASTM specifications, having a minimum working pressure rating of 150 psi or greater and equipped with pressure type joints. The water lines and sanitary sewer shall be separated by the design requirements of the TCEQ, and a minimum horizontal distance of 4 feet, measured between the nearest outside walls of the pipe, and in all cases, the water line shall be located above the sanitary sewer. When a water main crosses a utility other than sanitary sewer, a minimum of 6 inches of clearance must be maintained, and the water main shall have one joint of pipe, a minimum 18 feet long, centered on the other utility. b. Where a sanitary sewer crosses the water main, and that portion of the sanitary sewer within 9 feet of the water is constructed as described in Section 290.44(e) of the TCEQ Rules and Regulations, the water line may be placed no closer than 6 inches from the sewer. The separation distance must be measured between the nearest outside pipe diameters. The water line shall be located at a higher elevation than the sanitary sewer, wherever possible and one joint of the new pipe, a minimum of 18 feet long, shall be centered on the existing line. 2. When water lines are installed in areas which have existing sanitary sewers, every effort should be made to maintain 9 feet of separation between the outside pipe diameters of the two lines. Where this separation cannot be achieved because of local conditions, which must be fully documented in any planning material submitted, the following spacings shall be observed: a. Where a new water line is to cross or be installed in parallel with an existing sanitary sewer, and the sanitary sewer is constructed as described in Section 290.44(e) of the TCEQ Rules and Regulations, the separation distances specified in those rules shall apply as though the sanitary sewer was new. b. Where a new water line is to be installed in parallel to an existing clay, truss, or concrete gravity sanitary sewer showing no evidence of leakage vertically and horizontally for a distance of 4 feet, the sanitary sewer need not be disturbed. Should excavation for the water line produce evidence that the sanitary sewer is leaking, then the sanitary sewer shall be repaired. c. Where a new water line is to cross an existing clay, truss, or concrete gravity sewer showing no evidence of leakage vertically or horizontally for a distance of 4 feet, the sewer need not be disturbed if the water line is to be installed at least 24 inches above the existing sanitary sewer. A full joint of the water line, at least 18 feet long, shall be centered over the sanitary sewer crossing, in this case, so as to provide maximum protection against contamination. d. Existing clay, truss or concrete sanitary sewer pipe which shows no evidence of leakage and because of physical limitations shall remain at a higher elevation Revised 9/2008 Section III Page 8 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM than the proposed intersecting water line or closer than 2 feet of spacing may remain undisturbed if the water line is inserted in a joint of pressure -type carrier pipe at least 18 feet long and two (2) nominal sizes larger than the water line. The carrier pipe shall be centered on the sanitary sewer crossing and both ends sealed with cement grout. In lieu of this procedure, that portion of the sanitary sewer within 9 feet of the water line may be replaced with cast iron or ductile iron pipe with water -tight joints as described in Section 290.44(e) of the TCEQ Rules and Regulations, above. Sanitary sewer manholes - provide a minimum 9-foot horizontal clearance from outside wall of existing or proposed sanitary sewer manholes unless manholes and connecting sanitary sewers can be made water -tight and tested for no leakage. If a 9- foot clearance cannot be obtained, the water line may be located closer to a manhole when prior approval has been obtained from the Director of Community Development and the Director of Public Works using one of the procedures below; however, in no case shall the clearance be less than 4 feet: a. A steel water line may be encased in a steel carrier pipe. Open cut and backfill with compacted cement -stabilized sand. b. The water line may be augured past the manhole with one 20-foot section of C- 900 PVC pipe 150 psi, installed centered about the existing sanitary sewer manhole with pressure grout using a bentonite/clay mixture. Fire hydrants. Do not install fire hydrants within 9 feet vertically or horizontally of sanitary sewer mains, service leads, and force mains regardless of construction. 1.05 APPURTENANCES A. Valves. Set at maximum distances along line as follows: a. 6 inch through 14 inch - 1000 feet. b. 16 inch through 20 inch - 2000 feet. C. The total number of valves at any intersection shall equal the total number of lines leading out from the intersection point minus one, three (3) valves for a cross, and two (2) valves for a tee, unless otherwise specified. B. Valve Types 1. Valve types (all valves shall open counterclockwise and have mechanical joints): a. 6 inch through 14 inch — gate valves. b. 16 inch through 20 inch — butterfly valves. C. Location All water lines shall be valved within the street right-of-way. Valves shall not be placed under or within 2 feet of ultimate pavement, except as specifically approved by the Director of Community Development and the Director of Public Works. Revised 9/2008 Section III Page 9 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM 2. Valves shall be located on the projection of intersecting street right -of- way lines or at the curb return adjoining a paved street across the main. Tapping sleeves and valves are excluded from this requirement. 3. Isolate fire hydrants from the service line with a valve located at the fire hydrant branch. This valve shall not be located in the slope or flowline of ditches on open - ditch streets. 4. Intermediate valves, not located on the projection line of the right-of-way line, shall be located on lot lines or 5 feet from fire hydrants but not set in driveways or sidewalks. 5. Locate valves a minimum of 9 feet horizontally from sanitary sewer crossings. D. Fire hydrants. Spacing. a. Single Family Residential Development - 500 foot spacing. b. Commercial, Multi -Family Developments and Multiple Single -Family Dwellings - 300 foot spacing and at all street intersections. Location in or along street right-of-ways. a. Fire hydrants shall be located at street intersections where possible, but in any case not more than than the spacing noted in la and lb. b. Locate fire hydrants at P.C.s of the intersection curb radius, 3 feet behind the existing curb or location of a future curb. C. On all TxDOT highways, county roads and open -ditch streets, set the fire hydrants within 3 feet of right-of-way lines. Fire hydrants lead valves shall not be located in the slopes or flowlines of ditches. d. Set intermediate fire hydrants on lot lines, extended to pavement, when located between right-of-way intersections. These locations may be adjusted 5 feet either way to miss driveways, sidewalks or other obstructions. In either case, do not locate fire hydrants closer than 3 feet to curbed driveways or closer than 5 feet to non -curbed driveways. e. Fire hydrants shall not be installed within 9 feet of a sanitary sewer system under any condition. Location of fire hydrants outside the street right-of-way. a. The City Fire Marshal will establish and approve the location of fire hydrants in apartment complexes and platted private street developments within the city. b. Locate fire hydrants in protected, easily accessible areas behind curb lines. C. For fire hydrants which are located adjacent to water lines constructed in 10- foot wide waterline easements, the fire hydrant shall be centered in a minimum 10-foot by 10-foot separate easement. d. For commercial and multi -family developments inside the city, provide isolation valves at each end of fire loops requiring on -site fire hydrants. Revised 9/2008 Section III Page 10 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM 4. Fire Flow Requirements for Buildings One (1) and two (2) family dwellings: The minimum fire flow requirements for one (1) and two (2) family dwellings having a fire -flow calculation area which does not exceed thirty-six hundred (3,600) square feet shall be one -thousand (1,000) gallons per minute. Fire flow and flow duration for dwellings having a fire -flow calculation area in excess of thirty-six hundred (3,600) square feet shall not be less that that specified in Exhibit A -Table B 105.1 at the end of this section. 5. Fire hydrants should be audited for flow and pressure and painted per City specifications. E. Fittings All fittings shall be identified and described on the construction plans. Fittings are not permitted in fire hydrant leads, except as specifically approved by the Director of Community Development and the Director of Public Works. Normally, all water line fittings shall be mechanical joints only. Push -on joints may be used at special locations if specifically approved by the Director of Community Development and the Director of Public Works. 4. All plugs shall be provided with retention clamps. 5. Polyethylene tube encasement shall conform with the minimum requirements of "Polyethylene Encasement for Gray and Ductile Cast -Iron Piping for Water and Other Liquids", ANSI/AWWA C105, current revision. Soils within the project shall be tested in accordance with Appendix A of ANSI/AWWA C105 to adequately determine the requirements for encasement. 6. Concrete thrust blocking shall be required on all bends, tees, plugs and combinations thereof. 7. All fittings and fire hydrants shall be tied together with 3/4-inch stainless steel all - threads and I -bolts or approved equal (i.e., Mega Lugs). F. Water main service Water main service for lines in or along street right-of-ways. a. Meters 2 inch and smaller - located in rights -of -way, water line easements, or in a minimum 5'x5' separate water meter easement on private property. Meters shall be located in areas with easy access and protected from traffic and adjacent to right-of-way whenever possible. b. Meters 3 inches and larger - located at the property line or in a minimum 10' x 20' separate water meter easement if necessary. Revised 9/2008 Section III Page 11 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM (1) Meters shall be located in areas with easy access and protected from traffic and adjacent to rights -of -ways whenever possible. (2) Meters shall not be located in areas enclosed by fences. C. Separate tap and service leads shall be designed for each meter. d. Meters larger than 2 inches must have bypass assembly and coupling for easy change out. Contact the Public Works Department for additional requirements. For proposed apartments or town homes in private street developments, provide one (1) master meter sized for the entire development. Exceptions may be granted by the Director of Community Development and the Director of Public Works for unusual circumstances. If an exception is approved, do not interconnect multiple meters. All sprinkler and irrigation lines shall be eauitmed with a backflow prevention device according to its application as reauired by current TCEO regulations. The backflow assembly shall be located after the water meter for an irrigation system and in a vault near the building for a sprinkler system. A certified tester shall test the backflow prevention assembly annually and submit the results to the City. 1.06 SUBMITTALS A. General - Conform to the following submittal requirements in addition to those of general procedure of the City of Friendswood. B. Water Line Sizes - Submit justification, calculations, and locations for proposed 6-inch lines and for lines 12-inch and larger, for approval by the Director of Community Development and the Director of Public Works, unless water line sizes are provided by the City in advance. C. Valves - Submit information for approval by the Director of Community Development and the Director of Public Works with justification and locations for the use of 16-inch and 20-inch gate valves proposed as substitutes for butterfly valves. D. Water Meter Service 1. For construction inside the city limits, submit an application for meter services and metered sprinkler connections to the Building Inspections Division prior to construction. 2. Submit requests for more than one service meter in proposed private street or multi -family developments to the Department of Public Works. E. Elevated stream or ditch crossings - Submit design calculations for support columns and column spacing. F. Master Development Plan - For multiple -phase developments, submit a master development plan along with construction plans. Revised 9/2008 Section III Page 12 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM G. Backflow Prevention — All irrigation and sprinklers must be equipped with backflow prevention devices per current TCEQ regulations. 1. A double check backflow prevention assembly is required for 3 inch and larger lines. 1.07 QUALITY ASSURANCE A. Prepare calculations and construction drawings under the supervision of a Professional Engineer licensed by the State of Texas and trained in the disciplines required by the drawings. The final construction drawings must be sealed, signed, and dated by the Professional Engineer responsible for the development of the drawings. 2.0 EXECUTION 2.01 RESEARCH REQUIREMENTS A. Research existing utility and right-of-way information. B. Verify that no restrictions exist that will deny approval of the project concept. 2.02 DESIGN ANALYSIS A. Water line sizes - Prepare narrative justification and calculations for proposed 6-inch lines and for lines 12-inch and larger, unless sizing is provided by the City in advance. B. Elevated stream or Ditch Crossings - Prepare design calculations for support columns and column spacing. 2.03 DRAWINGS A. General: Conform to the following drawing requirements in addition to those of "Graphic Requirements" and the City's standard water line details and standard specifications. B. Appurtenances - Identify, describe and enclose in rectangular box on drawings. Valves a. Designate 6-inch through 12-inch gate valves with box as GV&B. b. Provide complete description and size for other valves. 2. Water meters, service leads, and metered sprinkler connections. a. Show the location of service line tees, tapping sleeve and valves, valve boxes, and temporary plugs to be installed to serve future 3-inch or larger meters. Revised 9/2008 Section III Page 13 of 14 City of Friendswood Community Development Department Design Criteria Manual WATER LINE DISTRIBUTION SYSTEM b. Develop plan and profile sheets for 4-inch and larger leads and connections that cross public rights -of -way or other utilities. C. Construction features Show all special construction features required to complete the project, and in a safe, convenient and economical manner. Auger Construction a. If the construction is predominately open cut, all portions of the street that must be augured shall be clearly shown on drawings by location and length. Include designation for sections at trees with 6 inches or larger diameters located within 10 feet of water Line. b. Curbs - Include a requirement on drawings for construction of ADA ramps at street intersections where curbs are to be removed or are damaged by water line construction. Conform to the City's Standard Details for ADA ramps. Revised 9/2008 Section III Page 14 of 14 Exhibit A Table B105.1 Minimum Required Fire Flow and Flow Duration for Buildingsa Fire -Flow Calculation Area (square feet) FIRE FLOW (gallons per minute)° FLOW DURATION (hours) IA and le Type IIA and IIIAb Type IV and V-Ab Type IS and IIIBb Type V-Bb -Type 0-22,700 0-12,700 0-8,200 0-5,900 0-3,600 1,500 22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750 2 30,201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000 38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250 48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500 59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750 70,901-83,700 39,701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000 3 83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250 97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500 112,701-128,700 63,401-72,400 40,601-46,400 29,301-33,500 18,001-20,600 3,750 128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 20,601-23,300 4,000 145,901-164,200 82,101-92,400 52,501-59,100 37,901-42,700 23,301-26,300 4,250 164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29,300 4,500 183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750 203,701-225,200 114,601-126,700 73,301-81,100 53,001-58,600 32,601-36,000 5,000 225,201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600 5,250 247,701-271,200 139,401-152,600 89,201-97,700 65,401-70,600 39,601-43,400 5,500 271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43,401-47,400 5,750 295,901-Greater 166,501-Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000 4 115,801-125,500 83,701-90,600 51,501-55,700 6,250 125,501-135,500 90,601-97,900 55,701-60,200 6,500 135,501-145,800 97,901-106,800 60,201-64,800 6,750 145,801-156,700 106,801-113,200 64,801-69,600 7,000 156,701-167,900 113,201-121,300 69,601-74,600 7,250 167,901-179,400 121,301-129,600 74,601-79,800 7,500 179,401-191,400 129,601-138,300 79,801-85,100 7,750 191,401-Greater 138,301-Greater 85,101-Greater 8,000 For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 Um, 1 pound per square inch = 6.895 KPA. a. The minimum required fire flow shall be permitted to be reduced by 25 percent for Group R. b. Types of construction are based on the Intemational Building Code. c. Measured at 20 psi. 2003 INTERNATIONAL FIRE CODE® City of Friendswood Community Development Department SECTION IV STREET PAVING DESIGN REQUIREMENTS Design Criteria Manual STREET PAVING 1.0 GENERAL Should any portion of this Section conflict with the Subdivision Ordinance (Appendix B) or the Zoning Ordinance (Appendix C), the latter two (2) shall govern. The Director of Community Development shall have the final interpretation of any provisions in this manual. The Director of Community Development has the right to issue administrative orders or design criteria modifications for just cause related to any provisions or conditions in this manual. 1.01 CHAPTER INCLUDES: Geometric design guidelines for streets, criteria for street paving, and standard paving notes for drawing call outs. 1.02 REFERENCES A. AASHTO - American Association of State Highway and Transportation Officials. B. ASTM - American Society for Testing Materials. C. ACI - American Concrete Institute. D. TxMUTCD - Texas Manual on Uniform Traffic Control Devices. E. City of Friendswood Standard Details, latest version. These can be purchased from Community Development or downloaded from www.ci.friendswood.tx.us 1.03 DEFINITIONS A. Geotechnical Engineer - An engineer certified by the American Association for Laboratory Accreditation (A21,A). B. HMAC - Hot Mix Asphaltic Concrete. C. Curb -and -Gutter Streets — Full -width reinforced concrete pavement with curbs. Curb -and - gutter streets require inlets and underground storm sewers. Revised 9/2008 Section IV Page I of 9 City of Friendswood Communitv Development Department 1.04 Design Criteria Manual STREET PAVING D. Open -Ditch Streets — Full -width reinforced concrete pavement or asphaltic pavement with open ditches. Open -ditch streets do not require underground storm sewers; however, the ditches shall be designed to accommodate the storm water runoff. DESIGN REQUIREMENTS The following design requirements are applicable to all street pavement constructed within right- of-way limits within the city limits of Friendswood. A. General 1. All paving and construction plans for all streets within the city shall be approved by the City of Friendswood. 2. Street design shall conform to all applicable planning tools, such as the Texas Manual on Uniform Traffic Control Devices, major thoroughfare plans, master plans, etc. Other considerations for design shall include street function, street capacity, service levels, traffic safety, pedestrian safety, and utility locations. These additional considerations may effect the minimum requirements set forth herein. Refer to the City of Friendswood Major Thoroughfare Plan for streets requiring additional considerations. 3. Designs shall conform to the City of Friendswood Standard Details. 4. Generally, the use of individual pavers is not allowed in the City of Friendswood right-of-way; stamped concrete is allowed. The only exception for use of individual pavers is for sidewalks in the Downtown District. 5. No asphalt turnouts are allowed in the City of Friendswood rights -of -way. 6. Concrete mix design shall conform to the City of Friendswood Design Specifications. B. Minimum Width Requirements for Concrete Paving: 1. Curb -and -gutter concrete and HMAC streets for low -density residential developments such as SFR, MFR-L and MFR-GHD: 28 feet back to back of curb (B/B). 2. Pavement for open -ditch streets used for only SFR residential developments with minimum 120-foot wide lots: 26 feet edge to edge of pavement. 3. Streets for medium to high density residential, commercial and collector streets: 41 feet BB of curb or from edge of pavement to edge of pavement. Revised 9/2008 Section IV Page 2 of 9 City of Friendswood Community Development Department Design Criteria Manual STREET PAVING 4. Streets for major thoroughfares or boulevards: two divided pavement sections of 25 B/B feet (4-lane divided) or two pavement sections 34 feet B/B of curb (6-lane divided). Radius for cul-de-sac pavement on any street shall be 50 feet, measured from the face of curb. Radius of right-of-way for cul-de-sacs shall be 10 feet greater than the cul-de-sac pavement, but not less than 60 feet. C. Minimum Thickness and Reinforcement Requirements for Concrete and HMAC Pavement: The following requirements shall be the minimum allowable. Pavement thickness and reinforcement not less than the minimum requirements shall be designed by a Professional Engineer, licensed by the State of Texas and who is responsible for the project, with the design based on a current soils analysis and recommendations by a qualified geotechnical engineer. For pavement widths 28 feet BB of curb or 26 feet edge to edge of pavement: a. Minimum concrete slab thickness shall be 6 inches with fc = 3,000 psi and reinforcement shall be Grade 60, fy = 60,000 psi, #4 deformed reinforcing bars spaced at 16 inches center to center both ways and minimum lap lengths of 18 inches. Expansion joints shall be placed at the end of each curb return and at a maximum spacing of 60 feet with control joints every 15 feet. b. Minimum stabilized subgrade thickness shall be 6 inches. 2. For pavement widths greater than 28 feet BB or 26 feet edge to edge of pavement, and for boulevard or major thoroughfare sections: a. Minimum concrete slab thickness shall be 7 inches with f,, = 3,000 psi and reinforcement shall be Grade 60, fy = 60,000 psi, #4 deformed reinforcing bars spaced at 16 inches center to center both ways and minimum lap lengths of 18 inches. Expansion joints shall be placed at the end of each curb return and at a maximum spacing of 60 feet on residential and collector streets, and a maximum spacing of 60 feet on boulevards and major thoroughfares, with control joints every 15 feet. b. Minimum stabilized subgrade thickness shall be 8 inches. D. Subgrade Treatment: The geotechnical engineer shall base depth of subgrade stabilization on structural number (SN) in conjunction with pavement thickness design. The following is a general guidance for subgrade treatment: For subgrade soil conditions with a clay content of 10.0% or higher and plasticity index (PI) of 10 or more, the subgrade shall be stabilized with lime. Subgrade shall be stabilized with a minimum 6% lime by weight, at required thickness and compacted to 95% standard Proctor density. Alternative subgrade stabilization may be substituted when specific recommendations are made by the geotechnical engineer for the project, and when specifically approved by the Director of Community Development. Revised 9/2008 Section IV Page 3 of 9 City of Friendswood Community Development Department Design Criteria Manual STREET PAVING 2. For subgrade soil conditions containing a clean sand with no clay content, the subgrade shall be stabilized with cement. E. Requirements for Intersections, Turnouts, Transitions, and Boulevards or Thoroughfares: l . At a "T" intersection with a street that has not been improved to its ultimate width, the concrete pavement shall be stopped either at the right-of-way line or the end of the curb return, whichever would require less concrete removal at a future date. For roadway turnouts placed at an existing street intersection, the turnout shall be designed to fit the ultimate pavement width of the intersecting cross street and then transitioned to the existing roadway. The transition length for meeting an open -ditch street shall be 50 feet for street widths less than or equal to 28 feet B/B; 75 feet for 29 feet to 40 feet B/B width; and 100 feet for 41 feet BIB width or greater. a. Streets other than concrete shall have transitions with a minimum thickness of 8 inches of lime stabilized subgrade, 6 inches of hot -mix asphaltic concrete base, or approved equal, with 2 inches of hot -mix asphaltic surfacing. b. Concrete streets shall have transitions with a minimum thickness of 6 inches of stabilized subgrade and 6 inches of concrete pavement. When paving only one section of a proposed two -section thoroughfare or boulevard (boulevard section) all left -turn lanes and esplanade crossovers shall be paved to the centerline of the street right-of-way. F. Requirements for Ditches on Open -Ditch Streets: 1. Minimum grade on ditches shall be 0.20 percent. 2. Ditch capacity shall be designed to handle the storm water runoff as determined by the City's Drainage Design Requirements. 3. The maximum side slope shall not be steeper than 3 horizontal to 1 vertical. 4. Culverts for roadside ditches only shall be designed to carry the storm water runoff, but shall not be less than 18-inch diameter pipe constructed of reinforced concrete. G. Requirements for Pavement on Curb -and -gutter Streets: 1. Inlet spacing: a. Curb inlets shall be spaced and sized to intercept the calculated storm water runoff for the design storm. The design water surface elevation for the design storm flow at the inlet shall be less than or equal to the top of curb adjacent to the inlet. Revised 9/2008 Section IV Page 4 of 9 City of Friendswood Design Criteria Manual Community Development Department STREET PAVING b. Maximum travel distance of water in the street from a high point to a curb inlet shall be 300 feet on major thoroughfares, boulevards, commercial streets and collector streets unless otherwise approved by the Director of Community Development. The maximum travel distance of water in the street from a high point to a curb inlet permitted on residential streets shall be 300 feet unless otherwise approved by the Director of Community Development. C. Maximum drop of grade tangents from opposite directions to a common inlet shall be 1.5 feet. d. Curb inlets shall be located on the intersecting side street at an intersection with a higher classification street. Location of curb inlets required on a major thoroughfare at intersections shall be specifically approved by the Director of Community Development. e. Backfill around inlets below grade with 1.5 sacks per cubic yard of cement stabilized sand and to top of first stage of inlets. 2. Design gutter grade shall be 0.30 percent; if the gutter grade is less than 0.30 percent and approved by the Director of Community Development, then the Director of Community Development shall determine the required inlet spacing. The minimum acceptable gutter grade shall be 0.20 percent. 3. Maximum cut from finished grade at property line to top of curb shall be 1.75 feet. 4. Minimum grade shall be 1.0 percent fall around intersection turnout for a minimum radius of 25 feet. Grades for larger radius shall be determined on an individual basis. 5. Vertical curves shall be installed when algebraic differences in intersecting grades exceed 1.0 percent. Elevations shall be shown at 10-foot intervals through vertical curves. Maintain a minimum of 0.03-foot elevation change at 10-foot intervals by altering the calculated elevations. 6. When a curb -and -gutter intersects a drainage ditch, the elevation of the adjacent gutter shall be above the design water surface elevation in the ditch. 7. Minimum gutter grade around a cul-de-sac shall be 0.60 percent. 8. Curves on major thoroughfares shall be superelevated in accordance with AASHTO whenever the centerline radius of any lane of pavement is less than 2,000 feet. 9. The amount of cross slope over the pavement section shall be shown on the drawings. The required cross slope shall be 3/8 inch per foot from curb line to quarter point, and 1/4-inch per foot from quarter point to the center line, and 7/8-inch per foot for left - turn lanes. 10. A minimum grade of 0.40 percent around the longest radius is required on an L-Type street intersection. Revised 9/2008 Section IV Page 5 of 9 City of Friendswood Community Development Department Design Criteria Manual STREET PAVING 11. When meeting an existing upright curbed street, top of new curb elevations shall be designed to meet an elevation 6 inches above the existing gutter/pavement, or gutters shall be matched and new top of 6" curb transitioned to top of existing curb. At existing inlets, top of new curb elevations shall be designed to match existing top of existing inlets. 12. When the curb elevations are not established below the natural ground, fill lines shall be shown on the drawings and shall be of sufficient height to ensure a minimum of 3/8-inch per foot transverse slope toward the curb from the property line between a point, 2 feet outside the right-of-way and the top of curb. If this type fill is required and the pavement is adjacent to a nonparticipating property owner, fill easements from this property owner shall be obtained, filed, and a copy of the easements shall accompany the final drawings. Construction of this nature will require back -slope drainage design to prevent trapping storm water runoff. 13. Elevations and grades shall be labeled for all tops of curb. Centerline elevations and grades are acceptable for open -ditch sections only. H. Requirements for Inlets on Curb -and -gutter Streets: 1. Type "BB" with grate tops or type "H-2" inlets shall be used on all curb -and -gutter streets within the City depending on storm water runoff requirements, unless otherwise approved by the City. 2. Inlets shall be placed at the end of pavement in order to eliminate direct drainage of storm water from the pavement gutter into an open -ditch or onto adjacent property. On open -ditch streets, place stub -outs with ring grates from inlets to ditches. I. Requirements for Curbs and Sidewalks: 1. For curbs located along the outside edges of residential streets, the standard dimensions shall be 4-inches tall and 12-inches wide. Curb height for streets other than residential shall be 6 inches tall. The curb height on all esplanades shall be 6 inches. 2. Sidewalks are required as set out in Section III of Appendix B-Subdivisions and Section 70-66 of the Code of Ordinances, and where sidewalks are required, they shall have a minimum width of 4 feet, except on TxDOT right-of-ways where the minimum width shall be 5 feet. Sidewalk wheelchair ramps shall be required at all intersections, and at or through all driveways where required. The design and installation of such ramps shall comply with Texas Accessibility Standards Architectural Barriers requirements. Revised 9/2008 Section IV Page 6 of 9 City of Friendswood Community Development Department Design Criteria Manual STREET PAVING All sidewalks shall be constructed in accordance with the City of Friendswood Standard Details, including through all driveways where required. The design and installation of such sidewalks shall comply with Texas Accessibility Standards and Architectural Barriers requirements. 5. The location of all proposed and existing sidewalks shall be shown on the construction drawings. Requirements for Miscellaneous Items: 1. The type and amount of subgrade treatment shall be shown on the drawings. 2. Paving headers shall be placed at the end of all concrete pavements. 3. All concrete to be removed shall be saw cut one half of the pavement depth before removal. 4. Sight distance requirements shall be based on the latest version of the AASHTO design practices. 5. Standard City of Friendswood barricades shall be placed at the end of all dead-end streets not terminating in a cul-de-sac. 6. The appropriate drainage agency approval shall be obtained before City approval is granted if the design involves a drainage way or other drainage facility. 7. A letter of agreement from the affected pipeline company(s) is required when any paving is placed over a transmission pipeline or any storm sewer is placed over or under such lines. 8. When new concrete pavement meets existing concrete pavement, horizontal dowels shall be used if no exposed reinforcing steel for interconnection with new pavement exists. Horizontal dowels shall be Grade 60, #6 rebars, 24 inches long, drilled and embedded 12 inches into the center of the existing slab and epoxied. Dowels shall be spaced at 16 inches center to center, unless otherwise specified. 9. Dead-end streets or ends of concrete slabs designed to be extended in the future shall have paving headers and 12 inches of reinforcing steel exposed beyond the pavement, coated with asphalt and wrapped with burlap, or shall have paving headers and dowel type expansion joint for future pavement tie-in. 10. Pavement extensions shall connect to the existing pavement as shown on the City of Friendswood Standard Details. Revised 9/2008 Section IV Page 7 of 9 City of Friendswood Design Criteria Manual Community Development Department STREET PAVING 11. A design for concrete pavement thickness is required for all pavement within industrial areas and on major thoroughfares. Concrete pavement thickness design shall be based on the latest version of the AASHTO design procedures for rigid pavements. 12. The pavement structure for each roadway shall be designed based on soil data from the site and based on the anticipated traffic volume, loading and service life of the proposed pavement structure. The design engineer is responsible for ensuring that the pavement structure is designed to withstand the anticipated loads on the roadway. 1.05 APPURTENANCES — Reserved 1.06 SUBMITTALS — Reserved 1.07 QUALITY ASSURANCE. A. All construction drawings and specifications shall be prepared by or under the supervision of a Professional Engineer licensed by the State of Texas, and all documents shall be sealed, dated, and signed by the engineer responsible for their preparation. B. All geotechnical testing, environmental and similar services for design and testing shall be performed by or under the supervision of a Professional Engineer licensed by the State of Texas and trained in the science of soil analysis. All design and testing reports and documents shall be sealed, dated, and signed by the engineer responsible for their preparation. 2.0 EXECUTION 2.01 RESEARCH REQUIREMENTS — Reserved 2.02 DESIGN ANALYSIS A. All pavement design shall be supported by calculations to establish the required thickness and reinforcement. B. The appropriate geotechnical soils report shall be the basis for design considering the use, loading, and life span of the proposed pavement. C. All drainage improvements shall be designed to accommodate the anticipated storm runoff. 2.03 DRAWINGS A. Construction drawings shall be prepared in compliance with the City of Friendswood Design Criteria Manual, Section One- Graphic Requirements. Revised 9/2008 Section IV Page 8 of 9 City of Friendswood Community Development Department Design Criteria Manual STREET PAVING B. Refer to The City of Friendswood Design Criteria Manual, Appendix B, Figure 1 "Geometric Street Design Standards" for additional information and guidance. Revised 9/2008 Section IV Page 9 of 9 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE SECTION V STORM DRAINAGE DESIGN REQUIREMENTS 1.0 GENERAL Should any portion of this Section conflict with any provisions of the Subdivision Ordinance, of Zoning Ordinance, the Galveston County Consolidated Drainage District or the Harris County Flood Control District the latter four (4) will govern. The Director of Community Development shall have the final interpretation of any provisions in this manual. The Director of Community Development has the right to issue administrative orders or design criteria modifications for just cause related to any provisions or conditions in this manual. 1.01 CHAPTER INCLUDES: Criteria for the design of storm drainage improvements. A. Design requirements - The drainage criteria developed by the City of Friendswood and complemented by those of the Galveston County Consolidated Drainage District and the Harris County Flood Control District is intended to provide design guidelines for protection of all areas of the City from structural flooding resulting from a 100-year storm event. This is accomplished with the application of various drainage enhancements such as storm sewers, roadside ditches, open channels, detention and sheet flow runoff. The combined system is intended to prevent structural flooding from extreme events up to a 100-year storm; all development must account for the 100-year storm event as further detailed in this Section. B. Storm Sewer - Storm sewers and roadside ditch conduits are designed as a balance of capacity and economics. These conduits are designed to convey less intense, more frequent rainfalls with the intent of allowing for traffic movement on streets during these events. C. Street Drainage — When rainfall events exceed the capacity of storm sewer system, the additional run-off is intended to be stored, detained or conveyed overland in a manner that reduces the threat of flooding to structures. Street ponding of short duration is anticipated and designed to contribute to the overall capability of the drainage system. D. Flood Control - The City of Friendswood is a participant in the National Flood Insurance Program. The intent of the flood insurance program is to make insurance available at a reasonable cost by providing for measures that may reduce the likelihood of structural flooding. E. Relationship to the Platting Process - Approval and review of storm drainage is a part of the review process for planning and platting of new developments. The review of storm drainage is overseen by the Community Development Department. Revised 9/2008 Section V Page 1 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE F. Acceptance Procedures — For projects in Galveston County, the Galveston County Consolidated Drainage District must accept and approve all detention ponds or other drainage facilities entering their system before the City of Friendswood accepts the infrastructure. For projects in Harris County, the Harris County Flood Control District will accept and approve all detention ponds as applicable. 1.02 REFERENCES A. City of Friendswood Standard Details and Technical Specifications, latest version. These can be purchased from the Community Development or downloaded from www.ci.friendswood.tx.us B. City of Friendswood Flood Damage Prevention Ordinance, Chapter 34 of the Code of Ordinances, and any subsequent revisions. C. Galveston County Consolidated Drainage District Criteria Manual D. Harris County Flood Control District Design Criteria Manual. Ordinance No. T2007-20 amends the Flood Damage Prevention Ordinance by adopting the Harris County floodplain maps as revised on June 18, 2007. E. TX DOT Bridge Division Hydraulic Manual, the latest edition. F. National Weather Service Documents - TP-40 Rainfall Frequency Atlas of the United States. G. Harris County/City of Friendswood Memorandum of Understanding regarding maintenance of Harris County Hydraulic and Hydrologic models. 1.03 DEFINITIONS Conduit - any open or closed device for conveying storm water. Development - A change in land use that alters the impervious coverage of the tract of land. Impervious cover includes, but is not limited to concrete, asphalt, stabilized soil, tennis courts, water features, pools, sidewalks, crushed concrete, eAd limestone and roofing. Drainage Area Map - Area map of a watershed which is subdivided to show each area served by each subsystem. FEMA - Federal Emergency Management Agency GCCDD- Galveston County Consolidated Drainage District HCFCD - Harris County Flood Control District Revised 9/2008 Section V Page 2 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE Hydraulic Grade Line - A line representing the pressure head available at any given point within the drainage system. In -Fill Development - Development of open tracts of land in areas where the storm drainage infrastructure is already in place and takes advantage of the existing infrastructure as a drainage outlet. Public storm sewers - Defined as sewers and appurtenances that provide drainage for public rights -of -way, or more than one private tract, and are located in public rights -of -way or drainage easements. Private storm sewers — Defined as sewers and appurtenances that provide drainage for a private development, not normally available to the public. Rainfall frequency- Probability of a rainfall event defined by a percent chance of occurring in any given year. Information on rainfall frequency is published by the National Weather Service. For the purpose of storm drainage design, the following frequencies are applicable: 1. 5-year frequency — a rainfall intensity having a 20 percent probability of occurrence in any given year, or nominally likely to occur once every 5 years. 2. 10-year frequency — a rainfall intensity having a 10 percent probability of occurrence in any given year, or nominally likely to occur once every 10 years. 3. 25-year frequency — a rainfall intensity having a 4 percent probability of occurrence in any given year, or nominally likely to occur every 25 years. 4. 100-year frequency - a rainfall intensity having a 1 percent probability of occurrence in any given year, or nominally likely to occur every 100 years. Sheet Flow - Overland stormwater run-off that is not conveyed in a defined conduit. 1.04 DESIGN REQUIREMENTS All designs of drainage facilities shall meet the requirements of the City of Friendswood Standard Details and Technical Specifications. A. Determination of Run-off 1. Design Storm Events - All drainage improvements shall be designed for the following storm frequencies as established by the City of Friendswood, Galveston County Consolidated Drainage District and The Harris County Flood Control District. Revised 9/2008 Section V Page 3 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE Tyne of Facility Frequency Road Side Ditch 5 years Storm Sewers 5 years Channels/Storm Sewers/Culverts draining 100 acres or less 25 years Bridges 100 years Creeks/Channels/Culverts draining 100 acres or more 100 years 2. The Rational Method shall be used for determining the peak flow rate in the sizing of all drainage improvements. a. Time of Concentration (minutes) is the time required for peak runoff from the entire upstream contributing area to reach the point of interest. Time of concentration can be calculated based upon an analysis of the actual travel time from the most remote point in the drainage area. The travel path should be clearly denoted and a sketch included in the design calculations. tc = D/60V + 10 (minutes) D = flow distance (ft) V = flow velocity (ft/sec) For purposes of calculating tc, the following velocities are recommended: V = 1 ft/sec for overland flow V = 1.5 ft/sec or flow across paved surfaces or along gutter flowlines. V = 2 ft/sec for flow in ditch or channel V = 3 ft/sec for flow in storm sewer b. Rainfall Intensity (inches/hour) shall be calculated using the following formula: I = b (d + tc)e Values typically used in Friendswood are listed below: Rainfall tc <=60 min Frequency b d e 5-year 92.9 19.7 0.788 10-year 107.9 23.6 0.781 25-year 98.5 24.0 0.729 100-year 90.8 16.5 0.685 Rainfall t, >60 min Frequency b d e 5-year 70.1 7.7 0.752 Revised 9/2008 Section V Page 4 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE 10-year 96.6 17.2 0.770 25-year 89.2 10.4 0.736 100-year 84.0 11.0 0.679 b, d, and a values are derived from a single frequency rainfall intensity graph. b = the y-intercept of the straight line d = a constant used to adjust the relationship to plot as a straight line e = the slope of the straight line c. The Rational Method is a method for calculating the peak run-off for a storm drain system. The formula for determining the peak flow rate is: Q = Cf CIA Where: Q = Flow rate (cubic feet per second (cfs)) Cf = Frequency factor, the product of Cf and C should not exceed 1.0 C = Runoff Coefficient I = Rainfall intensity (inches/hour) for a given storm frequency (Typically 5 year, 25 year and 100 year). A = Area (acres) For the purposes of peak flow calculations, use the following "Cf' Cf = 1.00, for storm frequencies of 10 years or less Cf = 1.10, for storm frequencies of 25 years Cf = 1.25, for storm frequencies of 100 years For the purposes of peak flow calculations, use the following "C" which are in no way related to the lot coverage percentage as defined in the Zoning Ordinance. Land Use Type Raw Undeveloped Acres Improved Undeveloped Acres (i.e. mowed, filled, re -graded, etc.) Park Land Residential: SFR-Estates SFR Multi -family MFR-GHD MFR-L Run-off Coefficient 0.20 0.30 0.40 0.45 0.60 0.65 0.75 Revised 9/2008 Section V Page 5 of 18 City of Friendswood Community Development Department Design Criteria Manual STORM DRAINAGE MFR-M 0.80 MFR-H 0.85 MHR 0.85 Commercial/Industrial OPDBP 0.90 OBD/CSC/NC 0.95 LI/I 0.95 Pond (detention and amenity) 1.00 Alternatively, for estate -sized lots (greater than 2.0 acres), the run-off coefficient "C" in the Rational Method formula can be calculated from the equation: C = 0.6Ia + 0.2 Where: C = watershed coefficient Ia = impervious area/total area If the alternate form is to be submitted, the calculation of "C" shall be provided as part of the drainage calculations. B. Design of storm sewers 1. Design Frequency a. Areas of New Development The design storm event for sizing storm sewers for new development areas shall be a 5-year storm. In any case where new development interferes with the natural sheet flow of the existing adjacent land, the storm system shall accommodate the runoff. Stubbed -out streets next to undeveloped areas shall have storm sewer lines continuing to an approved outfall. b. In -fill Development An existing storm sewer and structures shall be evaluated using a 5-year storm, assuming no development takes place. The storm sewer and structures shall then be evaluated with the development in place. (1) If the proposed development has a lower or equal impervious cover, no modifications to the existing storm sewer system are required. (2) if the hydraulic gradient of the existing storm drain is below the top of the curb, no improvements to the existing storm sewer system are required. C. Private Drainage Systems Revised 9/2008 Section V Page 6 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE Storm sewers for private drainage systems shall conform to the City of Friendswood Standards for public drainage systems. Minimum diameter pipe for a private storm sewer system is 10 inches. (1) Unless otherwise approved by the Director of Community Development, all private drainage systems shall be constructed in conformance with the public storm sewer standards. (2) An approved permit shall be fled with the City before any work shall be done on a private drainage system, and shall include plan and profile sheets detailing the scope of the work, including elevations. (3) Open ditch areas may be converted into storm sewer lines with the approval of a development permit. Guidelines for the process are available at the City of Friendswood Community Development Department. (4) Private storm sewer connections to public storm sewers shall occur at a manhole or at the back of an inlet as approved by the City. Pipe Velocity and Slope Design a. All storm drains shall be designed by the application of Manning's Equation and the Continuity Equation. Manning's Equation: V = (1.486/n) Rv3S'/' Where V = velocity (ft/sec) R = hydraulic radius (area in square feet/wetted perimeter in feet) S = slope of energy line in feet/feet (same as conduit bottom slopes for uniform flow) n = coefficient of roughness n = 0.013 for concrete pipes, n = 0.024 for CMP n=0.011 for PVC n = 0.010 for HDPE *Note: All public storm sewers in or on public rights -of -way or public drainage easements shall be constructed of RCP unless otherwise approved by the Director of Community Development. Manning's roughness coefficients for CMP, PVC, and HDPE shall be used for storm sewers on private property only. CMP pipes shall be used for public storm sewers only upon specific approval of the Director of Community Development and/or the applicable drainage district entity (GCCDD or HCFCD). Continuity Equation: Q=VA Where Q = discharge (cfs) Revised 9/2008 Section V Page 7 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE V = velocity (ft/sec) A = wetted cross sectional area of conduit (AZ ) b. Design velocities shall be 3 feet per second with the pipe flowing full. C. Maximum velocities shall not exceed 7 feet per second without the approval of the Director of Community Development. d. Minimum Public Storm Sewer Pipe Slopes: Pipe Diameter % Slope 18 0.26 (18" used for inlet leads only) 24 0.18 30 0.14 36 0.11 42 0.08 48 0.07 54 0.06 60 0.05 For pipe sizes not listed above, the minimum slope shall be determined utilizing a design velocity of 3 feet per second. Pipe Sizes and Placement a. Public storm sewer lines and inlet leads shall be a minimum of 24" inside diameter and 18" inside diameter, respectively, or equivalent. Box culverts shall be at least 2 feet x 2 feet inside dimension. b. Larger pipes upstream shall not flow into smaller pipes unless it is intended for detention requirements. C. Match crowns of pipe at any size change unless severe depth constraints prohibit such or engineering calculations show flowlines should be matched. d. Locate public storm sewers in public street rights -of -way or in parallel and adjoining easements or in other approved easements. Easements shall be at least 20-feet wide and the storm sewer shall be centered in the easement. Starting Water Surface and Hydraulic Gradient a. The hydraulic gradient shall be calculated assuming the top of the outfall pipe as the starting water surface. b. At drops in pipe flowline, should the upstream pipe be higher than the hydraulic grade line, then the hydraulic grade line shall be recalculated assuming the starting water surface to be at the tope of pipe at that point. C. For the design storm, the hydraulic gradient shall at all times be below the gutter line elevations at any point along the street. Revised 9/2008 Section V Page 8 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE d. Hydraulic grade lines shall be shown on all profile drawings. 5. Manhole Locations Manholes are required at the following locations: a. Size or cross section changes. b. Inlet lead and conduit intersections. C. Changes in pipe grade. d. Street intersections. e. A maximum spacing of 500 feet measured along the conduit run. f. Manholes shall be placed so as not to be located in driveway or sidewalk areas. g. Adjust manhole frames and covers within the limits of the pavement to meet the proposed final top of slab. 6. Inlets a. Locate inlets at all low points in gutter. b. Valley gutters across intersections are not permitted. C. Inlet spacing is generally a function of gutter slope. For minimum gutter slopes of 0.30 percent, the maximum spacing of inlets shall result from a maximum gutter run of 350 feet from a high point in the pavement to an inlet on a continuously graded street section, for a maximum spacing of 700 feet between inlets. d. If gutter slopes are less than 0.30 percent, the Director of Community Development shall determine the inlet spacing. The acceptable minimum gutter grade is 0.20 percent. e. Use only Standard Inlets: Inlet Application Capacity Type A Parking Lots/Small Areas 2.5 cfs Type B-B Residential 5.0 cfs Type D Parking Lots 2.0 cfs Type E Roadside ditches 20.0 cfs Type H-2 Residential / Commercial 5.0 cfs £ Do not use 'Beehive" style grate inlets or other "specialty" inlets. g. Do not use grate top inlets in an unlined roadside ditch. h. Place inlets at the end of curb return on side streets when such streets intersect streets of a higher classification, unless special conditions warrant otherwise and are approved by the Director of Community Development. i. Storm sewer inlets shall be established in such numbers and in such locations as to effectively drain storm water from paved sections. A graphical plan and calculations of the hydraulic gradient shall be furnished by the design engineer. Revised 9/2008 Section V Page 9 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE C. Consideration of Overland Flow Design Frequency. The design frequency for consideration of overland sheet flow shall consider extreme storm events which exceed the capacity of the underground storm sewer system, resulting in ponding and overland sheet flow through the development to the primary drainage outlet. 2. Relationship of Structures to Street. All structures shall be constructed according to the Flood Damage Prevention Ordinance and shall be higher than the highest level of ponding resulting from the extreme storm event as shown on the latest City adopted flood maps. 3. Calculation of Flow. a. Streets will be designed so that consecutive high points in the street will provide for a gravity flow of drainage to the ultimate outlet. b. The maximum depth of ponding at high points will be the top of curb of streets with curbs, or the elevation of the centerline of roads without curbs. C. The maximum depth of ponding at low points will be 9 inches above the gutter elevation of curb of streets with curbs or 3 inches above the elevation of the centerline of streets without curbs. d. Sheet flow between lots can be provided only through a defined drainage easement. e. A map shall be provided to delineate the flow direction of the extreme event through a proposed development and how this flow is discharged to the primary drainage outlet. f. In areas where ponding occurs and no sheet flow path exists, a calculation shall be provided to show that run-off from the 100-year event can be conveyed and remain in compliance with the other terms of this Section. 4. Overland flow shall enter outfall drainage facilities (channels or detention ponds) through a storm sewer with its last run sized to convey the 100-year event. Calculations shall be submitted for sizing the structure and determining that adequate inlet capacity exists. Maintain pre-existing natural overland flow of storm water and provide protection for adjacent properties from re -directed storm water flows. 6. Show contours of adjacent properties within 200 feet of development greater than 5 acres, and account for natural and existing overland flow or channelized flows. D. Design of Open Channels Design Frequency Revised 9/2008 Section V Page 10 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE a. Open channels shall be designed according to methods described in the GCCDD & HCFCD Criteria Manuals. b. Design standards for channel construction shall follow the requirements specified in the GCCDD & HCFCD Criteria Manuals. C. Design standards for the outfalls into channels shall conform to those in the GCCDD & HCFCD Criteria Manuals. 2. Determination of Water Surface Elevations. a. Water surface elevations shall be calculated using Manning's Equation and the Continuity equation. b. For the design storm event, the water surface for ditches and channels shall be calculated to remain within the banks and at or below the required freeboard. Design of Culverts a. Head losses in culverts shall conform to TxDOT Bridge Division Hydraulics Manual, Chapter 4 - Culverts. E. Design of Roadside Ditches 1. Design Frequency a. Roadside ditches are permissible only for single-family residential lots having widths larger than, or equal to, 120 feet. b. Design storm event for a roadside ditch shall provide 0.5 feet of freeboard below the edge of pavement or the natural ground at the right-of-way line, whichever is lower. C. The design must include an extreme event analysis to indicate that adjoining structures will not be flooded. Velocity Considerations a. For grass -lined sections, the design velocity shall be 2.0 feet per second during the design storm event. The maximum velocity shall be 5 feet per second. b. A grass lined or unimproved roadside ditch shall have side slopes no steeper than 3 horizontal to 1 vertical. C. Minimum grades for roadside ditches shall be 0.20%. d. Calculation of velocity shall use a Manning's roughness coefficient of 0.040 for earthen sections and 0.025 for ditches with paved inverts. e. Use erosion control methods acceptable to the City when design velocities are calculated to be greater than 3 feet per second and are approved by the City. 3. Culverts a. Culverts shall be placed at all driveway and roadway crossings, and other locations where appropriate. b. Culverts shall be designed assuming inlet control. Revised 9/2008 Section V Page 11 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE C. Roadside culverts shall be sized based on drainage area. Calculations shall provide for each block based on drainage design criteria presented in this manual. d. Cross open channels with roadside culverts no smaller than 18 inches in diameter or equivalent. The size of culvert used shall not create a head loss of more than 0.20 feet greater than the normal water surface profile without the culvert. e. Use erosion control methods acceptable to the City when design velocities are calculated to be greater than 3 feet per second and approved by the City. f. Sloped end treatments (S.E.T.) are required on all TxDOT Highways. Depth and Size Limitations for Open Ditches a. Residential streets - the maximum depth shall not exceed 2.5 feet below the edge of pavement. b. Roadside ditch bottoms shall be at least 2 feet wide. C. Ditches in adjoining and parallel easements shall have the top of bank not less than 2 feet from the outside easement line or edge of pavement when applicable. d. Roadside ditch side slopes shall not exceed 3 horizontal to 1 vertical. e. Design storm event for a roadside ditch shall provide 0.5 feet of freeboard below the edge of pavement or the natural ground at the right-of-way line, whichever is lower. F. Design of Outfalls. Outfall design shall conform to GCCDD and HCFCD standards as applicable. 2. Detention pond and storm sewer outfalls shall be placed one foot above the flowline of the receiving channels, creeks and detention pond, or two foot above normal water elevation, whichever is greater. Flowlines of storm sewer outfalls shall be located 6 inches above the flowline of a receiving roadside ditch. G. Storm Water Detention 1. Application of Detention. a. As a normal consideration, storm water detention shall be required. The use of on -site detention is required under certain circumstances enumerated in Subsection G, Items 6 and 7, in order to mitigate potential damage to existing structures unless the current infrastructure is improved, or the City has developed a plan for a detention facility to serve the overall area. b. Design calculations for sizing the detention basin and related structures shall be performed by the applicable method described in the following sections. Revised 9/2008 Section V Page 12 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE C. All calculations shall be sealed and signed by a Professional Engineer licensed by the State of Texas. d. A parking lot with a curb may be used as part of the detention system, provided that the maximum depth of water over the inlet throat flow line does not exceed 9 inches and the maximum depth in any parking stall does not exceed 6 inches. Calculation of Detention Volume a. The Modified Rational Method shall be used to determine the detention storage volume for developments that are 5 acres or smaller. b. A simplified method may be used for determining the amount of detention volume required based upon a rate of 0.45 acre-feet/acre, as found in the GCCDD Criteria Manual. This method may be used for developments less than 5 acres. C. The Triangular Hydrograph method shall be used for determining the amount of detention volume required for development of 100 acres or less. d. The Unit Hydrograph Method, which calculates the required detention storage volume by determining the difference in volumes between the inflow and outflow hydrographs, may be used for developments less than 100 acres. e. For developments with more than 100 acres, a detailed hydrologic analysis utilizing the HEC-1 Flood Hydrograph method shall be required. Calculation of Outlet Size Outfalls which utilize a pipe restrictor to control outflow shall use the orifice equation. a. Reducer or Restrictor Pipes shall be sized as follows: (1) Use the following equations to calculate the required outflow orifice: Area of pipe = nd2A Q = CA (2 gh)�" D=Qia /2.25h-va Where Q = outflow discharge in cfs. C=0.8 h = water surface differential (ft) D = orifice diameter (ft) A = area of pipe (ft') g = gravity (32.2 ft/s2) (2) For head differential in systems outfalling into a roadside ditch or storm sewer, the actual head loss or 1 foot whichever is greater, shall be used. For all other discharge conditions use 2 feet or the difference between 100 year water surface elevation and the elevation of the 25-year storm in the receiving channel, whichever is greater. (3) For detention systems outfalling into a public storm sewer, the restrictor shall be sized based upon the peak 5-year developed flow. Revised 9/2008 Section V Page 13 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE (4) For detention systems outfalling into a public roadside ditch, the restrictor shall be sized based upon the peak 5-year undeveloped flow. (5) For detention systems outfalling into creeks, channels or storm sewers sized to carry the 25-year or 100-year storm, the restrictor shall be metered to release the 5-year, 25-year and 100-year undeveloped flows. (6) Restrictor shall be either the required diameter or the equivalent cross - sectional area. The orifice diameter "D" shall be a minimum of 6 inches. (7) Detention ponds less than 1 acre in size shall have a minimum of 4 inches of freeboard. All ponds 1 acre or larger in size shall have at least 1 foot of freeboard. Freeboard shall be measured from the maximum 100-year water surface elevation and shall not be used in the calculation of storage or mitigation. Detention Pond Structural Requirements a. Side slopes shall not exceed a slope of 4 horizontally to 1 vertically. b. Maintenance berms will be required in accordance with the Galveston County Consolidated Drainage District Design Criteria Manual. C. Ponds with lengths over 50 feet shall have a concrete pilot channel. d. Concrete pilot channels shall have a minimum width of 4 feet and a minimum thickness of 4 inches with #3 rebar spaced at 12 inches on center each way. The concrete channels shall be constructed of 5-sack cement concrete with a compressive strength of 3000 psi at 28 days. Provide a 1-inch depression per every 1 foot of transverse slope with redwood headers spaced every 40 feet. e. Single -user ponds may use a GCCDD-approved alternative to concrete pilot channels. f. Appropriate covering (grass, slope paving, etc.) shall be established on side slopes and pond bottom to prevent erosion during periods of maximum water velocity g. A concrete gravity spillway, set at the maximum ponding elevation, shall be provided at the detention pond outfall structure. h. Wet detention ponds and ponds with vertical walls shall provide access for safety and maintenance purposes. Wet detention systems shall have a method in place to minimize stagnation, such as an aeration system. i. "Dry " detention ponds shall not be designed with less than two feet of depth. Ownership and Easements a. Private Facilities (1) Pumped systems shall not be allowed. Only detention facilities which rely on gravity to discharge storm runoff will be allowed by the City and the GCCDD. (2) Responsibility for maintenance of the detention facility must be indicated on the plat. (3) All private properties being served shall have drainage access to the pond. Revised 9/2008 Section V Page 14 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE (4) A private maintenance agreement must be provided when multiple tracts are being served. b. Public Facilities (1) Facilities will only be accepted for maintenance by the City when such is in the public interest. (2) The City will require a maintenance work area 20 feet wide surrounding the extent of the detention area. Public rights -of -way or permanent access easements may be included as a portion of this 20-foot width. (3) A dedication of easements or reserves must be provided by the plat. (4) Proper dedication of public access to the detention pond must be shown on the plat or by separate instrument. This includes permanent access easements with overlapping public utility easements. Off -Site Detention in the Galveston County Consolidated Drainage District In Galveston County, off -site detention, such as regional or sub -regional detention, may be purchased from the Galveston County Consolidated Drainage District provided: a. The detention facility is in the same watershed or sub -watershed as the site being developed. b. Notwithstanding any other provision contained herein to the contrary, detention for construction or site development relating to single-family residential construction on lots or tracts containing 3.5 acres or less that do not involve the subdivision of land, and for construction or site development relating to multiple -family or commercial construction on lots or tracts containing 2.0 acres or less that do not involve the subdivision of land, shall be in accordance with GCCDD Form DR-001, a copy of which is made a part of this manual. Cost is based on amount of impervious cover. C. The development is less than or equal to 8 acres for any single-family residential development or less than or equal to 5 acres for any other type of development. Cost is determined using an engineered drainage plan. d. Excess detention capacity may not be used for mitigation of fill in the flood plain. e. Regional Detention. It is the desire of the City of Friendswood that regional detention be utilized when available. If new development is within the service area of a publicly -owned or operated regional storm water detention facility, connection to such regional facility shall be as required by the drainage master plan applicable to such facility. f. Regional Detention Purchase Requirements: Residential 0-3.5 acres Impervious Cover Method Residential 3.5-8 acres Purchase based on Engineered Drainage Plan@ Current GCCDD price Residential 8+ acres No Purchase of Detention Available -Drainage Plan Required Revised 9/2008 Section V Page 15 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE Commercial 0-2 acres Impervious Cover Method Commercial 2-5 acres Purchase based on Engineered Drainage Plan@ Current GCCDD price Commercial 5+ acres No Purchase of Detention Available -Drainage Plan Required 7. Redevelopment and Additions in the Galveston County Consolidated Drainage District a. All improved residential lots (less than 3.5 acres) within an existing subdivision served by a detention facility that is within the platted boundaries of said subdivision and that has been previously accepted and approved by the City and the GCCDD, shall be exempt from the regulation to purchase detention for additional impervious cover. b. Residential lots (less than 3.5 acres) in an existing subdivision without an approved detention facility, may purchase regional detention from the GCCDD for additional impervious cover based on the current fees. C. All commercial (2.0 acres or less) and multi -family developments (3.5 acres or less) served by a detention facility that has been previously accepted and approved by the City and the GCCDD, shall be exempt from the regulation to purchase detention for additional impervious cover. 8. Conveyance a. The developer shall provide conveyance to a detention facility without having a detrimental effect on any adjacent properties. b. If conveyance is directed through properties not directly owned by the developer, an executed contract or recorded deed between the parties agreeing to the said conveyance must be presented to the City and the appropriate drainage district entity. C. This procedure is approved by both the City and the corresponding drainage district entity (GCCDD or HCFD) during preliminary plan review. 1.05 RESERVED 1.06 SUBMITTALS A. Preliminary Submittals- Submit for Review and Comment 1. One line drawings are required as part of the platting process. One line drawings shall include: a. Approximate definition of lots and street patterns. b. The approximate drainage areas for each system. C. A definition of the proposed drainage system by single line. d. The proposed pipe diameters. e. Any proposed drainage easements. Revised 9/2008 Section V Page 16 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE f. Floodplain and floodway boundaries, if any. B. Final Design - Submit the following for approval: 1. Copies of any documents which show approval of exceptions to the City design criteria. 2. Design calculations for storm line sizes and grades, and for detention facilities, if any. 3. Design calculations for the hydraulic grade line of each line or ditch, and for detention facilities, if any. 4. Contour map and drainage area map of the project. 5. Plan and profile sheets showing storm sewer or open -ditch design (public facilities only). 6. Projects located within a flood plain boundary or within a flood plain management area shall: a. Show the flood plain boundary or flood plain area, as appropriate, on the one - line drawing or drainage area map. 7. Soil boring logs. 8. All drainage plans shall have a current FEMA flood zone determination statement. C. Signature State - Submit the Following for Approval. 1. Review prints. 2. Original drawings. 3. Storm water detention maintenance agreement letters. 1.07 QUALITY ASSURANCE A. Prepare calculations and construction drawings under the supervision of a Professional Engineer licensed by the State of Texas and trained in the disciplines required by the drawings. The final construction drawings and all design calculations shall be sealed, signed, and dated by the Professional Engineer licensed by the State of Texas responsible for the development of the drawings. PART 2 EXECUTION Revised 9/2008 Section V Page 17 of 18 City of Friendswood Design Criteria Manual Community Development Department STORM DRAINAGE 2.01 RESEARCH REQUIREMENTS — Reserved 2.02 DESIGN ANALYSIS A. All projects shall be tied to National Geodetic Survey (NGS) Datum adjustment which matches the Federal Emergency Management Agency (FEMA) rate maps or the most current NGVD which matches the FEMA rate maps. In the event GPS surveying is used to establish benchmarks, at least two references to benchmarks relating to the FEMA rate maps must be identified. Equations may be used to translate other datum adjustments to the required adjustment. B. Plan sets shall include a drainage area map, which shall contain all storm sewer drainage calculations. C. All drainage systems for curb -and -gutter pavements shall be underground closed conduits; individual residential lot drainage is exempt. Drainage systems for pavements without curb -and -gutter shall be roadside open -ditch sections. D. Soil boring with logs shall be made along the alignment of all storm sewers having a cross section equal to or greater than 72 inches in diameter or equivalent cross section area. Boring should be taken at intervals not to exceed 500 linear feet and to a depth not less than 3 feet below the flow line of the sewer. The required bedding will be determined from the soil boring. E. Plan sets shall include the 5-year Hydraulic Grade Line for storm sewers and roadside ditches on the plan and profile sheets. Revised 9/2008 Section V Page 18 of 18 City of Friendswood Community Development Department SECTION VI SITE DEVELOPMENT Design Criteria Manual SITE DEVELOPMENT 1.0 GENERAL Should any portion of this Section conflict with the Subdivision Ordinance (Appendix B) or the Zoning Ordinance (Appendix C), the latter two (2) shall govern. The Director of Community Development shall have the final interpretation of any provisions in this manual. The Director of Community Development has the right to issue administrative orders or design criteria modifications for just cause related to any provisions or conditions in this manual. Sanitary sewers located on private property that are not in a dedicated easement, are under the jurisdiction of the Plumbing Code, and will be addressed/reviewed by the Building Official. 1.01 CHAPTER INCLUDES: Site Development 1.02 REFERENCES A. City of Friendswood Zoning Ordinance. B. City of Friendswood Subdivision Ordinance. C. City of Friendswood Standard Details, latest version. These details can be purchased from Community Development or downloaded from www.ci.friendswood.tx.us D. Texas Department of Transportation -Traffic Control Plan 1.03 DEFINITIONS A. Commission — Planning and Zoning Commission 1.04 DESIGN REQUIREMENTS A. Site Development Requirements 1. General Requirements a. Site development plans for all site developments within the City of Friendswood shall be approved by the City prior to construction. Revised 9/2008 Section VI Page 1 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT b. Site developments, not including single family residential, shall include any project that affects public water, wastewater, storm drainage, sidewalks or paving facilities. C. All site developments shall conform to the requirements of these Standards, the 2003 International Code Series, and all applicable rules and regulations of the City of Friendswood. d. All wastewater, drainage and paving site development improvements, up to and including the connection to the public system, shall be privately owned, operated and maintained. All water site development improvements, up to, but not including, the meter and meter vault, shall be privately owned, operated and maintained e. Restore the City of Friendswood rights -of -way or easements to existing or better condition than that prior to start of work. f. Private utilities and service lines shall be placed in an easement on the property being served. Design Review Requirements for Site Development Plans. a. All site development plans for proposed developments shall be submitted to the Community Development Department for approval prior to construction. Site development plans shall show all proposed water, wastewater, paving, parking, drainage, street signage, streetlight locations, flood protection facilities, and sidewalks with approved ADA ramps locations and a traffic control plan b. A traffic impact study shall be required for any development proposal expected to generate traffic volumes that will significantly impact the capacity and/or safety of the street system. All proposed developments generating volumes of 5,000 trips per day or greater shall abide by this criteria. The trip estimate shall be based on the latest version of the Institute of Transportation Engineers' Trip Generation Manual. c. The developer should first schedule a Development Review Committee meeting with Community Development Department staff. At this meeting, infrastructure issues and the feasibility of developing the site will be discussed. d. Based on the DRC, the developer shall prepare a site plan for submittal to be reviewed by staff. The developer shall consult with staff until all significant issues surrounding the proposed site plan and development are resolved prior to proceeding to the Commission for review and possible approval. e. The final site plan is prepared after all comments on staff review have been addressed. Any applicant may submit a site plan for consideration by the Commission at any time after the staff review is completed. The Commission reviews the final document for completeness and public awareness. The submittal for the final site plan requires that nine (9) copies of: 1. Site Plan 2. Landscaping Plan 3. Elevation Plan and three (3) copies o£ 1. Drainage Plan 2. Utility Plan 3. Grading Plan Revised 9/2008 Section VI Page 2 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT 4. Photometric Plan 5. Storm Water Pollution Prevention Plan to be provided to Community Development Department staff at least three (3) days prior to the next regularly scheduled Commission meeting. f. Approval from the appropriate drainage entity is required prior to Commission approval. Once the site plan is approved, the developer may begin the building permitting process. g. Three (3) copies of the site development plans shall be submitted to the Building Official for review. The City will typically respond within two (2) to four (4) weeks of the initial submittal. h. When plan changes are requested, two (2) copies of the revised site development plans shall be resubmitted to the City for final review, which will ultimately result in the issuance of the building permit(s). Building Slab Elevations - Minimum building slab elevations shall conform to the requirements of the City of Friendswood Flood Damage Prevention Ordinance and adopted flood zone maps. 4. Water Service - Water service lines and meters shall be sized in accordance with requirements set out in the Waterline Distribution System Design Requirements. Sanitary Sewer Service - Sanitary sewer service leads are normally installed during construction of the public sanitary sewer. When a sanitary sewer service lead is to be installed for a site development, refer to the Wastewater Collection System Design Requirements. All lots, tracts, or reserves shall be connected directly to a public sanitary sewer by a single lead, except as specifically approved by the City. The City shall be contacted for all sanitary sewer connections for commercial projects within the City. Site Drainage Requirements - All commercial, industrial, office, recreational, and multi -family tracts shall have an internal drainage system. The internal drainage system shall collect all site runoff and direct it into a private storm sewer system that shall connect to the public drainage facilities in the area. Any exceptions require specific approval from the City. a. The internal site storm sewer shall be connected to a public storm sewer at a manhole or at an inlet adjoining the site. The site drainage outfall shall be connected to the nearest existing drainage system with adequate capacity to serve the drainage area. Where extension of the existing drainage system is required, all costs for extension shall be the responsibility of the development. b. All internal facilities shall be designed by a Professional Engineer licensed by the State of Texas and shall be sized to drain the site in accordance with these standards. C. Drainage calculations shall be submitted with all site development plans. Other supporting data may be required by the City. d. When the site drains directly into a Galveston County or Harris County facility and/or into a TxDOT or county right-of-way, the appropriate governmental entity(s) shall approve the site development connection to the public facilities. Revised 9/2009 Section VI Page 3 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT 7. Driveways a. It is desirable to minimize the number of non-residential driveways on all streets in order to reduce the number of conflict points and facilitate traffic flow. It is recognized, however, that certain existing tracts may not be able to fully comply with the following standards due to limited frontage or other constraints. b. When compliance with these criteria is precluded for any reasons, attempts should be made to obtain alternative access where feasible, including joint access driveways, access easements to adjoining properties or access to intersecting streets. C. If it can be demonstrated to the City Engineer that sufficient attempts to secure alternative access have been made and that such access is still not possible, the City Engineer may accept a Traffic Impact Analysis performed by a Professional Engineer licensed by the State of Texas to permit a deviation to the driveway spacing requirements indicated herein. d. Residential driveways shall be a minimum of 12 feet wide and a maximum of 18 feet wide at the right-of-way line and should be placed at least 25 feet away from the property line at the intersection of two (2) streets and at least five (5) feet from a property line between two (2) properties. e. Residential lots must have a minimum of 100 feet of frontage in order to be eligible for a circular driveway on the lot, and the two (2) driveways shall have at least 45 feet of separation between them. f. Non-residential driveways shall be a minimum of 25 feet wide and a maximum of 35 feet wide. Non-residential driveways shall be spaced with a minimum of 50-foot separation. g. Non-residential driveways on major thoroughfares/boulevard streets shall be placed no closer than 125 feet from the ultimate curb line of the intersecting major thoroughfare or boulevard street. Non-residential driveways on collector/ minor streets are to be placed no closer than 75 feet from the ultimate curb line of the intersecting major thoroughfare/boulevard street. Non-residential driveways on major thoroughfares/boulevard streets are to be placed no closer than 75 feet from the ultimate curb line of the intersecting collector commercial/minor street. h. For purposes of determining the separation distance, the back of curb or edge of street shall be used in conjunction with the edge of driveway which is closest and parallel to the street from which the measurement is to be taken. i. Non-residential tracts with less than 150 feet of frontage on a public street shall have no more than one (1) driveway. Commercial tracts with between 150 and 320 feet of frontage on a public street shall have no more than two (2) driveways. Commercial tracts with between 321 feet and 600 feet of frontage on a public street shall have no more than three (3) driveways. Commercial tracts with over 600 feet of frontage on a public street shall have the number of driveways specially designated and specifically approved by the City. j. Non-residential driveway connections to the public street shall be approved and inspected by the City, TxDOT or county representatives or appropriate entity. Revised 9/2008 Section VI Page 4 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT k. Driveway radii shall not extend beyond the projection of a property line perpendicular to the back of the curb. 1. Driveways shall be installed according to the City of Friendswood Standard Details. in. Driveways shall be evaluated with respect to location of existing or proposed signage, landscaping and structures for adequate sight distance. n. A note stating, "Access to adjacent property and common driveways may be required," shall be placed on the site plan. o. Curb returns for driveways shall be, at a minimum: i. For residential driveways: a. 5 feet on local streets less than 28 feet in width b. 10 feet on collector streets, major thoroughfares and boulevards, and local streets greater than 28 feet in width ii. For non-residential driveways: a. 25 feet on local streets less that 28 feet in width b. 35 feet on collector streets, major thoroughfares, boulevards, and local streets greater than 28 feet in width 8. Fire Lanes a. Fire lane easements shall be required on all multi -family and non-residential tracts if any part of a building is greater than 150 feet from either a fire lane or a public street right-of-way. b. Fire lanes shall be either 20 feet wide with a 25-foot radius or 25-feet wide with 20 feet radius. C. Fire lanes shall be constructed using the same pavement structural requirements as a public pavement. Alternate materials may be used with specific approval from the City. d. Fire lanes shall be designed to drain in compliance with the Site Development Requirement. e. Fire lane markings shall be provided as specified in the Friendswood Code of Ordinances. f. An emergency vehicle turn -around, whether a cul-de-sac of a radius required by the Fire marshal or a T-head at least 120 feet in length, shall be required under certain conditions. 9. Controlled Access Gate Requirements a. Plans for access control systems shall be submitted to the Fire Marshal's Office and approved prior to construction. b. All access control gates shall have emergency means of operation in the event of power loss. C. Access control gates shall provide a clear, passable width of at least 20 feet. d. A Knox® key switch shall be provided for all controlled access gates. The key switch shall operate all gates. e. A Knox® pad lock shall be provided for all non -motorized gates. f. The location of the key switch shall be approved by the Fire Marshal's Office. g. The owner or owners association shall maintain all parts of the access system and keep them in good working order. Revised 9/2008 Section VI Page 5 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT h. The Fire Marshal's Office and Police Dispatch shall be notified immediately of any damage to the access system that hinders access including, but not limited to, damage to the key box, lock, or gates. 10. Pollution Prevention A pollution prevention plan shall be provided for all site development projects. a. Filter fabric fence shall be installed at the perimeter of the site before construction begins. b. Once construction is completed, either filter fabric fence, 5 feet of hydro -mulch or sod shall be installed at the back of all curbs, or other Best Management Practices shall be implemented. C. Refer to the Storm Water Ordinance for additional requirements. 11. Parking Lot Guidelines A parking lot layout is required to ensure that adequate off-street parking is provided with the construction, alteration, remodeling or change of use of any building or change in use of land. a. Off-street parking spaces shall be located on the same lot, tract, parcel, or premises as the use being served or on other property of the same or less restrictive zoning classification that the owner of the premises being served has a continuing right to use for parking. When the off-street parking spaces are not located on the same lot, tract, parcel, or premises being served, the distance from the center of the parking lot to an entrance to the building or use shall not exceed 500 feet in distance, measured along the shortest available pedestrian route with public access. b. Any existing building or use that is enlarged, structurally altered, or remodeled to the extent of increasing or changing the use by more that 50 percent as it existed shall be accompanied by off-street parking for the entire building or use. When the enlargement, structural alteration, or remodeling is to the extent that the use is not increased or changed by more than 50 percent, additional off-street parking shall only be required for the increased or changed floor area or use. c. Existing parking spaces may not be used to satisfy additional off-street parking requirements unless the existing spaces exceed the number recommended for the building or use for which the existing spaces are associated. d. The number of off-street parking spaces recommended for each building or use shall be determined by reference to the Parking Group Table in Appendix C- Zoning of the Code of Ordinances. Where several different property uses will share a joint parking area, the parking should be computed based upon the overall development. Shopping centers containing not more than 200,000 square feet of gross leasable floor area should have a minimum of six spaces per 1,000 square feet of gross leasable floor area. Shopping centers containing more than 200,000 square feet of gross floor area should have a minimum of 5.5 spaces per 1,000 square feet of gross leasable floor area. e. The design and dimensions of off-street parking areas shall be in accordance with the following table of minimum dimensions. Minimum stall width shall be nine feet, except for residential and all -day office parking which may utilize stalls 8'/2 feet in width, provided that minimum aisle widths are increased by one foot. In Revised 9/2008 Section VI Page 6 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT addition, the dimensions of up to 20 percent of the total number of off-street parking spaces may be reduced to eight feet in width and 16 feet in depth to accommodate compact automobiles, and such spaces must be so marked. All dimensions below are in feet: Angle (degrees) 00 350 450 600 900 Stall, parallel to aisle 23.0 18.0 12.7 10.4 9.0 Stall, perpendicular to aisle 9.0 16.5 19.0 20.0 18.0 Aisle width, one-way 12.0 12.0 12.0 16.0 24.0 Aisle width, two-way 22.0 22.0 22.0 24.0 24.0 Cross aisle, one-way 11.0 11.0 11.0 11.0 11.0 Cross aisle, two-way 22.0 22.0 22.0 22.0 22.0 Refer to Appendix B-Figure 8 of this Design Criteria Manual for Off-street Parking Diagram f. Off-street parking spaces shall be clearly marked. Parking spaces abutting an adjoining property line or street right-of-way shall be provided with wheel guards or bumper guards located such that no part of a normally parked vehicle will extend beyond the property line. When wheel guards are used, they shall be centered 2.5 feet from the property line for 90-degree parking, 2.3 feet for 60- degree parking, and 2.0 feet for 45-degree and 30-degree parking. g. Approval of the parking layout and design of all off-street parking areas shall be given by the Director of Community Development. The Director of Community Development shall determine that spaces provided are usable, and that the circulation pattern within the area is adequate. h. One ADA-compatible space is required for every 25 regular spaces (full-sized or compact -sized) or for any increment thereof. 2.0 EXECUTION 2.01 RESEARCH REQUIREMENTS A. Discuss project concepts outlining proposed features and usage with the City. B. Research existing utility and right-of-way information. C. Verify that no restrictions exist that could result in denial of the project concept. 2.02 DESIGN ANALYSIS - Reserved 2.03 DRAWINGS Revised 9/2008 Section VI Page 7 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT A. The site development plan shall include layout sheet(s) providing a photometric layout of the site complete with location of proposed lights, information on light heights and type of light standard proposed. B. The site development plan shall include an overall drainage layout showing: Total area (in acres) of site to be drained. 2. Area (in acres) drained to each inlet. 3. Contours or an adequate number of spot elevations to indicate area drained to each inlet. 4. Top elevation and flowline elevation at each inlet. 5. Gradient and size on each private storm sewer. 6. Computations to support pipe sizes and grades shown (minimum private storm size shall be 10 inches.) 7. Design velocity for storm sewers shall be 3 feet per second. 8. A TxDOT or a county permit shall be required for drainage affecting a state or county owned/maintained facility. Submit permit with site plan. 9. The drawings shall be prepared and sealed by a Professional Engineer licensed by the State of Texas. 10. The size and location of any required detention facility shall be indicated on the plans, along with the size and location of the outfall structure. C. All site development plans shall be approved by the appropriate drainage entity prior to City approval being granted. E. The site plan shall show all water and sewer service lines with sizes, grades and alignments, and showing appropriate ties into existing public lines. E. The site development plan shall show all parking areas. F. The site development plan shall indicate the types and location of all existing and proposed landscaping. Landscaping shall meet the minimum requirements of Appendix C-Zoning Ordinance. A tree survey is required for first 20 feet of depth adjacent to all proposed streets. If no trees exist, a note to that effect shall be placed on the site development plan. The qualified tree list can be found in Appendix C of this Design Criteria manual. Revised 9/2008 Section VI Page 8 of 9 City of Friendswood Community Development Department Design Criteria Manual SITE DEVELOPMENT G. The site development plan shall show the location, height and area of all proposed buildings. All setback lines as required by the Zoning Ordinance shall also be shown, with a dimension called out on the site plan between the building and the site boundary. H. The land use for all adjacent property shall be shown on the site development plan. I. All parking lot pavement for site development plans shall be engineered to provide for operation and by vehicles normally expected to utilize the parking area, and the thickness of paving shall be based upon the soil conditions underlying the parking area. A Professional Engineer licensed in the State of Texas shall certify the design submitted for approval. J. Concrete sidewalks (a minimum of 4 feet wide and 4 inches thick with steel reinforcement) shall be required along all street frontages. The design and installation of such sidewalks shall comply with Texas Accessibility Standards Architectural Barriers requirements and the City of Friendswood Standard Details. The location of all proposed and existing sidewalks shall be shown on the site development plan. K. Show location of signs, screening walls or fences (indicate height, maximum 8 feet) and dumpsters (with appropriate screening). L. If the site is located within the Community Overlay Development District, a plan note shall be made on the site development plan indicating such; and that the site development will conform the Zoning Ordinance requirements. M. No improvements in or to public right-of-way shall be made without prior City approval. This includes planting trees in a public right-of-way of residential and non-residential areas or in any utility or drainage easement. Only Class 2 and Class 3 trees listed in Appendix C of this Design Criteria Manual may be planted in a public right -of way if such planting is approved by the City. No trees of any class may be planted in utility or drainage easements. Revised 9/2008 Section VI Page 9 of 9 City of Friendswood Design Criteria Manual Community Development and Public Works Department MODIFICATION PROCEDURES SECTION VII MODIFICATION PROCEDURES The City of Friendswood's Director of Community Development may grant a modification to the Design Criteria Manual, if the applicant can prove that the listed circumstances apply. A written application by the applicant must be filed with the Director of Community Development along with sealed engineering reports, drawings, etc. The following is a list of circumstances to apply for a modification: I . There is no available alternative or option that would allow compliance with the Design Criteria Manual in lieu of a modification; and 2. There are special circumstances or conditions affecting the applicant's land involved such that the strict application of the provisions of this chapter would deprive the applicant of all reasonable use of his land; and 3. The granting of the modification will not be detrimental to the public health, safety, or welfare; or injurious to other property in the area; and 4. The granting of the modification will not increase the 100-year flood plain base flood elevation on the upstream or downstream side of the applicant's property; and 5. The granting of the modification will not have the affect of preventing the orderly development of other land in the area in accordance with the provisions of the Design Criteria Manual. The Director of Community Development may grant a modification to the Design Criteria Manual if it is determined, based upon the evidence presented, that an undue hardship or deprivation of reasonable use of land may result from strict compliance with the Design Criteria Manual. A monetary hardship to the applicant, standing alone, shall not be deemed to constitute undue hardship. A modification may be granted so that substantial justice is done and the public interest secured, provided that such modification shall not have the effect of nullifying the intent and purpose of the Design Criteria Manual. A Design Criteria Modification Form is included as Attachment 3. Revised 9/2008 Section VII Page I of I CITY OF FRIENDSWOOD COMMUNITY DEVELOPMENT DEPARTMENT Design Criteria Manual Appendix A Attachments ATTACHMENTS Lift Station Start-up Log 2. ANSI/NSF Standard 60 and 61 Certification 3. Design Criteria Modification Form 4. GCCDD Form DR-001 0 Z i9 > Cl) • J M J h N H N z �p > J Q E J Q C 7 0 Z Q: f > J O am J J ca a 0 0 D Q. > ' E It aD Q o cc (n �/j "a U) J J CU > O O J � Cl)C � cB + - O d J C N m r a)O > 7 LL a E •+ f� a) a)S N f6 M u1 �..r Q cccc Z N N Z o `p a 0- (0 M N M n n N c N N .N Q J> J J a a 0-N Q N 2 N O 3 O O vOi 2_ j N O N �n c E O m Q. J > J d �- Q a z z m o E E a 3 z ) 10 J J C > •L J J LL w O ++ z V O Cl) � m 5 c U ~ Z c C7 0 U g 2 Q' Q mCL O N N (6 N J m N —U N O ui m .a n -0 tU �C a E E cv Z m LL Q o U)Z Z o o g U .. R IQ ai O Q a' a U) in v) 0 Attachment 2 TEXAS NATURAL RESOURCE CONSERVATION COMMISSION PDW PROGRAM STAFF GUIDANCE GuidanceTitle: ANSI/NSF STANDARD 60 AND 61 CERTIFICATION Rules Affected: 30, TAC, §290.42(I), §290.43(c)(8), §290.44(a)(1) and §290.44(I)(2)(B) PAGE 1/1 Sections §290.42(I), §290.43(c)(8), §290.44(a)(1) and §290.44(I)(2)(B)in our current Rules and Regulations for Public Water Systems concern ANSI/NSF product certification for all direct and indirect additives used in the production, treatment, storage and distribution of public drinking water. All such products must conform to ANSI/NSF Standard 60 for direct additives and ANSI/NSF Standard 61 for indirect additives as of January 1, 1993. Since these requirements went into effect wee have been contacted by a number of water system officials and consulting engineers concerning the limited availability of materials which meet these standards. In addition, manufacturers and distributors have informed us of lengthy delays in the certification process. We feel that these concerns are valid and that an interim guidance is necessary until more materials have made their way through the certification process. • The following guidance has been established: All materials which come in direct or indirect contact with public drinking water in any stage of treatment must conform to ANSI/NSF Standard 60 for direct additives and ANSI/NSF Standard 61 for indirect additives. Should no certified material for the intended purpose exist or if there are no such certified materials currently marketed in the State of Texas, a material may be conditionally accepted for use if: The material was previously approved by a nationally recognized authority such as EPA, NSF, USDA or USFDA for direct, indirect or incidental contact with water and/or food, and Proof of submission of the material to an organization accredited by ANSI for certification under ANSI/NSF Standards 60 and 61 is provided. Such proof shall consist of either a dated receipt from NSF, UL or other ANSI accredited organization or a letter from the accredited organization acknowledging that the material has been submitted for evaluation and certification. The conditional acceptance of any single product shall expire when the conditionally accepted product or an alternate competing product receives certification and is marketed within the State of Texas, or the conditiona accepted product is denied certification by an ANSI accredited organization. January 1, 1996 Effective Date N/A Expiration Date END �leeen f: �Ymlc%ry Steven E. Walden, R.S., Manager Public Drinking Water Section Water Utilities Division Attachment 3 CITY OF FRIENDSWOOD DESIGN CRITERIA MODIFICATION FORM Section VII. Modifications to standards identified in the Design Criteria Manual may be permitted by the City of Friendswood's Director of Community Development. The modification proposal must be submitted by a Professional Engineer licensed by the State of Texas and shall follow generally accepted engineering standards for traffic, sidewalk and other infrastructure as applicable, and such proposal contains the following information and substantiates the findings in Paragraph 4 below. If an appeal to the City of Friendswood City Engineer decision is requested, The Construction Board of Adjustment (hereinafter referred to as "the City") will review that appeal. PROJECT NAME: This entire form must be completed in its entirety. If form is submitted incomplete, it will be administratively rejected. PROJECT ENGINEER: SUBMITTAL DATE: SUBDIVISION NAME: MODIFICATION LOCATION: 1. Set forth the proposed deviation to the technical standard. SPECIFIC PROPOSED DEVIATION FROM TECHNICAL STANDARD: 2. Set forth the impact such deviation has on speed differential and street capacity, the likelihood of accidents, the long term maintenance and operation effect, the degree of functionality and efficiency, the technological advancements involved, and other relevant matters. IMPACT OF DEVIATION: 3. Show a comparison of the technical standard to the proposed deviation with respect to overall safety and quality, speed differential, street capacity, existing and projected accidents, long-term maintenance and operation, degree of functionality, degree of efficiency, technological advancements, and other relevant matters. COMPARISON OF TECHNICAL STANDARD TO PROPOSED DEVIATION: Describe all mitigating improvements that reduce the negative impact of the proposed deviation on overall safety and quality, speed differential, street capacity, accident occurrences, long-term maintenance and operation, degree of functionality, degree of efficiency and demonstrating the degree to which the proposed deviation detrimentally affects the foregoing. Other relevant factors, including technological advances, should be explained by describing how they will affect the proposed development. Mitigating improvements can include but are not limited to, traffic control devices, pavement improvements, added acceleration or deceleration lanes or reservoirs, and other on -site improvements. MITIGATING IMPROVEMENTS THAT REDUCE NEGATIVE IMPACT: SUMMARY & CONCLUSION/RECOMMENDATION FOR MODIFICATION: List of Supporting Documentation Attached? Yes No Seal of Professional Engineer: Community Development Use ONLY Reviewed By: Date Modification Request Approved / Denied By: Copies of Backup Information/Notes Attached Director of Date Community Development S / LL § m 3 \ F- 0a 0 g 0§ Lu\ �w z \ / � §/ § § 0 �< zm § § §k2 w �k §w \ \ < Z § §0 LLI ^ -0\§§ 0 §�§�/« < m m a cc m 7§I S �z W ® [ w § z 6w / ® $ �E C.) f §§ §k/ _ z kk /�§)c m �$ z5� /% � W_ E E §kk EI L 2� W� j) \\§k LL Eh 2§zC a. a oz� n� W§�m §§ W0 \kk W �® LL0 §ƒ oz; �\� \� C/) �<w 2; 2§§ o o z o00 ««< 0 §� 2 o�a. C �« 2�§ %3/ S_< §\§ LU �\ <<< \§ §§ LAC) a< m$2 \\LU k0 //w U)3 kkk moo �@@ c�< § § e�� §£C �� x x x x x x )§� 2)� �Lu %2 66± ��- l±E± EZw 0w j< k\ /\0 0/ § 0 §§ §I/§k§) w=�2 <°0 $w < <<< W �J§ n2 <z� � 3W< WW $$$ I §/022$$$ coo d2k 000 �000 <ee W// w� �\ ///%// </ A w z w A B\ § § 2 z 0 0 0 § 0 0 0 §& w § k KEQ$§ oS§W R§ 2§§§ 0§§§ L)�0 <W (L �w0L «wow <m � w§)$ /�0 s) $��\� ��Sf L) =) \--- <- 0WN \§ w o 0 c�R z w �eh0 u� �..•••• z s3= LULU %i § k/) D 0 q= S w £ i§ w -1 LL 8 < wz LL§ < \ CYLL&w «a LL U- msu LL «msu U) ramw EE § $ � ) � E / A » E E 3 \ $ the k 0 4) a CITY OF FRIENDSWOOD COMMUNITY DEVELOPMENT DEPARTMENT Design Criteria Manual Appendix B Figures Figure 1. Geometric Street Design Standards 2. Divided Roadway Cross Sections — Urban 3. Roadway Tapers For Subdivision Streets 4. Undivided Roadway Cross Sections — Urban 5. Typical Length of Median and Median Opening 6. Median Nose and Left Turn Bay Design 7. Offstreet Parking N c Z Q Lri ♦Z/� V W C! N L1 LL CD00 m O 0 0 O LO 0 o ch LO I I} U N N N � p p i W LL LL O O IT 00 N M 0 LO 00 co I W O o p Z N 0 M O N `� 00 O o 000 N 00 LQ co I Z 00 M O N p N DO r � 0 O LO LO LO C) 00 N O Z N W p N cM > p Co N O LO LO (0N LO N L? O LO (o 00 N O Z O 6 ch N W LL o aW o�oWa Z� L>L >���MZ Q�1~i I~�i JoZ Zg pZW�aYaL=�L C-)0-U a: - o ZZWwY � � �gg� Q z �v ���ao 4 44 t, v O CN CO N 04 z O U5 z uj o N N 04 0 000 N O j LL 0 O 0 0 0 W Z O (n cl M O d La s uj 4 CL s Q 09 09 W W WO U tA a z d W z dN di- f Cm u Z�Z �� is im so onend m oc t� h a O W Li ,i,> i O H li O h � W to Z w 0 U W U Z W z W w W Er- U a Li3 o w Q J v � c M N � N w LL�j m S + (0 14 N U 1-11 m Q O QW Q00on m O N 133a=dOr" W LaJ t]G N 6 Z O N � a Uj W Q m ►- V Q ck.' W Z N O til J DO W W W N_ W- W Z cx O tL ~ Z O I-W O O 0 z O L� W O W O W= Lai O m Q J J m W W tL V7 � N N tr Q w Q O a O w a OQ I w m ~CA: z — Z G usO = = J S Q 0 LO. J W W p Z � W Cl-QJQ r0x—, Li J N JLLJ oc0 W II 11 II Z OV LL- OaZ ZOJ N Lai tJCK O O p = EL a CL g C Ln W W N N Q W IX _ z< N p p OL W 00 i F— 3 ?a0 z= a 3 pLai Z j W O W N N a- d tD I I II p W Lr) p imm W i J Q II J N M U .-- W Q CN Ln W Q vd' Z X m ch Ki W in .' W o O I=-0o-,tco CO 0 OC) - QO z Z W � o 0 0 Q Q CD N H �..0 w 0 w (O N > L0 z 0 W zoo�� �z� ag z zQ W� a 00 w cnz�a oQQ �Qz wa wzW z� xwQ g4° a,Q ww0 39oz �Qw �wrx x av, a O Q Uwz �L�a �Ex-H ZHHQO Z Q 0 W 2 Z Z Q W m 0 J C.i a N m W I- Q W w 0 N w W W S V 2 3 0 0 O N s; V Z Z W a 0 Z Q O W 1.� O S H (.7 Z LA J J Q U IL r W r ¢ �3 WLd �- LJ m O ILn O ¢ O M N N � O 1-- W Z N Q o 0 0 p CL m u ¢ �" M N in N 0 W ccCL W � Z OG Z Z O 0 O� I+J Q O M In N In N Z W W O Nv U J W Z a to O o D �M W a �� m ~ to— V) Q O Ir> O 0 O In cx Ov M pn N Lu U V � _ Q W F Z > �W W M W N W O Z N W 11C9 N SUJ F— m =O LU CL DO J U '� cn A M � o z V I W 0 LLI J W 0 Z Z Q W F- Z W m W W Ua U'f � m Z Q � � W W W W a� Q N W a d Fi Ll- J 0 W 7 U Q � � vi Z U p 0 X L j IV W Lai _ in N Z 0 = Q p LLJ QN N Z W O N Laj LJ in O CX W a 3N a v m Q om LLI in�- � Z M CW7 V) � U = Z O U- W = 0 V) � LLI J V)I— w 0 _ Qcx Q LJ W m m Lal N N p ZZ_ Z J J Z �f W "v 23 0 0 c a s o �o LLA II a 11 II II Q m O~ in a Q &n .- V) W Z Z O V) O Z Z W � W W 0 — Z Z a o W co M 3 W W M a^0 18 MIN I �I ulo_ o y y a` I 22' � Wheel Gu ord {� 24'}} NOTE: 2 5' 18' Minimum stall widths shall be nine I M N. feel, except for residential and oll-day office parking which may ulilize stolls M feet in width, provided that the minimum aisle widths are increased by one foot. In addition, the dimensions of up to 20 percent of the total number of offset parking spaces may be reduced to eight feet a in widths and 16 feet in depth to accommodate compact automobiles. Parking spaces abutting an adjoining I WANGLE property line or street right of way shot[ be provided with wheel guards or bumper guards so located that no part of a normally parked vehicle will 16' 24' extend beyond properly line. 0 Q 0 O Q Wheel Guard 2.3' 60" ANGLE I 165 24' l lQ .< <I 19 300 ANGLE ly y I 45°ANGLE m 'I a l0 a o_ OFFSTREET PARKING STALL PERPENDICULAR TO AISLE )COMMUNITY DEVELOPMENT DRAWN: os/oa N.T.S. DETAIL offstreetparking 10.4 MIN. CITY OF FRIENDSWOOD COMMUNITY DEVELOPMENT DEPARTMENT Design Criteria Manual Appendix C Parking Group Table Parking Use Category Recommended Parking Spaces Accommodation Accommodation & Food Services Adult establishment Agricultural, Forestry, Fishing And Hunting Uses Arts, Entertainment & Recreations Broadcast & Telecommunications; Telecommunication Resellers: Information & Data Processing Services Car wash Civic, Social and Fraternal Associations Educational Services (based on maximum design capacity) Daycare center or pre -elementary Elementary school Jr. High School High School or Vocational School College or University Finance & Insurance Gas Station Health Care & Social Assistance Hospitals, Nursing & Residential Care facilities Information Services Mining, Utilities, Construction, Manufacturing, Transportation & Warehousing Mobile home Non -store retailers 1 '/2 spaces for each room/dwelling unit 1 space for every 4 seats or 1 space for every 50 sq. ft. of customer service area, whichever is greater 1 space for every 4 seats or 1 space for every 50 sq. ft. of customer service area, whichever is greater 2 per site + 1 per 1,000 sq. ft. enclosed floor area 1 space for each 250 sq. ft. gross floor area 1 space for each 300 sq. ft. of gross floor area 2 per wash bay, 3 stacking spaces per bay 1 space for each 300 sq. ft. of gross floor area 1 space per 300 sq. ft. of gross floor area 1 space per 20 students and 1 space per staff faculty member 1 space per 15 students and 1 space per staff faculty member 1 space per 3 students and 1 space per staff faculty member 1 space per commuter student and 1 space per staff faculty member 1 space for each 300 sq. ft. of gross floor area 1 space for each bay, plus 1 space for each pump island, minimum 6 spaces 1 space for each 250 sq. ft. gross floor area 1 space for each 1 '/z beds 3 spaces for each 5 employees on largest shift, or 1 space per 600 sq. ft. of gross floor area 3 spaces for each 5 employees on largest shift, or 1 space per 600 sq. ft. of gross floor area 2 '/2 spaces per trailer unit 1 space for each 2,000 sq. ft. of gross floor area Amusement and Recreation Industries Arcade 1 space per 200 sq. ft. of gross floor area Driving/archery/shooting range 1 space per 200 sq. ft. of gross floor area of indoor facilities, plus 1 space per tee or target Fairground, exhibition, carnival 1 space per 500 sq. ft. of outdoor site area, plus 1 space per 4 fixed spectator seats Go-carts and all -terrain vehicles 1 space per 2 vehicles, plus 1 space per 4 spectator seats Golf Course I space per 150 sq. ft. of gross floor area of indoor facilities, plus 5 spaces per green Miniature Golf 1 space per 200 sq. ft. of gross floor area of indoor facilities, plus 1.5 spaces per hole Rodeo, circus, auto/motorcycle 1 space per 3 spectator seats racing Skateboarding, water slide 1 space per 200 sq. ft. of gross floor area of indoor facilities, plus 1 space per 2 persons design capacity of outdoor facilities Sport fields, swimming pools, 1 space per 100 sq. ft. of gross floor area of indoor facilities private parks and playgrounds plus 1 space per 4 persons design capacity of outdoor facilities, including both participants and spectators as applicable Tennis and other sport courts 2 spaces per court Other Services 1 space for each 250 sq. ft. gross floor area Professional, Scientific & Technical I space for each 300 sq. ft. of gross floor area Services: Management of Companies & Enterprises; Administration/Support Services Public Administration 1 space for each 300 sq. ft. of gross floor area Real Estate, Rental & Leasing 1 space for each 300 sq. ft. of gross floor area Religious Organizations 1 space for each 4 seats in the largest auditorium, or 1 space for each 800 square feet of gross floor area, which ever is larger Residential Uses 2 spaces per household Retail Trade 4 spaces for each 1,000 sq. ft. gross floor area Transit & Ground Passenger 1 space per 100 sq. ft. of gross floor area Transportation; Scenic & Sightseeing Transportation Truck Transportation; Warehousing & 1 space for each 1,000 sq. ft. non -office floor area plus 1 space Storage for each 300 sq. ft. office area Vehicle Dealers 1 space for each 5,000 sq. ft. of lot area Whole Sale Trade 1 space per 2,000 sq. ft. of gross floor storage/sales area CITY OF FRIENDSWOOD COMMUNITY DEVELOPMENT DEPARTMENT Design Criteria Manual Appendix C Qualified Tree List Qualified Tree list by class of tree Common name Botanical name Class N/1 Site Light Size E/D Bald Cypress Taxodium distichum I N 2,3 2 1 D Bur Oak Quercus macrocarpa I N 2 1 l D Cedar Elm Ulmus crassifolia 1 N 2 1 2 D Drummond Red Maple Acer rubrum var. drummondii 1 N 2 1 2 D Eastern Redbud Cercis canadensis I N 2 2 2 D Live Oak Quercus virginiana 1 N 2 l 1 SE Overcup Oak Quercus lyrata 1 N 2,3 1 1 D Pecan Carya illinoensis 1 N 2 1 1 D Possumhaw Holly Ilex decidua 1 N 2 1,2 3 D Shumard Red Oak Quercus shumardii 1 N 2 1 1 D Southern Magnolia Magnolia grandiflora l N 2 1 1 E Swamp Chestnut Oak Quercus michhauxii I N 2,3 1 1 D Sweet -Bay Magnolia Magnolia virginiana 1 N 2 2 2 E Wax Myrtle Myrica cerifera 1 N 2/3 1 3 E American Elm Ulmus americana 2 N 2 l 1 D American Sycamore Platanus occidentalis 2 N 2 1 1 D Anacua/Sandpaper Tree Ehretia anacua 2 N 2 1 2 E Arrow -wood Viburnum Viburnum dentatum 2 N 2 2 3 D Black Hickory Carya texana 2 N 2 1,2 2 D Black Walnut Juglans nigra 2 N 2 1,2 1 D Blackgum Nyssa sylvatica 2 N 2,3 1,2 3 D Callery Pear/Braford Pyrus calleryana 2 I 2 l 3 D Carolina buckthorn Rhamnus caroliniana 2 N 2 1,2 3 D Chalk Maple Acer leucoderme 2 N 2 2 2 D Cherry Laurel Prunus caroliniana 2 N 2 2 2 E Chinese Elm Ulmus parvifolia 2 I 2 l 2 D Chinquapin Oak Quercus muhlenbergii 2 N 2 1 1 D Common Crapemyrtle Common Fig Common Persimmon Eastern Red Cedar Eve's Necklace Green Ash Huisache Loblolly Pine Mexican Plum Nuttail Oak Ornamental Holly Paloverde Parsley Hawthorn Post Oak Red Bay River Birch Rough -leaf Dogwood Rusty Blackhaw Viburnum Sassafras Scarlet (Red) Buckeye Shagbark Hickory Slash Pine Snowbell Southern Red Oak Sweetgum Texas Mountain -Laurel Texas Persimmon Texas Pistache Texas Redbud Water Hickory Water Oak Western Soapberry White Ash White Oak Willow Oak Winged Elm Woollybucket Bumelia Wright Acacia Yaupon Holly American Elderberry American Holly American Hornbean Black Locust Lagerstroemia indica 2 I 2 1 3 D Ficus carica 2 I 2 1 3 D Diospyros virginiana 2 N 2 1 2 D Juniperus virginiana 2 N 2 1,2 2 E Sophora affinnis 2 N 1 1 3 D Fraxinus pennsylvanica 2 N 2,3 1,2 1 D Acacia famesiana 2 N 1 1 3 D Pinus taeda 2 N 2 1 1 E Prunus mexicana 2 N 1 1 3 D Quercus nuttallii 2 N 2/3 1 1 D Ilex spp. 2 I 2 1,2 3 E Parkinsonnia aculeata 2 N 1 1 2 D Crataegus marshallii 2 N 2 2 3 D Quercus stellata 2 N 2 2 1 D Persea borbonia 2 N 2 2 2 E Betula nigra 2 N 2,3 2 2 D Corpus drummondii 2 N 1,2 3 3 D Viburnum rufidulum 2 N 2 2 3 D Sassafras albidum 2 N 2 2 2 D Aesculus pavia 2 N 2 2 3 D Carya ovata 2 N 2 1 1 D Pinus elloittii 2 1 2 1 1 E Styrax americana 2 N 2 1,2 3 D Qurcus falcata var. pagoda 2 N 2 1 1 D Liquidambar styraciflua 2 N 2 1 1 D Sophora secundiflora 2 N 1 1 3 E Diospyros virginiana(male) 2 N 1 1 3 D Pistacia texana 2 N 1 1 3 D Cercis canadensis texensis 2 N 1,2 2 3 D Carya aquatica 2 N 2,3 1 2 D Quercus nigra 2 N 2/3 1 1 D Sapindus drummondii 2 N 2 1 2 D Fraxinus americana 2 N 2 1 1 D Quercus alba 2 N 2 1 1 D Quercus phellos 2 N 2/3 1 1 D Ulmus alata 2 N 2 1 2 D Bumelia lanuginosa 2 N 2 2 2 D Acacua wrightii 2 N 1 1 3 D Ilex vomitoria 2 N 2 1 /2 3 E Sambucus canadensis 3 N 2 2 3 D Ilex opaca 3 N 2 2 2 E Carpinus caroliniana 3 N 2 2 2 D Robinia pseudoacacia 3 N 2,3 1 2 D Black Willow Box -Elder Maple Camphor -Tree Catalpa Common Pear Eastern Cottonwood Flowering Crabapple Hercules -Club Prickly -Ash Honey -Locust Japanese Yew Japanese Maple Loquat Mesquite Mexican Buckeye Red Mulberry Sugar Hackberry Vitex Water Tupelo Weeping Willow Arborvitae Arizona Ash Berlandier Ash Chinaberry Chinese Pistache Chinese Tallow Eucalyptus Golden-Raintree Japanese Black Pine Mimosa(Silktree) Mulberry Siberian Elm Silver Maple Tulip -Tree Salix nigra 3 N 3 1 2 D Acer negundo 3 N 2 2 2 D Cinnamomum camphora 3 I 2 1 2 E Catalpa bignonioides 3 N 2 1 2 D Pyrus communis 3 N 2 1 2 D Populus deltoides (male) 3 N 2 1 1 D Malus spp. 3 1 2 1 3 D Zanthoxylum clava-herculis 3 N 1 1 3 D Gleditsia triacanthos 3 N 2,3 1 2 D Podocarpus macrophyllus 3 1 2 1 2 E Acer palmatum 3 1 2 2 3 D Eriobotryajaponica 3 1 2 2 3 E Prosopis glandulosa 3 N 1 1 2 D Ungnadiaspeciosa 3 N 1 1 3 D Morus rubra 3 N 2 1 2 D Celtis laevigata 3 N 2 1,2 2 D Vitex agnus-castus 3 I 1 1 3 D Nyssa aquatica 3 N 3 2 1 D Salix babylonica 3 1 3 1 2 D Thuja spp. 4 1 Fraxinus velutina 4 1 Fraxinus berlandieriana 4 1 Melia azedarach 4 1 Pistacia chinensis 4 1 2 1 2 D Sapium sebiferum 4 1 Eucalyptus spp. 4 1 1,2 1 3 E Koelreuteria paniculata 4 1 2 1 2 D Pinus thunbergi 4 1 2 1 2 E Albizia julibrissin 4 1 Morus alba 4 I 2 1 2 D Ulmus pumila 4 I Acer saccharinum 4 1 Liriodendron tulipifera 4 I 2 1 1 D Trees are divided into four classes. Class 1 and 2 trees are considered the most valuable in enhancing the environment and are the most likely to prosper in the Friendswood area. Therefore, only Class 1 and 2 trees shall be approved as new plantings for a) city parks and property, and parking lots and b) for streets or other public right-of-ways, respectively, unless otherwise approved by the Director of Community Development on the advice of an Urban Forester. Species that are classified as shade trees will reach a height and size that will conflict with overhead powerlines, permanent structures, or the canopy will exceed the limits of a confined space. Species that are classified as small trees will not provide the protection or aesthetic impact of a large shade tree, yet they are suitable for planting beneath powerlines and are good alternatives for areas of limited space. Class 1: for the most part this class is for trees that are native, will do relatively well in the Friendswood area, have few diseases or pest problems, are easy to find in local nurseries and with few exceptions (redbud, possomhaw and waxmyrtle) are larger in size. Class 2: this class is for trees that are mostly native, will still do well in the Friendswood area, have little disease or pest problems, sometimes not quite as easy to find in nurseries, are more varied in size and in many cases are more suitable for wildlife. These trees tend to have either larger and messier fruit and/or are thornier than trees in Class 1. Some of these trees are also more prone to some decay at maturity and might not do as well in urbanized areas. Class 3: this class starts to pick up more introduced species, the trees might or might not do as well in the Friendswood area, require a little more maintenance and care, the natives might be harder to find in a nursery while the introduced species may be more readily available and in some cases these trees are more prone to decay, disease and pest problems. Class 4: this class is exclusively introduced species. They may or may not do well in Friendswood. If they do grow well they have the potential to become invasive species and cause problems for local ecosystems and are more prone to decay, disease and pest problems. NOT RECOMMENDED FOR PLANTINGS. Classifications N--Native I —Introduced Site 1--Xerophytic (requires little water) 2--Mesic (requires moderate water with good drainage) 3--Aquatic (tolerates poor drainage once established 3 years) Once Established Size 1--60 feet and greater ultimate height (large shade tree) 2--30 to 60 feet in ultimate height (medium tree) 3--30 feet and less in ultimate height (small tree) Foliage. D--Deciduous (sheds leaves annually) If placed on the south and west walls will reduce indoor temperatures in summer by shading the roof and walls. In winter, these trees allow sunlight through to help heat the house. E--Evergreen (having green leaves/needles through out the year) Can create a wind break if placed on the Northwest side of a building. SE --Semi evergreen For example, the code for Live Oak is 1/N/2/l/l, which indicates that the Live Oak is a Class 1 species that is native to Texas, requires moderate water with good drainage, demands or tolerates full sun, and will exceed 60 feet in ultimate height. As a shade tree, the Live Oak will provide protection and has aesthetic impact but the tree is not suitable for planting beneath powerlines or within confined spaces, or in streets or other public rights -of -way.